Form 150.62-EG5 (108)<br />

AIR-COOLED<br />

SCROLL CHILLERS<br />

STYLE B<br />

(Round Tube Condenser Coils)<br />

<strong>YLAA</strong>0070 – <strong>YLAA</strong>0150<br />

70 – 150 TON<br />

246 – 527 kW<br />

60 Hz<br />

R-410A


Table of contents<br />

Specifications........................................................................................................................................................................................................ 3<br />

Microcomputer Control Center............................................................................................................................................................................ 4<br />

Accessories and Options..................................................................................................................................................................................... 6<br />

Design Parameters............................................................................................................................................................................................... 8<br />

Water Pressure Drop............................................................................................................................................................................................ 9<br />

Selection Criteria and Procedures.................................................................................................................................................................... 10<br />

Pump Selection Criteria..................................................................................................................................................................................... 12<br />

Pump Pressure Drop Curves............................................................................................................................................................................. 14<br />

Single Pump Curves........................................................................................................................................................................................... 16<br />

Dual Pump Curves.............................................................................................................................................................................................. 17<br />

Ratings - 60 Hz.................................................................................................................................................................................................... 18<br />

Part Load Ratings – Standard Efficiency.......................................................................................................................................................... 26<br />

Part Load Ratings – High Efficiency................................................................................................................................................................. 27<br />

Physical Data - English...................................................................................................................................................................................... 28<br />

Dimensions – Four Fan Units............................................................................................................................................................................ 30<br />

Dimensions – Six Fan Units............................................................................................................................................................................... 31<br />

Dimensions – Eight Fan Units........................................................................................................................................................................... 32<br />

Isolator Locations............................................................................................................................................................................................... 33<br />

Isolator Details.................................................................................................................................................................................................... 35<br />

Electrical Notes................................................................................................................................................................................................... 38<br />

Electrical Data w/o Pumps................................................................................................................................................................................. 40<br />

Electrical Data w/ Pumps................................................................................................................................................................................... 42<br />

Wiring Diagram.................................................................................................................................................................................................... 50<br />

Elementary Wiring .............................................................................................................................................................................................. 52<br />

Condenser Fan Mapping and Sequencing....................................................................................................................................................... 54<br />

Compressor Wiring............................................................................................................................................................................................. 55<br />

Power Options Connection Diagram................................................................................................................................................................. 56<br />

Power Panel......................................................................................................................................................................................................... 57<br />

Dual Pump Wiring............................................................................................................................................................................................... 58<br />

Wiring................................................................................................................................................................................................................... 59<br />

MicroPanel Connections.................................................................................................................................................................................... 60<br />

Application Data.................................................................................................................................................................................................. 63<br />

Guide Specifications.......................................................................................................................................................................................... 64<br />

NOMENCLATURE<br />

The model number denotes the following characteristics of the unit:<br />

0070<br />

Y<br />

E<br />

York Chiller<br />

A = Americas<br />

4 Digit Unit Number<br />

E<br />

410A<br />

Unit Designator<br />

Z = Standard Efficiency (round tube)<br />

Y = High Efficiency (round tube)<br />

<br />

jOHNSON CONTROLS


Specifications<br />

FORM 150.62-EG5 (108)<br />

GENERAL<br />

The 70 - 150 Ton (246 - 527kW) <strong>YLAA</strong> models are shipped<br />

complete from the factory ready for installation and use.<br />

The unit is pressure-tested, evacuated, and fully charged<br />

with a zero Ozone Depletion Potential Refrigerant R-<br />

410A and includes an initial oil charge. After assembly, a<br />

complete operational test is performed with water flowing<br />

through the cooler to assure that the refrigeration circuit<br />

operates correctly.<br />

The unit structure is heavy-gauge, galvanized steel. This<br />

galvanized steel is coated with baked-on powder paint,<br />

which, when subjected to ASTM B117 1000 hour, salt<br />

spray testing, yields a minimum ASTM 1654 rating of<br />

“6”. Units are designed in accordance with NFPA 70 (National<br />

Electric Code), ASHRAE/ANSI 15 Safety code for<br />

mechanical refrigeration, ASME and rated in accordance<br />

with ARI Standard 550/590.<br />

COMPRESSORS<br />

The chiller has suction-gas cooled, hermetic, scroll compressors.<br />

The <strong>YLAA</strong> compressors incorporate a compliant<br />

scroll design in both the axial and radial direction. All rotating<br />

parts are statically and dynamically balanced. A large internal<br />

volume and oil reservoir provides greater liquid tolerance.<br />

Compressor-crankcase heaters are also included for extra<br />

protection against liquid migration.<br />

COOLER<br />

The cooler is equipped with a heater controlled by a separate<br />

thermostat. The heater provides freeze protection<br />

for the cooler down to -20 o F (-29°C) ambient. The cooler<br />

is covered with 3/4” flexible, closed-cell, foam insulation<br />

(K=0.25).<br />

The water baffles are constructed of brass to resist corrosion.<br />

The removable heads allow access to the internally<br />

enhanced, seamless, copper tubes. Vent and drain connections<br />

are included.<br />

Water inlet and outlet connections are grooved for compatibility<br />

with field supplied ANSI/AWWA C-606 couplings.<br />

CONDENSER<br />

Coils – Fin and tube condenser coils of seamless, internally-enhanced,<br />

high-condensing-coefficient, corrosion<br />

resistant copper tubes are arranged in staggered rows,<br />

mechanically expanded into aluminum fins. Integral subcooling<br />

is included. The design working pressure of the<br />

coil is 650 PSIG (45 bar).<br />

Fans – The condenser fans are composed of corrosion<br />

resistant aluminum hub and glass-fiber-reinforced polypropylene<br />

composite blades molded into a low-noise airfoil<br />

section. They are designed for maximum efficiency and<br />

are statically and dynamically balanced for vibration-free<br />

operation. They are directly driven by independent motors,<br />

and positioned for vertical air discharge. The fan guards<br />

are constructed of heavy-gauge, rust-resistant, coated<br />

steel. All blades are statically and dynamically balanced<br />

for vibration-free operation.<br />

Motors – The fan motors are Totally Enclosed Air-Over, squirrel-cage<br />

type, current protected. They feature ball bearings<br />

that are double-sealed and permanently lubricated.<br />

jOHNSON CONTROLS


Microcomputer Control Center<br />

All controls are contained in a NEMA 3R/12 cabinet with<br />

hinged outer door and includes:<br />

Liquid Crystal Display with Light Emitting Diode backlighting<br />

for outdoor viewing:<br />

Two display lines<br />

Twenty characters per line<br />

Color coded 12-button non-tactile keypad with sections<br />

for:<br />

DISPLAY/PRINT of typical information:<br />

Chilled liquid temperatures<br />

Ambient temperature<br />

System pressures (each circuit)<br />

Operating hours and starts (each compressor)<br />

Print calls up to the liquid crystal display:<br />

Operating data for the systems<br />

History of fault shutdown data for up to<br />

the last six fault shutdown conditions<br />

An RS-232 port, in conjunction with this<br />

press-to-print button, is provided to permit<br />

the capability of hard copy print-outs via a<br />

separate printer (by others).<br />

ENTRY section to:<br />

ENTER setpoints or modify system values<br />

SETPOINTS updating can be performed to:<br />

Chilled liquid temperature setpoint and range<br />

Remote reset temperature range<br />

Set daily schedule/holiday for start/stop<br />

Manual override for servicing<br />

Low and high ambient cutouts<br />

Number of compressors<br />

Low liquid temperature cutout<br />

Low suction pressure cutout<br />

High discharge pressure cutout<br />

Anti-recycle timer (compressor start cycle<br />

time)<br />

Anti-coincident timer (delay compressor<br />

starts)<br />

UNIT section to:<br />

Set time<br />

Set unit options<br />

UNIT ON/OFF switch<br />

The microprocessor control center is capable of displaying<br />

the following:<br />

• Return and leaving liquid temperature<br />

• Low leaving liquid temperature cutout setting<br />

• Low ambient temperature cutout setting<br />

• Outdoor air temperature<br />

• English or Metric data<br />

• Suction pressure cutout setting<br />

• Each system suction pressure<br />

• Discharge pressure (optional)<br />

• Liquid Temperature Reset via a Johnson Controls ISN<br />

DDC or Building Automation System (by others) via:<br />

- a pulse width modulated (PWM) input as standard<br />

- a 4-20 milliamp or 0 -10 VDC input, or contact<br />

closure with the optional B.A.S. interface option<br />

• Anti-recycle timer status for each system<br />

• Anti-coincident system start timer condition<br />

• Compressor run status<br />

• No cooling load condition<br />

• Day, date and time<br />

• Daily start/stop times<br />

• Holiday status<br />

• Automatic or manual system lead/lag control<br />

• Lead system definition<br />

• Compressor starts & operating hours<br />

(each compressor)<br />

• Status of hot gas valves, evaporator heater<br />

and fan operation<br />

• Run permissive status<br />

• Number of compressors running<br />

• Liquid solenoid valve status<br />

• Load & unload timer status<br />

• Water pump status<br />

<br />

jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

Provisions are included for: pumpdown at shutdown;<br />

optional remote chilled water temperature reset and two<br />

steps of demand load limiting from an external building<br />

automation system. Unit alarm contacts are standard.<br />

The operating program is stored in non-volatile memory<br />

(EPROM) to eliminate chiller failure due to AC powered<br />

failure/battery discharge. Programmed setpoints are retained<br />

in lithium battery-backed RTC memory for 5 years<br />

minimum.<br />

BUILDING AUTOMATION SYSTEM INTERFACE<br />

The factory addition of a Printed Circuit Board to accept<br />

a 4-20 milliamp, 0-10VDC or contact closure input to reset<br />

the leaving chiller liquid temperature from a Building<br />

Automation System. (Only one of following options can be<br />

offered on a unit at a time: BAS, Remote Control Panel or<br />

Multi-unit Sequence Control.) (Factory-mounted)<br />

- (The standard unit capabilities include remote startstop<br />

or up to two steps of demand (load) limiting<br />

depending on model.)<br />

- (The standard control panel can be directly connected<br />

to a Johnson Controls Building Automated System via<br />

the standard on-board RS485 communication port.)<br />

POWER PANEL<br />

Each panel contains:<br />

• Compressor power terminals<br />

• Compressor motor starting contactors per l.E.C.*<br />

• Control power terminals to accept incoming for<br />

115-1-60 control power<br />

• Fan contactors & overload current protection<br />

The power wiring is routed through liquid-tight conduit<br />

to the compressors and fans.<br />

* International Electrotechnical Commission<br />

jOHNSON CONTROLS


Accessories and Options<br />

POWER OPTIONS:<br />

COMPRESSOR POWER CONNECTIONS – Single-point<br />

terminal block connection(s) are provided as standard.<br />

The following power connections are available as options.<br />

(See electrical data for specific voltage and options availability.)<br />

(Factory-mounted)<br />

<br />

SINGLE-POINT SUPPLY TERMINAL BLOCK – Includes<br />

enclosure, terminal-block and interconnecting<br />

wiring to the compressors. Separate external protection<br />

must be supplied, by others, in the incoming<br />

compressor-power wiring. (Do not include this option<br />

if either the Single-Point Non-Fused Disconnect Switch<br />

or Single-Point Circuit Breaker options have been<br />

included.)<br />

SINGLE- POINT NON- FUSED DISCONNECT<br />

SWITCH OR MULTIPLE-POINT NON-FUSED DIS-<br />

CONNECT SWITHCHES – Unit-mounted disconnect<br />

switch(es) with external, lockable handle (in compliance<br />

with Article 440-14 of N.E.C.), can be supplied to isolate<br />

the unit power voltage for servicing. Separate external<br />

fusing must be supplied, by others in the power wiring,<br />

which must comply with the National Electrical Code<br />

and/or local codes.<br />

SINGLE-POINT NON-FUSED DISCONNECT SWITCH<br />

WITH INDIVIDUAL SYSTEM BREAKERS - Includes<br />

unit-mounted disconnect switch with external, lockable<br />

handles (in compliance with Article 440-14 of N.E.C.)<br />

to isolate unit power voltage for servicing. Factory<br />

interconnecting wiring is provided from the disconnect<br />

switch to factory supplied system circuit breakers.<br />

SINGLE-POINT CIRCUIT BREAKER – A unit mounted<br />

circuit breaker with external, lockable handle (in<br />

compliance with N.E.C. Article 440-14), can be supplied<br />

to isolate the power voltage for servicing. (This option<br />

includes the Single-Point Power connection.)<br />

CONTROL TRANSFORMER – Converts unit power voltage<br />

to 115-1-60 (0.5 or 1.0 KVA capacity). Factory mounting<br />

includes primary and secondary wiring between the<br />

transformer and the control panel. (Factory-mounted)<br />

CONTROL OPTIONS:<br />

AMBIENT KIT (LOW) – Units will operate to 30°F (-1°C).<br />

This accessory includes all necessary components to permit<br />

chiller operation to 0°F (-18°C). (This option includes<br />

the Discharge Pressure Transducer / Readout Capability<br />

option.) For proper head pressure control in applications<br />

below 30°F (-1°C) where wind gusts may exceed 5 mph,<br />

it is recommended that Optional Condenser Louvered<br />

Enclosure Panels also be included. (Factory-mounted)<br />

AMBIENT KIT (HIGH) – Required if units are to operate<br />

when the ambient temperature is above 115°F (46°C).<br />

Includes sun shield panels and discharge pressure<br />

transducers. (This option includes the Discharge Pressure<br />

Transducer / Readout Capability option.) (Fieldmounted)<br />

LANGUAGE LCD AND KEYPAD DISPLAY – Spanish,<br />

French, German, and Italian unit LCD controls and keypad<br />

display available. Standard language is English.<br />

COMPRESSOR, PIPING, EVAPORATOR<br />

options:<br />

CHICAGO CODE RELIEF VALVES – Unit will be provided<br />

with relief valves to meet Chicago code requirements.<br />

(Factory-Mounted)<br />

SERVICE ISOLATION VALVE – Service suction and<br />

discharge (ball type) isolation valves are added to unit<br />

per system. This option also includes a system high<br />

pressure relief valve in compliance with ASHRAE 15.<br />

(Factory-Mounted)<br />

HOT GAS BY-PASS – Permits continuous, stable operation<br />

at capacities below the minimum step of compressor<br />

unloading to as low as 5% capacity (depending on both<br />

the unit and operating conditions) by introducing an artificial<br />

load on the cooler. Hot gas by-pass is installed on<br />

only refrigerant system #1 on two-circuited units. (Factory-Mounted)<br />

Flanges (ANSI/AWWA C-606 couplings Type)<br />

– Consists of (2) Flange adapter for grooved end pipe (standard<br />

150 psi [10.5 bar] cooler). (Not available on optional<br />

DX cooler 300 PSIG DWP waterside.) (Field-mounted)<br />

FLOW SWITCH – The flow switch or its equivalent must<br />

be furnished with each unit.<br />

150 psig (10.5 bar) DWP – For standard units. Johnson<br />

Controls model F61MG-1C Vapor-proof SPDT, NEMA<br />

3R switch (150 psig [10.5 bar] DWP), -20°F to 250°F<br />

(-29°C to 121°C), with 1" NPT connection for upright<br />

mounting in horizontal pipe. (Field-mounted)<br />

Differential Pressure Switch – Alternative to an<br />

above mentioned flow switch. Pretempco model DPS300A-<br />

P40PF-82582-5 (300 psi max. working pressure), SPDT 5<br />

amp 125/250VAC switch, Range 3 - 40 psid, deadband<br />

0.5 - 0.8 psi, with 1/4” NPTE Pressure Connections.<br />

jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

HYDRO-KIT – Factory installed Hydro-Kit suitable for water<br />

glycol systems with up to 35% glycol at leaving temperatures<br />

down to 20 F. The Hydro-kit option is available in a<br />

single or dual configuration (dual as standby duty only), with<br />

totally enclosed permanently lubricated pump motors.<br />

The hydro-kit option comes standard with a balancing valve,<br />

flow switch, pressure ports, suction guide, strainer, bleed<br />

and drain valves and frost protection.<br />

Expansion tanks are optional within the Hydro-Kit option.<br />

CONDENSER AND CABINET OPTIONS:<br />

Condenser coil protection against corrosive environments<br />

is available by choosing any of the following options. For<br />

additional application recommendations, refer to FORM<br />

150.12-ES1. (Factory-Mounted)<br />

PRE-COATED FIN CONDENSER COILS – The unit’s<br />

coils are constructed with epoxy coated aluminum fins.<br />

This can provide corrosion resistance comparable to copper-fin<br />

coils in typical seashore locations. Either these or<br />

the post-coated coils (below), are recommended for units<br />

being installed at the seashore or where salt spray may<br />

hit the unit.<br />

POST-COATED DIPPED CONDENSER COILS – The<br />

unit’s coils are constructed with dipped-cured condenser<br />

coils. This is another choice for seashore and other corrosive<br />

applications (with the exception of strong alkalies,<br />

oxidizers and wet bromine, chlorine and fluorine in concentrations<br />

greater than 100 ppm).<br />

COPPER FIN CONDENSER COILS – The unit’s coils are<br />

constructed with copper fins. (This is not recommended for<br />

units in areas where they may be exposed to acid rain.)<br />

ENCLOSURE PANELS (UNIT) – Tamperproof Enclosure<br />

Panels prevent unauthorized access to units. Enclosure<br />

Panels can provide an aesthetically pleasing alternative<br />

to expensive fencing. Additionally, for proper head pressure<br />

control, Johnson Controls recommends the use of<br />

Condenser Louvered Panels for winter applications where<br />

wind gusts may exceed five miles per hour. The following<br />

types of enclosure panels are available:<br />

WIRE PANELS (Full Unit) – Consists of welded<br />

wire-mesh guards mounted on the exterior of the unit.<br />

Prevents unauthorized access, yet provides free air flow.<br />

(Factory-Mounted)<br />

WIRE/LOUVERED PANELS – Consists of welded wiremesh<br />

panels on the bottom part of unit and louvered<br />

panels on the condenser section of the unit. (Factorymounted).<br />

LOUVERED PANELS (Condenser Coil Only)<br />

– Louvered panels are mounted on the sides and ends of<br />

the condenser coils for protection. (Factory-Mounted)<br />

LOUVERED PANELS (Full Unit) – Louvered panels<br />

surround the front, back, and sides of the unit. They<br />

prevent unauthorized access and visually screen unit<br />

components. Unrestricted air flow is permitted through<br />

generously sized louvered openings. This option is applicable<br />

for any outdoor design ambient temperature up<br />

to 115°F (46°). (Factory-Mounted)<br />

COIL END HAIL GUARD – Louvered panel attached to<br />

exposed coil end. (Factory-Mounted)<br />

sound attenuation – One or both of the following<br />

sound attenuation options are recommended for residential<br />

or other similar sound sensitive locations:<br />

COMPRESSOR ACOUSTIC SOUND BLANKET<br />

– Each compressor is individually enclosed by an<br />

acoustic sound blanket. The sound blankets are made<br />

with one layer of acoustical absorbent textile fiber of<br />

5/8" (15mm) thickness; one layer of anti-vibrating heavy<br />

material thickness of 1/8" (3mm). Both are closed by<br />

two sheets of welded PVC, reinforced for temperature<br />

and UV resistance. (Factory-Mounted)<br />

ULTRA Quiet FANS – Lower RPM, 8-pole fan motors<br />

are used with steeper-pitch fans. (Factory-Mounted)<br />

VIBRATION ISOLATORS – Level adjusting, spring type 1"<br />

(25.4mm) or seismic deflection or neoprene pad isolators<br />

for mounting under unit base rails. (Field-mounted)<br />

jOHNSON CONTROLS


Design Parameters<br />

Nominal Evaporator Water Flow<br />

Unit<br />

Designation<br />

Temperature<br />

Air On Condenser (°F)<br />

Water Flow Water Flow<br />

(gpm) MIN (gpm) MAX<br />

Min (°F) Max (°F) Min Max<br />

<strong>YLAA</strong>0070 40 55 60 285 0 125<br />

<strong>YLAA</strong>0080 40 55 100 355 0 125<br />

<strong>YLAA</strong>0090 40 55 140 625 0 125<br />

<strong>YLAA</strong>0091 40 55 100 385 0 125<br />

<strong>YLAA</strong>0101 40 55 100 385 0 125<br />

<strong>YLAA</strong>0115 40 55 100 385 0 125<br />

<strong>YLAA</strong>0120 40 55 150 625 0 125<br />

<strong>YLAA</strong>0135 40 55 120 625 0 125<br />

<strong>YLAA</strong>0150 40 55 120 625 0 125<br />

<strong>YLAA</strong>0155 40 55 150 625 0 125<br />

NOTES:<br />

1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls Office for application requirements.<br />

2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest Johnson Controls Office for application guidelines. 3. The evaporator<br />

is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.<br />

4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system (for <strong>YLAA</strong>00140080 models<br />

only).<br />

5. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.<br />

<br />

jOHNSON CONTROLS


Water Pressure Drop<br />

FORM 150.62-EG5 (108)<br />

<strong>YLAA</strong> Evaporator Pressure Drop (IP Units)<br />

100.0<br />

D<br />

B<br />

F<br />

Pressure Drop (ft H2O)<br />

10.0<br />

A<br />

C<br />

E<br />

1.0<br />

10 100 1000<br />

Water Flow Rate (GPM)<br />

EVAPORATOR<br />

A<br />

B<br />

C<br />

D<br />

E<br />

F<br />

<strong>YLAA</strong> MODELS<br />

70SE<br />

80SE<br />

91HE,101HE, 115SE<br />

120SE, 155SE<br />

90SE<br />

135SE, 150SE<br />

jOHNSON CONTROLS


Selection Criteria and Procedures<br />

GUIDE TO SELECTION<br />

Capacity ratings for YORK <strong>YLAA</strong> Packaged Air-Cooled<br />

Liquid Chillers, shown on pages 18 through 23 cover the<br />

majority of design applications for these units. For unusual<br />

applications or uses beyond the scope of this catalog,<br />

please consult your nearest Johnson Controls Office or<br />

representative.<br />

SELECTION RULES<br />

1. Ratings – Ratings may be interpolated, but must not<br />

be extrapolated. The Ratings given on pages 18 through<br />

23 and the DESIGN PARAMETERS given on page 10<br />

indicate the limits of application for these chillers.<br />

2. Cooler Water – Ratings are based upon 2.4 GPM per<br />

ton which is equal to a 10°F chilled water range and a<br />

0.0001 fouling factor for the cooler at sea level. Tables<br />

on pages 18 through 23 give capacity, compressor kW<br />

required, cooler GPM and unit EER.<br />

3. Condenser – Ratings are given in terms of air on condenser<br />

in degrees Fahrenheit.<br />

4. Performance Data Correction Factors – Ratings are<br />

based on 0.0001 cooler fouling factor, 10°F chilled water<br />

range and at sea level. For operation at different conditions,<br />

apply the appropriate correction factor from the<br />

following table.<br />

FOULING FACTOR<br />

ALTITUDE<br />

SEA LEVEL<br />

2000 FT.<br />

4000 FT.<br />

6000 FT.<br />

TEMP<br />

SPLIT<br />

TONS<br />

0.0001 0.00025<br />

COMPR<br />

kW<br />

TONS<br />

COMPR<br />

kW<br />

8 0.994 0.999 0.991 0.998<br />

10 1.000 1.000 0.993 0.999<br />

12 1.005 1.001 0.999 0.999<br />

14 1.008 1.002 1.005 1.000<br />

8 0.990 1.010 0.984 1.009<br />

10 0.995 1.010 0.990 1.009<br />

12 0.999 1.011 0.995 1.010<br />

14 1.004 1.015 0.998 1.011<br />

8 0.983 1.021 0.977 1.020<br />

10 0.989 1.024 0.983 1.021<br />

12 0.994 1.025 0.988 1.024<br />

14 0.997 1.026 0.993 1.025<br />

8 0.978 1.035 0.973 1.034<br />

10 0.982 1.037 0.978 1.035<br />

12 0.987 1.037 0.980 1.036<br />

14 0.992 1.038 0.986 1.037<br />

6. Ethylene Glycol Correction Factors – The following<br />

factors are to be applied to the standard ratings for units<br />

cooling ethylene glycol.<br />

ETHYLENE GLYCOL<br />

% WEIGHT<br />

TONS<br />

PRESS<br />

COMPR GPM°F/TON<br />

kW<br />

DROP<br />

FREEZE PT<br />

10 0.985 0.997 24.1 1.034 26<br />

20 0.981 0.996 24.9 1.062 16<br />

30 0.974 0.995 26.1 1.096 5<br />

40 0.966 0.991 27.5 1.134 -10<br />

50 0.957 0.989 29.1 1.172 -32<br />

7. Propylene Glycol Correction Factors – The following<br />

factors are to be applied to the standard ratings for units<br />

cooling propylene glycol.<br />

PROPYLENE GLYCOL<br />

% WEIGHT<br />

TONS<br />

kW<br />

COMPR<br />

GPM°F/TON<br />

PRESS<br />

DROP<br />

FREEZE PT<br />

10 0.983 0.996 24.2 1.048 27<br />

20 0.974 0.995 24.4 1.086 19<br />

30 0.961 0.990 25.1 1.134 8<br />

40 0.946 0.98 26.0 1.186 -5<br />

50 0.928 0.984 27.2 1.247 -25<br />

METHOD OF SELECTION<br />

To select a Johnson Controls - <strong>YLAA</strong> Packaged Air-Cooled<br />

Liquid Chiller, the following data must be known:<br />

1. Design Capacity in tons refrigeration (TR).<br />

2. Entering and Leaving Liquid Temperatures.<br />

3. Outside ambient air temperature in degrees F.<br />

4. GPM of chilled liquid.<br />

Determine capacity requirements from the following<br />

formula:<br />

EXAMPLE – WATER CHILLING<br />

1. GIVEN: Provide a capacity of 90 Tons at 42°F<br />

leaving water 10°F range, 0.0001FF, 80°F air on<br />

the condenser, at sea level and 60 Hz.<br />

2. FIND: Unit Size Compressor kW Input<br />

3. From the Ratings on pages 18 - 23:<br />

SELECT: <strong>YLAA</strong>0090SE (English Units)<br />

91.4 Tons<br />

82 Compressor KW<br />

12.4 Unit EER<br />

4. Calculate Compressor kW at 50 Tons:<br />

kW = (90-91.4) x 80.7 = 80.7 kW<br />

10 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

5. Calculate GPM:<br />

90 Tons x 24<br />

GPM = 216 GPM<br />

10°F Range<br />

6. From Page 10, read 10 ft of water cooler pressure<br />

drop for GPM:<br />

7. A <strong>YLAA</strong>0090 is suitable.<br />

EXAMPLE – Brine Chilling<br />

1. GIVEN: Provide a capacity of 80 tons cooling<br />

30% by weight Ethylene Glycol from 50°F to 40°F,<br />

0.00025FF, 95°F air on the condenser, 60 Hz and<br />

4000 altitude.<br />

2. DETERMINE:<br />

Unit Size kW Input<br />

Ethylene Glycol GPM Cooler Pressure Drop<br />

3. See Ethylene Glycol correction factors, for 30%<br />

by weight Ethylene Glycol.<br />

READ: .974 Tons factor<br />

.995 Compr. kW factor 26.1 Gal./°F/Tons factor<br />

4. See Performance Data Correction Factors for<br />

0.00025 fouling factor and 4000 ft. altitude.<br />

READ: .983 Tons factor 1.021 kW factor<br />

5. From RATINGS on pages 18 - 23:<br />

SELECT: <strong>YLAA</strong>0090 (English Units)<br />

91.4 Tons 82.0 Compressor kW<br />

6. Determine <strong>YLAA</strong>0090 brine cooling capacity<br />

and Compressor kW requirement:<br />

A. Tons = 91.4 x .974 x .983 = 87.51<br />

B. Compr. kW = 82.0 x .995 x 1.021 = 83.3<br />

Determine average full load Compressor kW at<br />

80 tons: (80/87.51) x 83.3 = 76.15kW<br />

8. Determine Ethylene Glycol GPM:<br />

Tons x Gal. °F/min/Ton factor<br />

GPM = Range 80.0 x 26.1<br />

GPM = 10 GPM = 208.8<br />

9. Determine Cooler Pressure Drop:<br />

A. See Ethylene Glycol correction factors for 30%<br />

by weight Ethylene Glycol.<br />

READ: 1.096 Pressure Drop Factor<br />

B. See pages 18-19 at 88.7 GPM for the <strong>YLAA</strong>0090.<br />

READ: 6.8 Ft. H 2<br />

O Pressure Drop<br />

C. Cooler Pressure Drop = 6.8 x 1.096 or 7.5 Ft.<br />

H 2<br />

O<br />

10. <strong>YLAA</strong>0090 is suitable.<br />

jOHNSON CONTROLS<br />

11


Pump Selection Criteria<br />

Pump Selection<br />

Multiple pump sizes are available for each <strong>YLAA</strong> model<br />

providing the ability to closely match the system requirements.<br />

Within the YORKworks CE chiller selection program<br />

is an integral pump selection program that can be<br />

used for a quick and easy pump selection. Please contact<br />

your local Johnson Controls sales rep for assistance with<br />

this selection program. If this program is not available or<br />

if a manual selection is desired, the following steps can<br />

be followed to make a pump selection for the hydro kit<br />

option.<br />

1. Determine whether a single pump or dual pump<br />

(standby) option is required. For this example, single<br />

pump hydro kits will be used.<br />

2. Determine the required flow (GPM). This value will<br />

be calculated with the chiller selection. Pump design<br />

flow must be within the limits of the chiller.<br />

ex. 100 Ton Chiller: 235 gpm (<strong>YLAA</strong><br />

0101HE) single pump option<br />

3. Calculate the external system pressure loss (ft) for<br />

all piping and components external to the chiller.<br />

ex. 45 ft<br />

4. Determine the internal pressure loss to the chiller (ft)<br />

due to the evaporator from the Water Pressure Drop<br />

charts. Combine this with the external system pressure<br />

loss (ft) to determine the preliminary pressure<br />

loss.<br />

ex. Internal Pressure Loss due to evapora<br />

tor:12 ft (from chart on page 11)<br />

Preliminary pressure loss: 45 ft (exter<br />

nal) + 12 ft (evaporator) = 57 ft<br />

5. Review the available hydro kit options for the <strong>YLAA</strong><br />

model (See Table 1) selected using the Hydro Kit by<br />

Models Chart. Use the flow and head calculated in<br />

steps 2 and 4 to select a preliminary design point. If<br />

the preliminary design point does not fall directly on<br />

the curve, select the next step larger size of impeller.<br />

ex. Preliminary design point: 235 gpm/57<br />

ft<br />

Preliminary selection: Hydro Kit<br />

B/3x3x10@ 1740 rpm; 9.00 in impeller<br />

diameter with 7.5Hp motor.<br />

page 16-17, determine the internal pressure loss to<br />

the chiller due to the hydro kit piping for the selected<br />

Hydro Kit. Add this to the preliminary pressure loss<br />

(from step 4) to determine the total pressure loss:<br />

ex. For Hydro Kit B on <strong>YLAA</strong>0101 unit, the<br />

hydro kit pressure loss is 15 ft.<br />

Total pressure loss = 57 ft + 15 ft = 72<br />

ft<br />

7. Check to see if the Hydro-Kit selection is valid. Using<br />

the total pressure loss (from step 6), plot the flow<br />

(GPM) and the total pressure loss on the hydro kit<br />

selected in step 5. If the pump selection is no longer<br />

adequate, re-select a hydro kit and go back to step<br />

6. (Note: if a design point does not fall directly on<br />

the curve, one can select the next step larger size of<br />

impeller and use the circuit balancing valve to adjust<br />

the system head requirements and correct for small<br />

variations from the selected pump curve.) If the pump<br />

selection is satisfactory, proceed to step 8.<br />

ex. Total Pressure Loss = 72ft. with GPM = 235<br />

Selection is still valid for a Hydro-Kit B (3x3x10,<br />

1800rpm, 9” impeller @ 7.5Hp)<br />

8. The pump efficiency can be read from the pump<br />

curve using the dashed efficiency lines labeled as a<br />

percentage.<br />

ex. Efficiency: 68 % (from pump curve)<br />

9. The pump is selected<br />

ex. Hydro Kit B at 68%<br />

10. The pump NPSHr required can also be read from the<br />

pump curves. When selecting a pump one must make<br />

sure that the system designed NPSHa available is<br />

greater than the NPSHr required by the pump plus<br />

the fluid vapor pressure.<br />

ex. NPSHr = 6 ft (From Pump Curve for<br />

Hydro Kit B)<br />

NPSHa = 30 ft (From System Design<br />

- Figure 3)<br />

VP = 0.4 ft (Water at 50ºF)<br />

NPSHr + VP < NPSHa<br />

6 ft + 0.4 ft < 30 ft<br />

If the system flow or pressure exceeds that of the hydro<br />

kit pump curves provided, an integral hydro kit is not<br />

available for your application and a separate pump must<br />

be provided.<br />

6. Using the Hydro Kit pressure loss charts found on<br />

12 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

Table1 – Pump Selection Information<br />

Kit Series Kit Type Pump Size Pump HP Motor RPM<br />

Impeller Dia<br />

(in)<br />

Models Where Used<br />

A 4380 Single 3X3X8 5 1800 7.5 70,80,90,91<br />

B 4380 Single 3X3X10 7.5 1800 9 70,80,90,91,101<br />

C 4380 Single 3X3X10 10 1800 10 70,80,115,120,135<br />

D 4380 Single 3X3X6 15 3600 5.9 70,80,90,91,101,115,120,135<br />

E 4380 Single 3X3X8 20 3600 6.3 90,91,101,115,120,135<br />

F 4380 Single 3X3X8 7.5 1800 8 101,115,120,135<br />

G 4380 Single 4X4X8 10 1800 7.6 150,155<br />

H 4380 Single 4X4X6 10 3600 4.9 150,155<br />

I 4380 Single 4X4X6 15 3600 5.5 150,155<br />

J 4380 Single 4X4X6 20 3600 5.95 150,155<br />

K 4382 Dual 4X4X8 7.5 1800 7.85 70,80,90,91,101,115,120,135<br />

L 4382 Dual 4X4X6 10 3600 5.25 70,80,90,91,101,115,150,155<br />

M 4382 Dual 4X4X6 15 3600 5.6 70,80,90,91,120,135,150,155<br />

N 4382 Dual 3X3X8 15 3600 6.6 70,80,90,91,<br />

O 4382 Dual 4X4X6 15 3600 5.9 101,115,120,165<br />

P 4382 Dual 3X3X8 20 3600 7.15 101,115,120<br />

R 4382 Dual 4X4X8 20 3600 6.3 135,150,155<br />

jOHNSON CONTROLS<br />

13


Pump Pressure Drop Curves<br />

<strong>YLAA</strong>0070<br />

50<br />

45<br />

40<br />

Hydro Kits A, B, C, D, N<br />

Hydro Kits K, L, M<br />

35<br />

Pd (ft)<br />

30<br />

25<br />

<strong>YLAA</strong>0091<br />

20<br />

15<br />

10<br />

5<br />

0<br />

50<br />

45<br />

40<br />

35<br />

Hydro Kits A,B,D,E,N<br />

Hydro Kits K, L, M<br />

Flow (GPM)<br />

<strong>YLAA</strong>0080<br />

Pd (ft)<br />

30<br />

25<br />

20<br />

50<br />

45<br />

40<br />

Hydro Kits A, B, C, D<br />

Hydro Kits K, L, M<br />

Hydro Kit N<br />

15<br />

10<br />

5<br />

Pd (ft)<br />

35<br />

30<br />

25<br />

20<br />

0<br />

0 200 400 600<br />

Flow (GPM)<br />

15<br />

10<br />

<strong>YLAA</strong>0101<br />

5<br />

0<br />

0 200 400 600<br />

Flow (GPM)<br />

50<br />

45<br />

40<br />

35<br />

Hydro Kits B,D,E, F, P<br />

Hydro Kits K, L, O<br />

Pd (ft)<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

15<br />

10<br />

5<br />

Hydro Kits A,B,D,E,N<br />

Hydro Kits K, L, M<br />

<strong>YLAA</strong>0090<br />

Pd (ft)<br />

30<br />

25<br />

20<br />

15<br />

10<br />

5<br />

0<br />

0 200 400 600<br />

Flow (GPM)<br />

0<br />

0 200 400 600<br />

Flow (GPM)<br />

14 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

<strong>YLAA</strong>0115<br />

50<br />

45<br />

40<br />

Hydro Kits C,D,E, F<br />

Hydro Kits K, L, O<br />

Hydro Kit P<br />

Pd (ft)<br />

Pd (ft)<br />

Pd (ft)<br />

35<br />

30<br />

25<br />

20<br />

15<br />

10<br />

5<br />

0<br />

0 200 400 600<br />

Flow (GPM)<br />

jOHNSON CONTROLS<br />

<strong>YLAA</strong>0120<br />

50<br />

Hydro Kits C,D,E, F, K, M, O<br />

45 Hydro Kit P<br />

40<br />

35<br />

30<br />

25<br />

20<br />

15<br />

10<br />

5<br />

0<br />

0 200 400 600<br />

Flow (GPM)<br />

<strong>YLAA</strong>0135<br />

50<br />

Hydro Kits C,D,E, F<br />

45<br />

Hydro Kit K,M,O,R<br />

40<br />

35<br />

30<br />

25<br />

20<br />

15<br />

10<br />

5<br />

0<br />

0 200 400 600<br />

Flow (GPM)<br />

Pd (ft)<br />

Pd (ft)<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

15<br />

10<br />

5<br />

0<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

15<br />

10<br />

5<br />

0<br />

<strong>YLAA</strong>0150<br />

Hydro Kits G,H,I,J,L,M,R<br />

0 200 400 600<br />

Flow (GPM)<br />

<strong>YLAA</strong>0155<br />

Hydro Kits G,H,I,J,L,M,R<br />

0 100 200 300 400 500 600 700<br />

Flow (GPM)<br />

15


Single Pump Curves<br />

Kit A & F<br />

Kit E<br />

Kit B & C<br />

Kit G<br />

Kit D<br />

Kit N, I, & J<br />

16 jOHNSON CONTROLS


Dual Pump Curves<br />

FORM 150.62-EG5 (108)<br />

Kit K<br />

Kit N & P<br />

Kit L, M, & O<br />

Kit R<br />

jOHNSON CONTROLS<br />

17


Ratings - 60 Hz<br />

MODEL: <strong>YLAA</strong>0070ZE IPLV: 15.7<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

75.0 80.0 85.0 90.0 95.0 100.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER<br />

40.0 74.7 61.9 13.1 72.8 65.2 12.1 70.9 68.8 11.3 68.8 72.7 10.4 66.8 76.8 9.6 64.3 80.8 8.8<br />

42.0 77.1 62.5 13.4 75.1 65.9 12.4 73.1 69.5 11.5 71.0 73.3 10.6 68.9 77.4 9.8 66.3 81.5 9.0<br />

44.0 79.5 63.2 13.6 77.5 66.5 12.7 75.4 70.1 11.8 73.3 74.0 10.9 71.1 78.1 10.1 68.4 82.1 9.2<br />

45.0 80.7 63.5 13.8 78.7 66.8 12.8 76.6 70.5 11.9 74.4 74.4 11.0 72.2 78.5 10.2 69.5 82.5 9.3<br />

46.0 82.0 63.8 13.9 79.9 67.2 13.0 77.8 70.8 12.0 75.6 74.7 11.1 73.3 78.8 10.3 70.6 82.8 9.5<br />

48.0 84.5 64.5 14.2 82.3 67.9 13.2 80.2 71.5 12.3 77.9 75.4 11.4 75.5 79.5 10.5 72.7 83.5 9.7<br />

50.0 87.1 65.2 14.5 84.9 68.6 13.5 82.6 72.2 12.5 80.2 76.1 11.6 77.8 80.2 10.7 74.9 84.3 9.9<br />

MODEL: <strong>YLAA</strong>0080ZE IPLV: 15.0<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

75.0 80.0 85.0 90.0 95.0 100.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER<br />

40.0 80.3 69.1 12.7 78.2 72.9 11.8 76.0 77.0 10.9 73.8 81.4 10.0 71.5 86.1 9.2 68.7 90.8 8.5<br />

42.0 82.9 69.8 13.0 80.7 73.6 12.1 78.5 77.7 11.1 76.1 82.2 10.3 73.8 86.9 9.5 70.9 91.5 8.7<br />

44.0 85.5 70.6 13.3 83.3 74.4 12.3 81.0 78.5 11.4 78.6 83.0 10.5 76.1 87.7 9.7 73.2 92.3 8.9<br />

45.0 86.8 71.0 13.4 84.5 74.8 12.4 82.2 78.9 11.5 79.8 83.4 10.6 77.3 88.1 9.8 74.4 92.7 9.0<br />

46.0 88.2 71.4 13.6 85.9 75.2 12.6 83.5 79.3 11.6 81.0 83.8 10.7 78.5 88.5 9.9 75.5 93.1 9.1<br />

48.0 90.9 72.2 13.8 88.5 76.0 12.8 86.0 80.2 11.9 83.5 84.6 11.0 81.0 89.3 10.1 77.9 93.9 9.3<br />

50.0 93.7 73.0 14.1 91.2 76.9 13.1 88.7 81.0 12.1 86.1 85.4 11.2 83.5 90.1 10.3 80.3 94.8 9.5<br />

MODEL: <strong>YLAA</strong>0090ZE IPLV: 14.9<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

75.0 80.0 85.0 90.0 95.0 100.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER<br />

40.0 89.8 77.6 12.8 87.3 81.8 11.8 84.7 86.3 10.9 82.0 91.2 10.0 79.2 96.3 9.2 76.0 101.4 8.4<br />

42.0 92.7 78.5 13.1 90.1 82.7 12.1 87.5 87.2 11.2 84.7 92.1 10.3 81.9 97.3 9.5 78.6 102.4 8.6<br />

44.0 95.6 79.4 13.3 93.0 83.7 12.3 90.3 88.2 11.4 87.5 93.1 10.5 84.6 98.2 9.7 81.2 103.3 8.9<br />

45.0 97.1 79.9 13.4 94.4 84.2 12.5 91.7 88.7 11.5 88.9 93.6 10.6 86.0 98.7 9.8 82.5 103.9 9.0<br />

46.0 98.6 80.4 13.6 95.9 84.7 12.6 93.1 89.3 11.6 90.3 94.1 10.7 87.4 99.3 9.9 83.9 104.4 9.1<br />

48.0 101.6 81.5 13.8 98.8 85.7 12.8 95.9 90.3 11.9 93.1 95.2 11.0 90.1 100.3 10.1 86.5 105.4 9.3<br />

50.0 104.7 82.5 14.1 101.8 86.8 13.1 98.9 91.4 12.1 95.9 96.2 11.2 92.9 101.4 10.3 89.2 106.5 9.5<br />

NOTES:<br />

1. kW = Compressor Input Power<br />

2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)<br />

3. LCWT = Leaving Chilled Water Temperature<br />

4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor<br />

5. Rated in accordance with ARI Standard 550/590<br />

6. The shaded points are certified in accordance with ARI Standard 550/590-98<br />

18 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

MODEL: <strong>YLAA</strong>0070ZE IPLV: 15.7<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

105.0 110.0 115.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER<br />

40.0 61.7 85.0 8.1 59.0 89.5 7.4 56.3 94.1 6.7<br />

42.0 63.7 85.7 8.3 60.9 90.1 7.5 58.1 94.8 6.9<br />

44.0 65.7 86.4 8.5 62.9 90.8 7.7 60.0 95.5 7.0<br />

45.0 66.7 86.7 8.6 63.9 91.2 7.8 60.9 95.9 7.1<br />

46.0 67.7 87.1 8.7 64.9 91.6 7.9 61.9 96.2 7.2<br />

48.0 69.8 87.8 8.9 66.9 92.3 8.1 63.8 97.0 7.4<br />

50.0 72.0 88.5 9.1 68.9 93.0 8.3 65.8 97.7 7.6<br />

MODEL: <strong>YLAA</strong>0080ZE IPLV: 15.0<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

105.0 110.0 115.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER<br />

40.0 65.9 95.6 7.7 63.0 100.8 7.0 51.4 83.4 6.8<br />

42.0 68.0 96.4 7.9 65.1 101.6 7.2 53.2 84.0 7.0<br />

44.0 70.2 97.2 8.1 67.2 102.4 7.4 55.0 84.6 7.2<br />

45.0 71.4 97.6 8.2 68.3 102.8 7.5 55.9 84.9 7.3<br />

46.0 72.5 98.0 8.3 69.3 103.2 7.6 56.8 85.2 7.4<br />

48.0 74.7 98.9 8.5 71.5 104.0 7.7 58.7 85.8 7.6<br />

50.0 77.1 99.7 8.7 73.7 104.9 7.9 60.6 86.4 7.8<br />

MODEL: <strong>YLAA</strong>0090ZE IPLV: 14.9<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

105.0 110.0 115.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER<br />

40.0 72.7 106.7 7.7 69.4 112.4 7 48.1 72.8 7.3<br />

42.0 75.2 107.7 7.9 71.8 113.3 7.2 49.8 73.3 7.5<br />

44.0 77.7 108.7 8.1 74.2 114.4 7.4 51.6 73.8 7.7<br />

45.0 79 109.2 8.2 75.4 114.9 7.4 52.5 74 7.8<br />

46.0 80.3 109.8 8.3 76.6 115.4 7.5 53.4 74.3 7.9<br />

48.0 82.9 110.8 8.5 79.1 116.5 7.7 55.2 74.9 8.1<br />

50.0 85.5 111.9 8.6 70.9 94.6 8.4 57.1 75.4 8.3<br />

NOTES:<br />

1. kW = Compressor Input Power<br />

2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)<br />

3. LCWT = Leaving Chilled Water Temperature<br />

4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor<br />

5. Rated in accordance with ARI Standard 550/590<br />

6. The shaded points are certified in accordance with ARI Standard 550/590-98<br />

jOHNSON CONTROLS<br />

19


Ratings - 60 Hz – continued<br />

MODEL: <strong>YLAA</strong>0091YE IPLV: 14.6<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

75.0 80.0 85.0 90.0 95.0 100.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER<br />

40.0 91.3 70.5 13.6 88.9 74.3 12.7 86.5 78.4 11.7 84.1 82.7 10.9 81.6 87.4 10.0 78.5 92.1 9.2<br />

42.0 94.3 71.2 13.9 91.9 74.9 13.0 89.5 79.0 12.1 86.9 83.4 11.2 84.3 88.1 10.3 81.2 92.8 9.5<br />

44.0 97.4 71.9 14.3 95.0 75.6 13.3 92.4 79.7 12.4 89.8 84.1 11.5 87.1 88.8 10.6 83.9 93.5 9.7<br />

45.0 99.0 72.3 14.4 96.5 76.0 13.5 93.9 80.0 12.5 91.3 84.4 11.6 88.6 89.1 10.7 85.3 93.8 9.8<br />

46.0 100.6 72.6 14.6 98.0 76.4 13.6 95.4 80.4 12.7 92.8 84.8 11.7 90.0 89.5 10.8 86.7 94.2 10.0<br />

48.0 103.8 73.4 14.9 101.2 77.1 13.9 98.5 81.2 13.0 95.7 85.5 12.0 92.9 90.2 11.1 89.5 95.0 10.2<br />

50.0 107.1 74.2 15.2 104.4 77.9 14.2 101.6 81.9 13.3 98.8 86.3 12.3 95.8 91.0 11.4 92.3 95.7 10.5<br />

MODEL: <strong>YLAA</strong>0101YE IPLV: 14.9<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

75.0 80.0 85.0 90.0 95.0 100.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER<br />

40.0 102.2 84.3 13.0 99.5 88.9 12.1 96.8 93.9 11.2 94.0 99.2 10.3 91.2 104.9 9.5 87.7 110.6 8.7<br />

42.0 105.5 85.1 13.3 102.8 89.7 12.4 100.0 94.7 11.5 97.1 100.1 10.6 94.2 105.8 9.8 90.6 111.4 9.0<br />

44.0 108.9 86.0 13.6 106.1 90.6 12.7 103.3 95.6 11.7 100.3 100.9 10.8 97.3 106.6 10.0 93.6 112.3 9.2<br />

45.0 110.7 86.4 13.8 107.8 91.1 12.8 104.9 96.0 11.9 101.9 101.4 11.0 98.8 107.1 10.1 95.1 112.8 9.3<br />

46.0 112.4 86.9 13.9 109.5 91.5 12.9 106.6 96.5 12.0 103.5 101.8 11.1 100.4 107.6 10.2 96.7 113.3 9.4<br />

48.0 116.0 87.8 14.2 113.0 92.5 13.2 110.0 97.4 12.3 106.8 102.8 11.4 103.6 108.5 10.5 99.7 114.2 9.6<br />

50.0 119.6 88.8 14.5 116.5 93.4 13.5 113.3 98.4 12.5 110.2 103.8 11.6 106.9 109.5 10.7 102.9 115.2 9.9<br />

MODEL: <strong>YLAA</strong>0115ZE IPLV: 14.3<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

75.0 80.0 85.0 90.0 95.0 100.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER<br />

40.0 118.5 104.1 12.5 115.5 109.6 11.6 112.3 115.5 10.7 109.0 121.9 9.9 105.6 128.6 9.1 101.5 135.2 8.4<br />

42.0 122.4 105.2 12.7 119.2 110.7 11.8 115.9 116.7 11.0 112.5 123.1 10.1 109.0 129.8 9.4 104.8 136.5 8.6<br />

44.0 126.3 106.4 13.0 123.0 112.0 12.1 119.6 117.9 11.2 116.1 124.3 10.4 112.5 131.1 9.6 108.2 137.7 8.8<br />

45.0 128.2 107.0 13.1 124.9 112.6 12.2 121.5 118.5 11.3 117.9 124.9 10.5 114.2 131.7 9.7 109.9 138.3 8.9<br />

46.0 130.2 107.6 13.3 126.8 113.2 12.3 123.3 119.2 11.5 119.7 125.6 10.6 116.0 132.3 9.8 111.6 139.0 9.0<br />

48.0 134.2 108.8 13.5 130.7 114.5 12.6 127.1 120.4 11.7 123.4 126.9 10.8 119.6 133.6 10.0 115.1 140.3 9.2<br />

50.0 138.2 110.1 13.8 134.6 115.8 12.8 130.9 121.8 11.9 127.1 128.2 11.0 123.2 135.0 10.2 118.6 141.7 9.4<br />

NOTES:<br />

1. kW = Compressor Input Power<br />

2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)<br />

3. LCWT = Leaving Chilled Water Temperature<br />

4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor<br />

5. Rated in accordance with ARI Standard 550/590<br />

6. The shaded points are certified in accordance with ARI Standard 550/590-98<br />

20 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

MODEL: <strong>YLAA</strong>0091YE IPLV: 14.6<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

105.0 110.0 115.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER<br />

40.0 75.4 97.1 8.4 72.2 102.3 7.7 68.9 107.7 7<br />

42.0 78 97.7 8.7 74.7 102.9 7.9 71.3 108.4 7.2<br />

44.0 80.6 98.4 8.9 77.2 103.7 8.1 73.8 109.2 7.4<br />

45.0 81.9 98.8 9 78.5 104 8.3 75 109.5 7.5<br />

46.0 83.3 99.2 9.1 79.8 104.4 8.4 76.3 109.9 7.6<br />

48.0 86 99.9 9.4 82.4 105.2 8.6 78.8 110.7 7.8<br />

50.0 88.7 100.7 9.6 85.1 105.9 8.8 81.4 111.5 8<br />

MODEL: <strong>YLAA</strong>0101YE IPLV: 14.9<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

105.0 110.0 115.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER<br />

40.0 84.2 116.5 8 80.6 122.8 7.3 68 107.3 7<br />

42.0 87 117.4 8.2 83.3 123.7 7.5 70.4 108 7.2<br />

44.0 89.9 118.3 8.4 86.1 124.6 7.7 72.8 108.7 7.4<br />

45.0 91.4 118.8 8.5 87.5 125.1 7.8 74.1 109 7.5<br />

46.0 92.8 119.2 8.6 88.9 125.5 7.9 75.3 109.4 7.6<br />

48.0 95.8 120.2 8.8 91.8 126.5 8.1 55.5 69.4 8.4<br />

50.0 98.8 121.2 9 94.7 127.5 8.3 57.5 69.8 8.6<br />

MODEL: <strong>YLAA</strong>0115ZE IPLV: 14.3<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

105.0 110.0 115.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER<br />

40.0 97.4 142.2 7.7 93.1 149.5 7 88.7 157.1 6.4<br />

42.0 100.6 143.4 7.9 96.2 150.8 7.2 91.7 158.4 6.5<br />

44.0 103.8 144.7 8 99.3 152 7.4 94.7 159.7 6.7<br />

45.0 105.4 145.3 8.1 100.9 152.7 7.4 96.2 160.3 6.8<br />

46.0 107.1 146 8.2 102.5 153.3 7.5 56.7 71.3 8.4<br />

48.0 110.4 147.3 8.4 105.7 154.7 7.7 58.7 71.8 8.6<br />

50.0 113.8 148.7 8.6 108.9 156.1 7.9 60.7 72.3 8.8<br />

NOTES:<br />

1. kW = Compressor Input Power<br />

2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)<br />

3. LCWT = Leaving Chilled Water Temperature<br />

4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor<br />

5. Rated in accordance with ARI Standard 550/590<br />

6. The shaded points are certified in accordance with ARI Standard 550/590-98<br />

jOHNSON CONTROLS<br />

21


Ratings - 60 Hz – continued<br />

MODEL: <strong>YLAA</strong>0120ZE IPLV: 14.5<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

75.0 80.0 85.0 90.0 95.0 100.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER<br />

40.0 125.3 107.4 12.8 121.9 113.1 11.9 118.4 119.0 11.0 114.8 125.4 10.2 111.0 132.2 9.4 106.6 138.9 8.6<br />

42.0 129.4 108.7 13.1 125.8 114.3 12.1 122.2 120.3 11.3 118.5 126.8 10.4 114.7 133.5 9.6 110.1 140.2 8.8<br />

44.0 133.5 110.0 13.3 129.8 115.6 12.4 126.1 121.6 11.5 122.3 128.1 10.6 118.3 134.9 9.8 113.7 141.6 9.0<br />

45.0 135.6 110.6 13.5 131.9 116.3 12.5 128.1 122.3 11.6 124.2 128.8 10.7 120.2 135.6 9.9 115.5 142.3 9.1<br />

46.0 137.7 111.3 13.6 133.9 117.0 12.6 130.1 123.0 11.7 126.1 129.5 10.8 122.1 136.3 10.0 117.3 143.0 9.2<br />

48.0 141.9 112.7 13.9 138.0 118.4 12.9 134.1 124.4 12.0 130.0 130.9 11.1 125.9 137.7 10.2 120.3 144.2 9.4<br />

50.0 146.2 114.1 14.1 142.2 119.8 13.1 138.1 126.0 12.2 133.9 132.4 11.3 129.7 139.2 10.4 124.6 145.9 9.6<br />

MODEL: <strong>YLAA</strong>0135ZE IPLV: 14.9<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

75.0 80.0 85.0 90.0 95.0 100.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER<br />

40.0 132.3 112.9 12.6 128.8 119.0 11.7 125.3 125.4 10.8 121.6 132.3 10.0 117.9 139.7 9.2 113.4 146.9 8.5<br />

42.0 136.6 114.1 12.9 133.1 120.2 12.0 129.4 126.6 11.1 125.7 133.5 10.3 121.8 140.9 9.5 117.2 148.1 8.7<br />

44.0 141.0 115.4 13.1 137.4 121.4 12.2 133.6 127.8 11.4 129.7 134.8 10.5 125.8 142.1 9.7 121.0 149.4 8.9<br />

45.0 143.2 116.0 13.3 139.5 122.0 12.4 135.7 128.5 11.5 131.8 135.4 10.6 127.8 142.8 9.8 123.0 150.0 9.0<br />

46.0 145.5 116.6 13.4 141.7 122.7 12.5 137.9 129.1 11.6 133.9 136.1 10.7 129.8 143.4 9.9 124.9 150.7 9.1<br />

48.0 150.0 117.9 13.7 146.1 124.0 12.8 142.2 130.5 11.9 138.1 137.4 11.0 133.9 144.8 10.2 128.8 152.1 9.3<br />

50.0 154.6 119.3 14.0 150.6 125.4 13.0 146.5 131.9 12.1 142.3 138.8 11.2 138.0 146.1 10.4 132.8 153.5 9.6<br />

MODEL: <strong>YLAA</strong>0150ZE IPLV: 14.9<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

75.0 80.0 85.0 90.0 95.0 100.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER<br />

40.0 146.0 127.7 12.4 142.2 134.5 11.5 138.3 141.8 10.7 134.3 149.6 9.9 130.1 157.8 9.1 125.1 166.0 8.4<br />

42.0 150.7 129.0 12.7 146.8 135.9 11.8 142.8 143.1 10.9 138.6 151.0 10.1 134.4 159.2 9.3 129.2 167.4 8.6<br />

44.0 155.5 130.4 13.0 151.5 137.3 12.1 147.4 144.6 11.2 143.1 152.4 10.3 138.7 160.7 9.6 133.4 168.9 8.8<br />

45.0 158.0 131.1 13.1 153.9 138.0 12.2 149.7 145.3 11.3 145.3 153.2 10.5 140.9 161.5 9.7 135.5 169.7 8.9<br />

46.0 160.4 131.8 13.2 156.2 138.8 12.3 152.0 146.1 11.4 147.6 153.9 10.6 143.0 162.2 9.8 137.6 170.5 9.0<br />

48.0 165.3 133.3 13.5 161.1 140.3 12.6 156.7 147.6 11.7 152.1 155.5 10.8 147.5 163.8 10.0 141.9 172.0 9.2<br />

50.0 170.3 134.9 13.8 165.9 141.8 12.8 161.4 149.3 11.9 156.8 157.1 11.0 152.0 165.4 10.2 146.2 173.6 9.4<br />

NOTES:<br />

1. kW = Compressor Input Power<br />

2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)<br />

3. LCWT = Leaving Chilled Water Temperature<br />

4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor<br />

5. Rated in accordance with ARI Standard 550/590<br />

6. The shaded points are certified in accordance with ARI Standard 550/590-98<br />

22 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

MODEL: <strong>YLAA</strong>0120ZE IPLV: 14.5<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

105.0 110.0 115.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER<br />

40.0 102.1 145.9 7.9 97.4 153.2 7.2 92.7 160.9 6.5<br />

42.0 105.5 147.3 8 100.7 154.6 7.3 74.8 116.8 7.1<br />

44.0 108.9 148.6 8.2 104.1 156 7.5 56.1 72 8.2<br />

45.0 110.7 149.3 8.3 105.7 156.7 7.6 57.1 72.3 8.3<br />

46.0 112.4 150.1 8.4 107.4 157.4 7.7 58.1 72.5 8.4<br />

48.0 115.9 151.5 8.6 110.8 158.9 7.9 60.1 73 8.7<br />

50.0 119.5 153 8.8 114.2 160.4 8 62.2 73.5 8.9<br />

MODEL: <strong>YLAA</strong>0135ZE IPLV: 14.9<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

105.0 110.0 115.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER<br />

40.0 108.8 154.6 7.8 104.1 162.6 7.1 83.3 125.2 7.2<br />

42.0 112.4 155.8 8 107.6 163.9 7.3 86.2 126 7.4<br />

44.0 116.1 157.1 8.2 111.2 165.2 7.5 89.2 126.8 7.6<br />

45.0 118 157.7 8.3 113 165.8 7.6 90.7 127.2 7.7<br />

46.0 119.9 158.4 8.4 114.8 166.5 7.7 92.2 127.7 7.8<br />

48.0 123.7 159.8 8.6 118.5 167.9 7.8 95.3 128.5 8.1<br />

50.0 127.6 161.2 8.8 122.2 169.3 8 98.4 129.4 8.3<br />

MODEL: <strong>YLAA</strong>0150ZE IPLV: 14.9<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

105.0 110.0 115.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER<br />

40.0 120 174.6 7.7 114.8 183.6 7 93.4 147.1 7<br />

42.0 124 176 7.9 118.7 185.1 7.2 96.6 148.1 7.2<br />

44.0 128 177.5 8 122.5 186.6 7.4 99.9 149.2 7.4<br />

45.0 130.1 178.3 8.1 124.5 187.4 7.4 101.6 149.7 7.5<br />

46.0 132.1 179.1 8.2 126.5 188.1 7.5 103.2 150.3 7.6<br />

48.0 136.2 180.7 8.4 130.4 189.7 7.7 106.6 151.4 7.8<br />

50.0 140.4 182.3 8.6 134.5 191.4 7.9 110 152.5 8<br />

NOTES:<br />

1. kW = Compressor Input Power<br />

2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)<br />

3. LCWT = Leaving Chilled Water Temperature<br />

4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor<br />

5. Rated in accordance with ARI Standard 550/590<br />

6. The shaded points are certified in accordance with ARI Standard 550/590-98<br />

jOHNSON CONTROLS<br />

23


Ratings - 60 Hz – continued<br />

MODEL: <strong>YLAA</strong>0155ZE IPLV: 14.8<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

75.0 80.0 85.0 90.0 95.0 100.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER<br />

40.0 149.4 130.1 12.5 145.4 137.0 11.6 141.4 144.3 10.8 137.1 152.2 9.9 132.8 160.5 9.2 127.6 168.7 8.4<br />

42.0 154.3 131.6 12.8 150.2 138.5 11.9 146.0 145.8 11.0 141.6 153.7 10.2 137.1 162.0 9.4 131.8 170.3 8.6<br />

44.0 159.2 133.1 13.0 154.9 140.0 12.1 150.6 147.3 11.2 146.1 155.2 10.4 141.6 163.5 9.6 136.1 171.8 8.8<br />

45.0 161.6 133.8 13.2 157.4 140.8 12.2 153.0 148.1 11.4 148.4 156.0 10.5 143.8 164.3 9.7 138.2 172.6 8.9<br />

46.0 164.1 134.6 13.3 159.8 141.5 12.4 155.4 148.9 11.5 150.7 156.8 10.6 146.0 165.1 9.8 140.4 173.4 9.0<br />

48.0 169.2 136.1 13.6 164.6 143.1 12.6 160.1 150.6 11.7 155.4 158.4 10.9 150.6 166.8 10.0 144.8 175.1 9.2<br />

50.0 174.3 137.8 13.8 169.7 144.8 12.9 164.9 152.3 11.9 160.1 160.1 11.1 155.1 168.5 10.2 149.2 176.8 9.4<br />

NOTES:<br />

1. kW = Compressor Input Power<br />

2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)<br />

3. LCWT = Leaving Chilled Water Temperature<br />

4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor<br />

5. Rated in accordance with ARI Standard 550/590<br />

6. The shaded points are certified in accordance with ARI Standard 550/590-98<br />

24 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

MODEL: <strong>YLAA</strong>0155ZE IPLV: 14.8<br />

AIR TEMPERATURE ON - CONDENSER (°F)<br />

LCHWT<br />

105.0 110.0 115.0<br />

(°F) TONS KW EER TONS KW EER TONS KW EER<br />

40.0 122.3 177.4 7.7 116.9 186.4 7 94.5 149 7<br />

42.0 126.4 178.9 7.9 120.8 188 7.2 97.8 150.1 7.2<br />

44.0 130.5 180.5 8.1 124.8 189.6 7.4 101.2 151.2 7.4<br />

45.0 132.6 181.3 8.2 126.8 190.4 7.5 102.9 151.8 7.5<br />

46.0 134.7 182.1 8.3 128.8 191.2 7.6 104.4 152.3 7.6<br />

48.0 138.9 183.8 8.4 132.9 192.9 7.7 108 153.5 7.8<br />

50.0 143.1 185.5 8.6 116.7 147.3 8.7 111.5 154.7 8<br />

NOTES:<br />

1. kW = Compressor Input Power<br />

2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)<br />

3. LCWT = Leaving Chilled Water Temperature<br />

4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor<br />

5. Rated in accordance with ARI Standard 550/590<br />

6. The shaded points are certified in accordance with ARI Standard 550/590-98<br />

jOHNSON CONTROLS<br />

25


Part Load Ratings – Standard Efficiency<br />

% DISPL<br />

AMBIENT<br />

DEG F<br />

<strong>YLAA</strong>0070ZE<br />

TONS COMP KW EER<br />

100.0 95.0 71.1 78.1 10.1<br />

83.3 88.4 63.2 59.9 11.4<br />

66.7 81.1 54.6 42.2 13.4<br />

50.0 71.1 42.7 28.2 15.4<br />

33.3 60.3 29.9 16.5 18.1<br />

16.7 55.0 15.0 7.7 19.0<br />

% DISPL<br />

AMBIENT<br />

DEG F<br />

IPLV: 15.7<br />

<strong>YLAA</strong>0080ZE<br />

TONS COMP KW EER<br />

100.0 95.0 76.1 87.7 9.7<br />

83.6 88.5 67.8 68.4 10.8<br />

66.7 80.8 58.1 46.4 13.1<br />

50.3 71.1 45.8 32.0 14.9<br />

33.3 59.5 31.0 18.3 17.2<br />

16.9 55.0 16.4 9.7 17.4<br />

IPLV: 15.0<br />

<strong>YLAA</strong>0120ZE<br />

% DISPL<br />

AMBIENT<br />

DEG F<br />

TONS COMP KW EER<br />

100.0 95.0 118.3 134.9 9.8<br />

75.0 83.9 96.5 85.2 12.1<br />

50.0 70.7 70.5 45.1 15.3<br />

25.0 55.0 33.0 23.0 16.1<br />

IPLV: 14.5<br />

<strong>YLAA</strong>0135ZE<br />

% DISPL<br />

AMBIENT<br />

DEG F<br />

TONS COMP KW EER<br />

100.0 95.0 125.8 142.1 9.7<br />

77.7 86.8 108.6 95.6 12.0<br />

67.0 81.1 96.6 77.0 12.8<br />

44.7 67.5 68.2 45.1 15.8<br />

22.3 55.0 34.5 19.9 17.8<br />

IPLV: 14.9<br />

<strong>YLAA</strong>0150ZE<br />

% DISPL<br />

AMBIENT<br />

DEG F<br />

TONS COMP KW EER<br />

100.0 95.0 138.7 160.7 9.6<br />

80.0 87.6 121.7 113.4 11.5<br />

60.0 77.1 97.3 73.5 13.4<br />

% DISPL<br />

AMBIENT<br />

DEG F<br />

<strong>YLAA</strong>0090ZE<br />

TONS COMP KW EER<br />

100.0 95.0 84.6 98.2 9.7<br />

40.0 64.4 68.1 43.5 16.3<br />

20.0 55.0 34.2 19.8 17.8<br />

IPLV: 14.9<br />

83.6 88.1 74.9 74.8 11.0<br />

49.3 69.3 48.4 32.8 15.4<br />

32.8 58.4 33.0 19.7 17.2<br />

16.4 55.0 17.2 9.8 17.9<br />

% DISPL<br />

AMBIENT<br />

DEG F<br />

IPLV: 14.9<br />

<strong>YLAA</strong>0115ZE<br />

TONS COMP KW EER<br />

100.0 95.0 112.5 131.1 9.6<br />

<strong>YLAA</strong>0155ZE<br />

% DISPL<br />

AMBIENT<br />

DEG F<br />

TONS COMP KW EER<br />

100.0 95.0 141.6 163.5 9.6<br />

80.0 87.5 123.8 114.3 11.6<br />

60.0 76.7 98.3 73.9 13.5<br />

40.0 63.7 67.6 43.3 16.2<br />

20.0 55.0 33.8 19.8 17.5<br />

IPLV: 14.8<br />

75.0 84.3 92.4 84.2 11.8<br />

50.0 71.9 69.2 45.3 15.0<br />

25.0 55.0 32.8 22.9 16.1<br />

IPLV: 14.3<br />

26 jOHNSON CONTROLS


Part Load Ratings – High Efficiency<br />

FORM 150.62-EG5 (108)<br />

<strong>YLAA</strong>0091YE<br />

% DISPL<br />

AMBIENT<br />

DEG F<br />

TONS COMP KW EER<br />

100.0 95.0 87.1 88.8 10.6<br />

83.8 88.2 77.3 67.9 11.9<br />

50.0 70.0 50.8 31.6 14.6<br />

16.2 55.0 16.1 9.1 18.0<br />

IPLV: 14.6<br />

<strong>YLAA</strong>0101YE<br />

% DISPL<br />

AMBIENT<br />

DEG F<br />

TONS COMP KW EER<br />

100.0 95.0 97.3 106.6 10.0<br />

86.1 89.3 88.1 84.0 11.2<br />

57.0 75.2 65.2 45.2 14.1<br />

43.0 65.7 49.8 32.1 16.1<br />

13.9 55.0 15.9 9.2 17.5<br />

IPLV: 14.9<br />

jOHNSON CONTROLS<br />

27


Physical Data - English<br />

Refrigerant R-410A<br />

Model Number <strong>YLAA</strong><br />

0070ZE 0080ZE 0090ZE 0091YE<br />

General Unit Data<br />

Nominal Tons, R-410A 65.2 71.9 84.6 87.1<br />

Length 116.1 116.1 116.1 142.7<br />

Width 88.0 88.0 88.0 88.0<br />

Height 95.3 95.3 95.3 95.3<br />

Number of Refrigerant Circuits 2 2 2 2<br />

Refrigerant Charge, Operating<br />

R-410A, ckt1 / ckt2, lbs 58/54 62/57 64/61 85/81<br />

Oil Charge, ckt1 / ckt2, gallons 2.58 / 2.58 3.28 / 2.58 3.28 / 2.76 2.76 / 2.76<br />

Shipping Weight<br />

Aluminum Fin Coils 4464 4893 5301 5862<br />

Copper Fin Coils 5264 5693 6101 7062<br />

Operating Weight<br />

Aluminum Fin Coils 4802 5300 5787 6290<br />

Copper Fin Coils 5602 6100 6587 7490<br />

Compressors, scroll type<br />

Compressors per circuit 3/3 3/3 3/2 2/2<br />

Compressors per unit 6 6 5 4<br />

Nominal Tons per compressor<br />

Circuit 1 13 15 15 15/32<br />

Circuit 2 13 13 15/32 15/32<br />

Condenser<br />

Total Face Area ft 2 106.9 106.9 106.9 160.3<br />

Number of Rows 3 3 3 3<br />

Fins per Inch 17 17 17 17<br />

Condenser Fans, Low Sound<br />

Number of Fans, ckt1./ckt2. 2/2 2/2 2/2 3/3<br />

Fan hp 2 2 2 2<br />

Fan RPM 1160 1160 1160 1160<br />

Total Chiller CFM 52000 52000 52000 78000<br />

Evaporator<br />

Water Volume, gallons 40 49 58 51<br />

Maximum Water Side Pressure, PSIG 150 150 150 150<br />

Maximum Refrigerant Side Pressure, PSIG 450 450 450 450<br />

Water Connections Size, inches 6 6 8 6<br />

28 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

Model Number <strong>YLAA</strong><br />

0101YE 0115ZE 0120ZE 0135ZE 0150ZE 0155ZE<br />

97.3 112.5 118.3 125.8 138.7 141.6<br />

142.7 142.7 142.7 187.7 187.7 187.7<br />

88.0 88.0 88.0 88.0 88.0 88.0<br />

95.3 95.3 95.3 95.3 95.3 95.3<br />

2 2 2 2 2 2<br />

62/106 87/84 91/88 116/106 116/108 118/111<br />

3.28 / 3.33 3.33 / 3.33 3.33 / 3.33 4.99 / 2.76 4.99 / 3.33 4.99 / 3.33<br />

6097 6172 6449 7507 7662 7856<br />

7297 7372 7649 9107 9262 9456<br />

6525 6600 7001 7964 8119 8408<br />

7725 7800 8201 9564 9719 10008<br />

3/2 2/2 2/2 3/2 3/2 3/2<br />

5 4 4 5 5 5<br />

15 32 32 32 32 32<br />

32 32 32 15/32 32 32<br />

160.3 160.3 160.3 213.8 213.8 213.8<br />

3 3 3 3 3 3<br />

17 17 17 17 17 17<br />

2/4 3/3 3/3 4/4 4/4 4/4<br />

2 2 2 2 2 2<br />

1160 1160 1160 1160 1160 1160<br />

78000 78000 78000 104000 104000 104000<br />

51 51 66 55 55 66<br />

150 150 150 150 150 150<br />

450 450 450 450 450 450<br />

6 6 8 8 8 8<br />

jOHNSON CONTROLS<br />

29


Dimensions – Four Fan Units<br />

P<br />

H<br />

F<br />

P<br />

D<br />

R1<br />

R2<br />

W C1 C2<br />

L<br />

<strong>YLAA</strong> Model<br />

L<br />

(length)<br />

W<br />

(width)<br />

H<br />

(height)<br />

F P D C1 C2 R2 R1<br />

<strong>YLAA</strong>0070ZE 116.0 88.3 95.3 89.6 43.9 13.4 19.0 84.5 68.3 23.0<br />

<strong>YLAA</strong>0080ZE 116.0 88.3 95.3 89.6 43.9 15.0 18.6 85.0 68.3 23.0<br />

<strong>YLAA</strong>0090ZE 116.0 88.3 95.3 89.6 43.9 16.3 19.6 83.0 68.3 23.0<br />

NOTE:<br />

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable<br />

operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow<br />

patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety<br />

cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is<br />

no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0''; top<br />

– no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.<br />

30 jOHNSON CONTROLS


Dimensions – Six Fan Units<br />

FORM 150.62-EG5 (108)<br />

F<br />

H<br />

P<br />

D<br />

W<br />

C1<br />

R1<br />

TYP<br />

C2<br />

R2<br />

TYP<br />

L<br />

<strong>YLAA</strong> Model<br />

L<br />

(length)<br />

W<br />

(width)<br />

H<br />

(height)<br />

F P D C1 C2 R2 R1<br />

<strong>YLAA</strong>0091YE 143.5 88.3 95.3 89.6 43.9 15.0 18.6 85.0 96.0 23.0<br />

<strong>YLAA</strong>0101YE 143.5 88.3 95.3 89.6 43.9 15.0 18.6 85.0 96.0 23.0<br />

<strong>YLAA</strong>0115ZE 143.5 88.3 95.3 89.6 43.9 15.0 18.6 85.0 96.0 23.0<br />

<strong>YLAA</strong>0120ZE 143.5 88.3 95.3 89.6 43.9 17.3 22.0 102.0 96.0 23.0<br />

NOTE:<br />

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable<br />

operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow<br />

patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety<br />

cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is<br />

no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0''; top<br />

– no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.<br />

jOHNSON CONTROLS<br />

31


Dimensions – Eight Fan Units<br />

F<br />

H<br />

P<br />

D<br />

W<br />

C1<br />

R3 R2 R1<br />

C2<br />

(TYP)<br />

L<br />

<strong>YLAA</strong> Model<br />

L<br />

(length)<br />

W<br />

(width)<br />

H<br />

(height)<br />

F P D C1 C2 R3 R2 R1<br />

<strong>YLAA</strong>0135ZE 187.5 88.25 95.3 89.6 43.875 16.25 19.6 83 58 65.9 39.2<br />

<strong>YLAA</strong>0150ZE 187.5 88.25 95.3 89.6 43.875 16.25 19.6 83 58 65.9 39.2<br />

<strong>YLAA</strong>0155ZE 187.5 88.25 95.3 89.6 43.875 17.25 22 102 58 65.9 39.2<br />

NOTE:<br />

Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable<br />

operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow<br />

patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety<br />

cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is<br />

no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0''; top<br />

– no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.<br />

32 jOHNSON CONTROLS


Isolator Locations<br />

FORM 150.62-EG5 (108)<br />

B<br />

I1<br />

TYP<br />

I2<br />

TYP<br />

A<br />

AVM LOCATIONS<br />

<strong>YLAA</strong> Model I1 I2 A B<br />

<strong>YLAA</strong>0070ZE 19.5 76.6 1.36 85.5<br />

<strong>YLAA</strong>0080ZE 19.5 76.6 1.36 85.5<br />

<strong>YLAA</strong>0090ZE 19.5 76.6 1.36 85.5<br />

B<br />

I1<br />

TYP<br />

I2<br />

TYP<br />

A<br />

AVM LOCATIONS<br />

<strong>YLAA</strong> Model<br />

I1 I2 A B<br />

<strong>YLAA</strong>0091YE 7.6 117.2 1.4 85.5<br />

<strong>YLAA</strong>0101YE 7.6 117.2 1.4 85.5<br />

<strong>YLAA</strong>0115ZE 7.6 117.2 1.4 85.5<br />

<strong>YLAA</strong>0120ZE 7.6 117.2 1.4 85.5<br />

jOHNSON CONTROLS<br />

33


Isolator Locations - continued<br />

B<br />

I1 I2 I3<br />

TYP TYP TYP<br />

A<br />

AVM LOCATIONS<br />

<strong>YLAA</strong> Model<br />

I1 I2 I3 A B<br />

<strong>YLAA</strong>0035ZE 7.6 69.0 80.0 1.4 85.5<br />

<strong>YLAA</strong>0150ZE 7.6 69.0 80.0 1.4 85.5<br />

<strong>YLAA</strong>0155ZE 7.6 69.0 80.0 1.4 85.5<br />

34 jOHNSON CONTROLS


Isolator Details<br />

FORM 150.62-EG5 (108)<br />

ONE INCH DEFLECTION SPRING ISOLATOR CROSS-REFERENCE<br />

Illustration shows single spring CIP-B or CIP-C mount.<br />

1786 to 2028 lbs 910 to 920 kg CIP-C-<br />

CIP-X-<br />

EQUIPMENT BASE<br />

Dowel Pin is 3/8" dia. for<br />

CIP-A & 1/2" thereafter<br />

A<br />

Mounting may be<br />

operated 1/2" above<br />

Free & Operating<br />

Height.<br />

FERROUS HOUSING<br />

SIDE ACCESS INTERNAL<br />

ADJUSTMENT BOLT<br />

Turn clockwise to load<br />

spring and maintain Free<br />

& Operating Height.<br />

NOTE-<br />

CIP Mounts are not<br />

to be used in seismic<br />

or wind load<br />

applications.<br />

FREE &<br />

OPERATING<br />

HEIGHT<br />

TYPE CIP DIMENSIONS (inches)†<br />

Size A L T W SW HCL HCW MBD SBC<br />

CIP-B 53/4<br />

8 1/4 1/2 2 3/4<br />

7/16 61/2<br />

11/2<br />

3/<br />

8<br />

CIP-C 65/8 8 7 /8 9/16<br />

3 1/2<br />

7 1<br />

/16 7 /4 13/4<br />

3/8<br />

7 1/4<br />

7 7/8<br />

Free<br />

Ht.<br />

61/8<br />

63/4<br />

Min<br />

Ht.<br />

51/4<br />

63/4<br />

NON-SKID NEOPRENE<br />

ACOUSTICAL ISOLATION PAD L<br />

(Bolting to floor is not necessary for<br />

indoor applications)<br />

T<br />

W<br />

†Casting dimensions may vary ±1/8"<br />

SBC<br />

HCL<br />

MAX BOLT<br />

DIA. - MBD<br />

Slot Width - SW<br />

HCW<br />

All springs have additional<br />

travel to solid equal to 50%<br />

of the rated deflection.<br />

BASE PLATE DIMENSIONS<br />

FOR UNITS WITH ALL POINT LOADS LESS THATN 1404 LBS (637 KG)<br />

Weight Range (lbs) Weight Range (kg) Model Number Color<br />

239 to 384 lbs 108 to 174 kg CIP-B- Red<br />

384 to 639 lbs 174 to 290 kg CIP-B- White<br />

639 to 851 lbs 290 to 386 kg CIP-B- Blue<br />

851 to 1064 lbs 386 to 483 kg CIP-B- Gray<br />

1064 to 1404 lbs 483 to 637 kg CIP-B- Black<br />

FOR UNITS WITH ANY POINT LOAD ABOVE 1404 LBS (637 KG)<br />

Weight Range (lbs) Weight Range (kg) Model Number Color<br />

Up to 851 lbs Up to 386 kg CIP-C- Black<br />

851 to 1149 lbs 386 to 521 kg CIP-C- Yellow<br />

1149 to 1489 lbs 521 to 675 kg CIP-C- Black<br />

1489 to 1786 lbs 675 to 910 kg CIP-C-<br />

Yellow w/<br />

Red<br />

Yellow w/<br />

Green<br />

2028 to 2254 lbs 920 to 1022 kg CIP-C- Red w/ Red<br />

2254 to 2936 lbs 1022 to 1332 kg CIP-C- Red w/ Green<br />

jOHNSON CONTROLS<br />

35


contact during<br />

normal operation<br />

Isolator Rubber Details (cont'd)<br />

Snubbing<br />

Collar<br />

E<br />

H<br />

MBD -Max<br />

Bolt<br />

Diameter<br />

T<br />

TWO INCH DEFLECTION, SEISMIC SPRING ISOLATOR CROSS-REFERENCE<br />

HCW<br />

W<br />

HCL<br />

L<br />

SLRS<br />

Adjustment<br />

Bolt<br />

Lower<br />

Restraining<br />

Nut<br />

Enclosed<br />

Steel<br />

Housing<br />

Internal<br />

Neoprene<br />

Acoustical<br />

Pad<br />

Non-Skid Neoprene Pad-<br />

Pad can be removed if<br />

mounts are welded<br />

into position.<br />

ENGLISH<br />

SIZE H T D E L HCL W HCW MBD<br />

2-C2 8 1/2 3/8 5/8 1 3/8 14 12 1/4 5 1/4 3 1/ 2 5/8"<br />

SI<br />

SIZE H T D E L HCL W HCW MBD<br />

2-C2 215.9 9.5 15.9 34.9 355.6 311.2 133.4 88.9 5/8"<br />

*Weight Range<br />

(lbs)<br />

Weight Range<br />

(kg)<br />

Model Number<br />

36 jOHNSON CONTROLS<br />

Color<br />

Up to 358 lbs Up to 162 kg SLRS-2-C2- Red<br />

358 to 443 lbs 162 to 201 kg SLRS-2-C2- White<br />

443 to 582 lbs 201 to 264 kg SLRS-2-C2- Black<br />

582 to 783 lbs 264 to 335 kg SLRS-2-C2- Blue<br />

783 to 1038 lbs 335 to 471 kg SLRS-2-C2- Green<br />

1038 to 1497 lbs 471 to 679 kg SLRS-2-C2- Gray<br />

1497 to 2058 lbs 679 to 933 kg SLRS-2-C2- Silver<br />

2058 to 2619 lbs 933 to 1188 kg SLRS-2-C2- Gray w/ red<br />

2619 to 3180 lbs 1188 to 1442 kg SLRS-2-C2- Silver w/ red


FORM 150.62-EG5 (108)<br />

NEOPRENE ISOLATOR CROSS-REFERENCE<br />

ND-X<br />

"CS" Cap Screw<br />

D<br />

Steel Plate - Top &<br />

Bottom Neoprene<br />

covered to prevent<br />

corrosion<br />

"MBD" Max. Bolt Dia.<br />

H<br />

BC<br />

L<br />

W<br />

T<br />

ENGLISH<br />

Size D H L T W BC CS MBD<br />

ND-C 2 9/16 2 3/ 4 5 1/ 2 1/ 4 2 5/16 4 1/8 1/2- 13 x 1” 1/ 2"<br />

ND-D 3 3/ 8 2 3/ 4 6 1/ 4 5/16 4 5 1/2- 13 x 1” 1/ 2"<br />

ND-DS 3 3/ 8 2 3/ 4 6 1/ 4 5/16 4 5 1/2- 13 x 1” 1/ 2"<br />

SI<br />

ND-C 65.1 69.9 139.7 6.4 58.7 101.9 1/2- 13 x 1” 1/ 2"<br />

ND-D 85.7 69.9 158.8 7.9 101.6 127.0 1/2- 13 x 1” 1/ 2"<br />

ND-DS 85.7 69.9 158.8 7.9 101.6 127.0 1/2- 13 x 1” 1/ 2"<br />

Weight Range<br />

(lbs)<br />

Weight Range<br />

(kg)<br />

Model Number<br />

Color<br />

Up to 751 lbs Up to 341 kg ND-C Yellow<br />

751 to 1651 lbs 341 to 749 kg ND-D Yellow<br />

1651 to 3226 lbs 749 to 1463 kg ND-E Yellow<br />

jOHNSON CONTROLS<br />

37


Electrical Notes<br />

NOTES:<br />

1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the<br />

rated load amps for all other loads included in the circuit, per N.E.C. Article 430‐24. If the optional Factory Mounted<br />

Control Transformer is provided, add the following MCA values to the electrical tables for the system providing power<br />

to the transformer: ‐17, add 2.5 amps; ‐28, add 2.3 amps; ‐40, add 1.5 amps, ‐46, add 1.3 amps; ‐58, add 1 amps.<br />

2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included in<br />

the circuit, per N.E.C. Article 440.<br />

3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load<br />

amps for all other loads included in the circuit to avoid nuisance trips at start‐up due to lock rotor amps. It is not recommended<br />

in applications where brown outs, frequent starting and stopping of the unit, and/or operation at ambient<br />

temperatures in excess of 95ºF (35ºC) is anticipated.<br />

4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load<br />

amps for all other loads included in the circuit, per N.E.C. Article 440-22.<br />

5. Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated load amps for<br />

the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Otherwise, HACR‐type<br />

circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated load amps for<br />

the largest motor plus 100% of the rated load amps for all other loads included in the circuit.<br />

6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the unit wiring<br />

lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire<br />

range specified. Actual wire size and number of wires per phase must be determined based on the National Electrical<br />

Code, using copper connectors only. Field wiring must also comply with local codes.<br />

7. A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C.<br />

Table 250‐95. A control circuit grounding lug is also supplied.<br />

8. The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the<br />

unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to<br />

be a Load Break Device.<br />

9. Field Wiring by others which complies to the National Electrical Code & Local Codes.<br />

LEGEND<br />

ACR-LINE<br />

C.B.<br />

D.E.<br />

DISC SW<br />

FACT MOUNT CB<br />

FLA<br />

HZ<br />

MAX<br />

MCA<br />

MIN<br />

MIN NF<br />

RLA<br />

S.P. WIRE<br />

UNIT MTD SERV SW<br />

LRA<br />

ACROSS THE LINE START<br />

CIRCUIT BREAKER<br />

DUAL ELEMENT FUSE<br />

DISCONNECT SWITCH<br />

FACTORY MOUNTED CIRCUIT BREAKER<br />

FULL LOAD AMPS<br />

HERTZ<br />

MAXIMUM<br />

MINIMUM CIRCUIT AMPACITY<br />

MINIMUM<br />

MINIMUM NON FUSED<br />

RATED LOAD AMPS<br />

SINGLE POINT WIRING<br />

UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT<br />

SWITCH)<br />

LOCKED ROTOR AMPS<br />

Voltage Code<br />

-17 = 200-3-60<br />

-28 = 230-3-60<br />

-40 = 380-3-60<br />

-46 = 460-3-60<br />

-58 = 575-3-60<br />

38 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

INTENTIONALLY LEFT BLANK<br />

jOHNSON CONTROLS<br />

39


Electrical Data w/o Pumps<br />

CHILLER<br />

MODEL<br />

0070<br />

0080<br />

0090<br />

0091<br />

0101<br />

0115<br />

0120<br />

0135<br />

0150<br />

0155<br />

MIN<br />

Volt<br />

Code MCA N/F<br />

DS<br />

MIN<br />

DUAL<br />

ELEM<br />

FUSE<br />

MAX<br />

DUAL<br />

ELEM<br />

FUSE<br />

MAX<br />

CB<br />

SYSTEM # 1 SYSTEM # 2<br />

COMPR 1 COMPR 2 COMPR 3 FAN COMPR 1 COMPR 2 COMPR 3 FAN<br />

RLA LRA RLA LRA RLA LRA QTY FLA LRA RLA LRA RLA LRA RLA LRA QTY FLA LRA<br />

17 351 400 400 400 51 300 51 300 51 300 2 7.6 31 51 300 51 300 51 300 2 7.6 31<br />

23 350 400 400 400 51 300 51 300 51 300 2 7.4 37 51 300 51 300 51 300 2 7.4 37<br />

40 186 250 200 200 27 139 27 139 27 139 2 4.5 22 27 139 27 139 27 139 2 4.5 22<br />

46 160 200 175 175 23 150 23 150 23 150 2 4.0 19 23 150 23 150 23 150 2 4.0 19<br />

58 136 200 150 150 20 109 20 109 20 109 2 2.9 15 20 109 20 109 20 109 2 2.9 15<br />

17 366 600 400 400 56 425 56 425 56 425 2 7.6 31 51 300 51 300 51 300 2 7.6 31<br />

23 365 600 400 400 56 425 56 425 56 425 2 7.4 37 51 300 51 300 51 300 2 7.4 37<br />

40 216 250 225 250 36 239 36 239 36 239 2 4.5 22 27 139 27 139 27 139 2 4.5 22<br />

46 173 200 200 200 27 187 27 187 27 187 2 4.0 19 23 150 23 150 23 150 2 4.0 19<br />

58 148 200 175 175 24 148 24 148 24 148 2 2.9 15 20 109 20 109 20 109 2 2.9 15<br />

17 391 600 450 500 56 425 56 425 56 425 2 7.6 31 110 599 56 425 2 7.6 31<br />

23 390 600 450 450 56 425 56 425 56 425 2 7.4 37 110 599 56 425 2 7.4 37<br />

40 249 400 300 300 36 239 36 239 36 239 2 4.5 22 69 358 36 239 2 4.5 22<br />

46 192 250 225 225 27 187 27 187 27 187 2 4.0 19 55 310 27 187 2 4.0 19<br />

58 168 200 200 200 24 148 24 148 24 148 2 2.9 15 49 239 24 148 2 2.9 15<br />

17 404 600 450 500 110 599 56 425 3 7.6 31 110 599 56 425 3 7.6 31<br />

23 403 600 450 500 110 358 56 425 3 7.4 37 110 599 56 425 3 7.4 37<br />

40 255 400 300 300 69 310 36 239 3 4.5 22 69 358 36 239 3 4.5 22<br />

46 200 250 225 250 55 239 27 187 3 4.0 19 55 310 27 187 3 4.0 19<br />

58 176 200 200 225 49 310 24 148 3 2.9 15 49 239 24 148 3 2.9 15<br />

17 460 600 500 500 56 425 56 425 56 425 2 7.6 31 110 599 110 599 4 7.6 31<br />

23 458 600 500 500 56 425 56 425 56 425 2 7.4 37 110 599 110 599 4 7.4 37<br />

40 291 400 350 350 36 239 36 239 36 239 2 4.5 22 69 358 69 358 4 4.5 22<br />

46 227 250 250 250 27 187 27 187 27 187 2 4.0 19 55 310 55 310 4 4.0 19<br />

58 200 250 225 225 24 148 24 148 24 148 2 2.9 15 49 239 49 239 4 2.9 15<br />

17 511 600 600 600 110 599 110 599 3 7.6 31 110 599 110 599 3 7.6 31<br />

23 510 600 600 600 110 599 110 599 3 7.4 37 110 599 110 599 3 7.4 37<br />

40 321 400 350 350 69 358 69 358 3 4.5 22 69 358 69 358 3 4.5 22<br />

46 255 400 300 300 55 310 55 310 3 4.0 19 55 310 55 310 3 4.0 19<br />

58 227 250 250 250 49 239 49 239 3 2.9 15 49 239 49 239 3 2.9 15<br />

17 582 800 700 700 110 599 110 599 110 599 4 7.6 31 110 599 56 425 4 7.6 31<br />

23 581 800 700 700 110 599 110 599 110 599 4 7.4 37 110 599 56 425 4 7.4 37<br />

40 366 600 400 400 69 358 69 358 69 358 4 4.5 22 69 358 36 239 4 4.5 22<br />

46 291 400 350 350 55 310 55 310 55 310 4 4.0 19 55 310 27 187 4 4.0 19<br />

58 257 400 300 300 49 239 49 239 49 239 4 2.9 15 49 239 24 148 4 2.9 15<br />

17 636 800 700 700 110 599 110 599 110 599 4 7.6 31 110 599 110 599 4 7.6 31<br />

23 635 800 700 700 110 599 110 599 110 599 4 7.4 37 110 599 110 599 4 7.4 37<br />

40 399 600 450 450 69 358 69 358 69 358 4 4.5 22 69 358 69 358 4 4.5 22<br />

46 318 400 350 350 55 310 55 310 55 310 4 4.0 19 55 310 55 310 4 4.0 19<br />

58 283 400 300 300 49 239 49 239 49 239 4 2.9 15 49 239 49 239 4 2.9 15<br />

40 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

Lug Sizing<br />

Non-Fuse Disc Sw. Circuit Breaker Terminal Block<br />

Rating Size Lug Rating Size Lug Lug<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 400 S5-400 S5: (2) 3/0 - 250kcmil (4) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 400 S5-400 S5: (2) 3/0 - 250kcmil (4) 4AWG - 500kcmil<br />

250 S4-250 S4: 6AWG - 350kcmil 200 S3-225 S3-S4-S5: 4AWG - 300kcmil (2) 4AWG - 500kcmil<br />

200 S3-225 S3-S4-S5: 4AWG - 300kcmil 175 S3-175 S3-S4-S5: 4AWG - 300kcmil (2) 4AWG - 500kcmil<br />

200 S3-225 S3-S4-S5: 4AWG - 300kcmil 150 S3-150 S3-S4: 2AWG - 4/0 (2) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 400 S5-400 S5: (2) 3/0 - 250kcmil (4) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 400 S5-400 S5: (2) 3/0 - 250kcmil (4) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 250 S4-250 S4: 6AWG - 350kcmil (2) 4AWG - 500kcmil<br />

250 S4-250 S4: 6AWG - 350kcmil 200 S3-225 S3-S4-S5: 4AWG - 300kcmil (2) 4AWG - 500kcmil<br />

200 S3-225 S3-S4-S5: 4AWG - 300kcmil 175 S3-175 S3-S4-S5: 4AWG - 300kcmil (2) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 500 S6-600 S6: (2) 250kcmil - 500kcmil (4) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 450 S6-600 S6: (2) 250kcmil - 500kcmil (4) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 300 S5-400 S5: (2) 3/0 - 250kcmil (2) 4AWG - 500kcmil<br />

250 S4-250 S4: 6AWG - 350kcmil 225 S3-225 S3-S4-S5: 4AWG - 300kcmil (2) 4AWG - 500kcmil<br />

250 S4-250 S4: 6AWG - 350kcmil 200 S3-225 S3-S4-S5: 4AWG - 300kcmil (2) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 500 S6-600 S6: (2) 250kcmil - 500kcmil (4) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 500 S6-600 S6: (2) 250kcmil - 500kcmil (4) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 300 S5-400 S5: (2) 3/0 - 250kcmil (2) 4AWG - 500kcmil<br />

250 S4-250 S4: 6AWG - 350kcmil 250 S4-250 S4: 6AWG - 350kcmil (2) 4AWG - 500kcmil<br />

250 S4-250 S4: 6AWG - 350kcmil 225 S3-225 S3-S4-S5: 4AWG - 300kcmil (2) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 500 S6-600 S6: (2) 250kcmil - 500kcmil (4) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 500 S6-600 S6: (2) 250kcmil - 500kcmil (4) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 350 S5-400 S5: (2) 3/0 - 250kcmil (2) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 250 S4-250 S4: 6AWG - 350kcmil (2) 4AWG - 500kcmil<br />

250 S4-250 S4: 6AWG - 350kcmil 225 S3-225 S3-S4-S5: 4AWG - 300kcmil (2) 4AWG - 500kcmil<br />

800 S6-800 S6: (3) 2/0 - 400kcmil 600 S6-600 S6: (2) 250kcmil - 500kcmil (4) 4AWG - 500kcmil<br />

800 S6-800 S6: (3) 2/0 - 400kcmil 600 S6-600 S6: (2) 250kcmil - 500kcmil (4) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 350 S5-400 S5: (2) 3/0 - 250kcmil (4) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 300 S5-400 S5: (2) 3/0 - 250kcmil (2) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 250 S4-250 S4: 6AWG - 350kcmil (2) 4AWG - 500kcmil<br />

800 S6-800 S6: (3) 2/0 - 400kcmil 700 S6-800 S6: (3) 2/0 - 400kcmil (4) 4AWG - 500kcmil<br />

800 S6-800 S6: (3) 2/0 - 400kcmil 700 S6-800 S6: (3) 2/0 - 400kcmil (4) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 400 S5-400 S5: (2) 3/0 - 250kcmil (4) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 350 S5-400 S5: (2) 3/0 - 250kcmil (2) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 300 S5-400 S5: (2) 3/0 - 250kcmil (2) 4AWG - 500kcmil<br />

800 S6-800 S6: (3) 2/0 - 400kcmil 700 S6-800 S6: (3) 2/0 - 400kcmil (4) 4AWG - 500kcmil<br />

800 S6-800 S6: (3) 2/0 - 400kcmil 700 S6-800 S6: (3) 2/0 - 400kcmil (4) 4AWG - 500kcmil<br />

600 S6-600 S6: (2) 250kcmil - 500kcmil 450 S6-600 S6: (2) 250kcmil - 500kcmil (4) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 350 S5-400 S5: (2) 3/0 - 250kcmil (4) 4AWG - 500kcmil<br />

400 S5-400 S5: (2) 3/0 - 250kcmil 300 S5-400 S5: (2) 3/0 - 250kcmil (2) 4AWG - 500kcmil<br />

jOHNSON CONTROLS<br />

41


Electrical Data w/ Pumps<br />

CHILLER<br />

MODEL<br />

Pump<br />

Model<br />

0070 A, K<br />

0070 B<br />

0070 C<br />

0070 D, M, N<br />

0070 L<br />

0080 A, K<br />

0080 B<br />

0080 C<br />

0080 D, M, N<br />

0080 L<br />

Volt<br />

Code<br />

Pump<br />

FLA<br />

MCA<br />

MIN<br />

N/F<br />

DS<br />

MIN<br />

DUAL<br />

ELEM<br />

FUSE<br />

MAX<br />

DUAL<br />

ELEM<br />

FUSE<br />

MAX CB<br />

SYSTEM # 1<br />

COMPR 1 COMPR 2 COMPR 3 FAN<br />

RLA LRA RLA LRA RLA LRA QTY FLA LRA<br />

17 15.4 366 600 400 400 51 300 51 300 51 300 2 7.6 31<br />

23 13.9 364 600 400 400 51 300 51 300 51 300 2 7.4 37<br />

40 8.1 194 250 225 225 27 139 27 139 27 139 2 4.5 22<br />

46 6.95 167 200 175 175 23 150 23 150 23 150 2 4.0 19<br />

58 5.56 142 200 150 150 20 109 20 109 20 109 2 2.9 15<br />

17 21.4 372 600 400 400 51 300 51 300 51 300 2 7.6 31<br />

23 20.4 371 600 400 400 51 300 51 300 51 300 2 7.4 37<br />

40 12 198 250 225 225 27 139 27 139 27 139 2 4.5 22<br />

46 10.2 171 200 200 200 23 150 23 150 23 150 2 4.0 19<br />

58 8.2 144 200 150 150 20 109 20 109 20 109 2 2.9 15<br />

17 32.2 383 600 400 400 51 300 51 300 51 300 2 7.6 31<br />

23 28.4 379 600 400 400 51 300 51 300 51 300 2 7.4 37<br />

40 15.4 202 250 225 225 27 139 27 139 27 139 2 4.5 22<br />

46 14.2 175 200 200 200 23 150 23 150 23 150 2 4.0 19<br />

58 11.4 147 200 175 150 20 109 20 109 20 109 2 2.9 15<br />

17 41.7 393 600 450 450 51 300 51 300 51 300 2 7.6 31<br />

23 36.3 387 600 400 400 51 300 51 300 51 300 2 7.4 37<br />

40 22.03 208 250 225 225 27 139 27 139 27 139 2 4.5 22<br />

46 18.2 179 200 200 200 23 150 23 150 23 150 2 4.0 19<br />

58 14.5 150 200 175 175 20 109 20 109 20 109 2 2.9 15<br />

17 27.1 378 600 400 400 51 300 51 300 51 300 2 7.6 31<br />

23 24.5 375 600 400 400 51 300 51 300 51 300 2 7.4 37<br />

40 14.8 201 250 225 225 27 139 27 139 27 139 2 4.5 22<br />

46 12.3 173 200 200 200 23 150 23 150 23 150 2 4.0 19<br />

58 9.84 146 200 175 175 20 109 20 109 20 109 2 2.9 15<br />

17 15.4 381 600 400 400 56 425 56 425 56 425 2 7.6 31<br />

23 13.9 379 600 400 400 56 425 56 425 56 425 2 7.4 37<br />

40 8.1 224 250 250 250 36 239 36 239 36 239 2 4.5 22<br />

46 6.95 180 200 200 200 27 187 27 187 27 187 2 4.0 19<br />

58 5.56 154 200 175 175 24 148 24 148 24 148 2 2.9 15<br />

17 21.4 387 600 450 450 56 425 56 425 56 425 2 7.6 31<br />

23 20.4 385 600 400 400 56 425 56 425 56 425 2 7.4 37<br />

40 12 228 400 250 250 36 239 36 239 36 239 2 4.5 22<br />

46 10.2 183 250 200 200 27 187 27 187 27 187 2 4.0 19<br />

58 8.2 157 200 175 175 24 148 24 148 24 148 2 2.9 15<br />

17 32.2 398 600 450 450 56 425 56 425 56 425 2 7.6 31<br />

23 28.4 393 600 450 450 56 425 56 425 56 425 2 7.4 37<br />

40 15.4 231 400 250 250 36 239 36 239 36 239 2 4.5 22<br />

46 14.2 187 250 200 200 27 187 27 187 27 187 2 4.0 19<br />

58 11.4 160 200 175 175 24 148 24 148 24 148 2 2.9 15<br />

17 41.7 407 600 450 450 56 425 56 425 56 425 2 7.6 31<br />

23 36.3 401 600 450 450 56 425 56 425 56 425 2 7.4 37<br />

40 22.03 238 400 250 250 36 239 36 239 36 239 2 4.5 22<br />

46 18.2 191 250 200 200 27 187 27 187 27 187 2 4.0 19<br />

58 14.5 163 200 175 175 24 148 24 148 24 148 2 2.9 15<br />

17 27.1 393 600 450 450 56 425 56 425 56 425 2 7.6 31<br />

23 24.5 389 600 450 450 56 425 56 425 56 425 2 7.4 37<br />

40 14.8 231 400 250 250 36 239 36 239 36 239 2 4.5 22<br />

46 12.3 185 250 200 200 27 187 27 187 27 187 2 4.0 19<br />

58 9.84 158 200 175 175 24 148 24 148 24 148 2 2.9 15<br />

42 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

SYSTEM # 2<br />

COMPR 1 COMPR 2 COMPR 3 FAN<br />

Non-Fuse Disc Sw.<br />

RLA LRA RLA LRA RLA LRA QTY FLA LRA Rating Size Lug<br />

51 300 51 300 51 300 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.4 37 250 S4-250 S4: 6AWG - 350kcmil<br />

27 139 27 139 27 139 2 4.5 22 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

23 150 23 150 23 150 2 4.0 19 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

20 109 20 109 20 109 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.4 37 250 S4-250 S4: 6AWG - 350kcmil<br />

27 139 27 139 27 139 2 4.5 22 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

23 150 23 150 23 150 2 4.0 19 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

20 109 20 109 20 109 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.4 37 250 S4-250 S4: 6AWG - 350kcmil<br />

27 139 27 139 27 139 2 4.5 22 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

23 150 23 150 23 150 2 4.0 19 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

20 109 20 109 20 109 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.4 37 250 S4-250 S4: 6AWG - 350kcmil<br />

27 139 27 139 27 139 2 4.5 22 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

23 150 23 150 23 150 2 4.0 19 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

20 109 20 109 20 109 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.4 37 250 S4-250 S4: 6AWG - 350kcmil<br />

27 139 27 139 27 139 2 4.5 22 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

23 150 23 150 23 150 2 4.0 19 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

20 109 20 109 20 109 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

27 139 27 139 27 139 2 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

23 150 23 150 23 150 2 4.0 19 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

20 109 20 109 20 109 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

27 139 27 139 27 139 2 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

23 150 23 150 23 150 2 4.0 19 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

20 109 20 109 20 109 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

27 139 27 139 27 139 2 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

23 150 23 150 23 150 2 4.0 19 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

20 109 20 109 20 109 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

27 139 27 139 27 139 2 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

23 150 23 150 23 150 2 4.0 19 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

20 109 20 109 20 109 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

51 300 51 300 51 300 2 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

27 139 27 139 27 139 2 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

23 150 23 150 23 150 2 4.0 19 200 S3-225 S3-S4-S5: 4AWG - 300kcmil<br />

20 109 20 109 20 109 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

jOHNSON CONTROLS<br />

43


Electrical Data w/ Pumps – continued<br />

CHILLER<br />

MODEL<br />

Pump<br />

Model<br />

0090 A, K<br />

0090 B<br />

0090 D, M, N<br />

0090 E<br />

0090 L<br />

0091 A, K<br />

0091 B<br />

0091 D, M, N<br />

0091 E<br />

0091 L<br />

Volt<br />

Code<br />

Pump<br />

FLA<br />

MCA<br />

MIN<br />

N/F<br />

DS<br />

MIN<br />

DUAL<br />

ELEM<br />

FUSE<br />

MAX<br />

DUAL<br />

ELEM<br />

FUSE<br />

MAX CB<br />

SYSTEM # 1<br />

COMPR 1 COMPR 2 COMPR 3 FAN<br />

RLA LRA RLA LRA RLA LRA QTY FLA LRA<br />

17 15.4 406 600 450 500 56 425 56 425 56 425 2 7.6 31<br />

23 13.9 404 600 450 500 56 425 56 425 56 425 2 7.4 37<br />

40 8.1 257 400 300 300 36 239 36 239 36 239 2 4.5 22<br />

46 7 199 250 225 250 27 187 27 187 27 187 2 4.0 19<br />

58 5.6 174 200 200 200 24 148 24 148 24 148 2 2.9 15<br />

17 21.4 412 600 450 500 56 425 56 425 56 425 2 7.6 31<br />

23 20.4 410 600 450 500 56 425 56 425 56 425 2 7.4 37<br />

40 12 261 400 300 300 36 239 36 239 36 239 2 4.5 22<br />

46 10.2 202 250 225 250 27 187 27 187 27 187 2 4.0 19<br />

58 8.2 176 200 200 225 24 148 24 148 24 148 2 2.9 15<br />

17 41.7 432 600 500 500 56 425 56 425 56 425 2 7.6 31<br />

23 36.3 426 600 500 500 56 425 56 425 56 425 2 7.4 37<br />

40 22 271 400 300 300 36 239 36 239 36 239 2 4.5 22<br />

46 18.2 210 250 225 250 27 187 27 187 27 187 2 4.0 19<br />

58 14.5 183 200 200 225 24 148 24 148 24 148 2 2.9 15<br />

17 54.7 445 600 500 500 56 425 56 425 56 425 2 7.6 31<br />

23 49.5 439 600 500 500 56 425 56 425 56 425 2 7.4 37<br />

40 29.1 278 400 300 300 36 239 36 239 36 239 2 4.5 22<br />

46 24.8 217 250 250 250 27 187 27 187 27 187 2 4.0 19<br />

58 19.8 188 250 225 225 24 148 24 148 24 148 2 2.9 15<br />

17 27.1 418 600 450 500 56 425 56 425 56 425 2 7.6 31<br />

23 24.5 414 600 450 500 56 425 56 425 56 425 2 7.4 37<br />

40 14.8 263 400 300 300 36 239 36 239 36 239 2 4.5 22<br />

46 12.3 204 250 225 250 27 187 27 187 27 187 2 4.0 19<br />

58 9.8 178 200 200 225 24 148 24 148 24 148 2 2.9 15<br />

17 15.4 419 600 450 500 110 599 56 425 3 7.6 31<br />

23 13.9 417 600 450 500 110 358 56 425 3 7.4 37<br />

40 8.1 263 400 300 300 69 310 36 239 3 4.5 22<br />

46 7 207 250 225 250 55 239 27 187 3 4.0 19<br />

58 5.6 182 200 200 225 49 310 24 148 3 2.9 15<br />

17 21.4 425 600 500 500 110 599 56 425 3 7.6 31<br />

23 20.4 423 600 500 500 110 358 56 425 3 7.4 37<br />

40 12 267 400 300 300 69 310 36 239 3 4.5 22<br />

46 10.2 211 250 225 250 55 239 27 187 3 4.0 19<br />

58 8.2 184 200 200 225 49 310 24 148 3 2.9 15<br />

17 41.7 446 600 500 500 110 599 56 425 3 7.6 31<br />

23 36.3 439 600 500 500 110 358 56 239 3 7.4 37<br />

40 22 277 400 300 300 69 310 36 187 3 4.5 22<br />

46 18.2 219 250 250 250 55 239 27 148 3 4.0 19<br />

58 14.5 190 250 225 225 49 310 24 425 3 2.9 15<br />

17 54.7 459 600 500 500 110 599 56 425 3 7.6 31<br />

23 49.5 452 600 500 500 110 358 56 425 3 7.4 37<br />

40 29.1 284 400 350 350 69 310 36 239 3 4.5 22<br />

46 24.8 225 250 250 250 55 239 27 187 3 4.0 19<br />

58 19.8 196 250 225 225 49 310 24 148 3 2.9 15<br />

17 27.1 431 600 500 500 110 599 56 425 3 7.6 31<br />

23 24.5 427 600 500 500 110 358 56 425 3 7.4 37<br />

40 14.8 270 400 300 300 69 310 36 239 3 4.5 22<br />

46 12.3 213 250 250 250 55 239 27 187 3 4.0 19<br />

58 9.8 186 200 200 225 49 310 24 148 3 2.9 15<br />

44 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

SYSTEM # 2<br />

COMPR 1 COMPR 2 COMPR 3 FAN<br />

Non-Fuse Disc Sw.<br />

RLA LRA RLA LRA RLA LRA QTY FLA LRA Rating Size Lug<br />

110 599 56 425 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 2 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 36 239 2 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

55 310 27 187 2 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 24 148 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 2 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 36 239 2 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

55 310 27 187 2 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 24 148 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 2 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 36 239 2 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

55 310 27 187 2 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 24 148 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 2 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 36 239 2 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

55 310 27 187 2 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 24 148 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 2 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 2 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 36 239 2 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

55 310 27 187 2 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 24 148 2 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 3 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 36 239 3 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

55 310 27 187 3 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 24 148 3 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 3 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 36 239 3 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

55 310 27 187 3 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 24 148 3 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 3 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 36 239 3 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

55 310 27 187 3 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 24 148 3 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 3 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 36 239 3 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

55 310 27 187 3 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 24 148 3 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 3 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 56 425 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 36 239 3 4.5 22 250 S4-250 S4: 6AWG - 350kcmil<br />

55 310 27 187 3 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 24 148 3 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

jOHNSON CONTROLS<br />

45


Electrical Data w/ Pumps – continued<br />

CHILLER<br />

MODEL<br />

Pump<br />

Model<br />

0101 B, F<br />

0101 D, O<br />

0101 E, P<br />

0101 K<br />

0101 L<br />

0115<br />

0120<br />

0115<br />

0120<br />

0115<br />

0120*<br />

0115<br />

0120<br />

0115<br />

0120<br />

F<br />

C<br />

D, M*, O<br />

E, P<br />

K<br />

Volt<br />

Code<br />

Pump<br />

FLA<br />

MCA<br />

MIN<br />

N/F<br />

DS<br />

MIN<br />

DUAL<br />

ELEM<br />

FUSE<br />

MAX<br />

DUAL<br />

ELEM<br />

FUSE<br />

MAX CB<br />

SYSTEM # 1<br />

COMPR 1 COMPR 2 COMPR 3 FAN<br />

RLA LRA RLA LRA RLA LRA QTY FLA LRA<br />

17 21.4 481 600 600 600 56 425 56 425 56 425 2 7.6 31<br />

23 20.4 479 600 600 600 56 425 56 425 56 425 2 7.4 37<br />

40 12 303 400 350 350 36 239 36 239 36 239 2 4.5 22<br />

46 10.2 238 400 300 300 27 187 27 187 27 187 2 4.0 19<br />

58 8.2 208 250 225 250 24 148 24 148 24 148 2 2.9 15<br />

17 41.7 501 600 600 600 56 425 56 425 56 425 2 7.6 31<br />

23 36.3 495 600 600 600 56 425 56 425 56 425 2 7.4 37<br />

40 22 313 400 350 350 36 239 36 239 36 239 2 4.5 22<br />

46 18.2 246 400 300 300 27 187 27 187 27 187 2 4.0 19<br />

58 14.5 214 250 250 250 24 148 24 148 24 148 2 2.9 15<br />

17 54.7 514 600 600 600 56 425 56 425 56 425 2 7.6 31<br />

23 49.5 508 600 600 600 56 425 56 425 56 425 2 7.4 37<br />

40 29.1 320 400 350 350 36 239 36 239 36 239 2 4.5 22<br />

46 24.8 252 400 300 300 27 187 27 187 27 187 2 4.0 19<br />

58 19.8 219 250 250 250 24 148 24 148 24 148 2 2.9 15<br />

17 15.4 475 600 600 600 56 425 56 425 56 425 2 7.6 31<br />

23 13.9 472 600 500 500 56 425 56 425 56 425 2 7.4 37<br />

40 8.1 299 400 350 350 36 239 36 239 36 239 2 4.5 22<br />

46 7 234 400 250 250 27 187 27 187 27 187 2 4.0 19<br />

58 5.6 205 250 225 250 24 148 24 148 24 148 2 2.9 15<br />

17 27.1 487 600 600 600 56 425 56 425 56 425 2 7.6 31<br />

23 24.5 483 600 600 600 56 425 56 425 56 425 2 7.4 37<br />

40 14.8 306 400 350 350 36 239 36 239 36 239 2 4.5 22<br />

46 12.3 240 400 300 300 27 187 27 187 27 187 2 4.0 19<br />

58 9.8 209 250 225 250 24 148 24 148 24 148 2 2.9 15<br />

17 21.4 532 600 600 600 110 599 110 599 3 7.6 31<br />

23 20.4 530 600 600 600 110 599 110 599 3 7.4 37<br />

40 12 333 400 400 400 69 358 69 358 3 4.5 22<br />

46 10.2 265 400 300 300 55 310 55 310 3 4.0 19<br />

58 8.2 235 400 250 250 49 239 49 239 3 2.9 15<br />

17 32.2 543 600 600 600 110 599 110 599 3 7.6 31<br />

23 28.4 538 600 600 600 110 599 110 599 3 7.4 37<br />

40 15.4 336 400 400 400 69 358 69 358 3 4.5 22<br />

46 14.2 269 400 300 300 55 310 55 310 3 4.0 19<br />

58 11.4 238 400 300 300 49 239 49 239 3 2.9 15<br />

17 41.7 552 800 600 600 110 599 110 599 3 7.6 31<br />

23 36.3 546 600 600 600 110 599 110 599 3 7.4 37<br />

40 22 343 400 400 400 69 358 69 358 3 4.5 22<br />

46 18.2 273 400 300 300 55 310 55 310 3 4.0 19<br />

58 14.5 241 400 300 300 49 239 49 239 3 2.9 15<br />

17 54.7 565 800 600 600 110 599 110 599 3 7.6 31<br />

23 49.5 559 800 600 600 110 599 110 599 3 7.4 37<br />

40 29.1 350 400 400 400 69 358 69 358 3 4.5 22<br />

46 24.8 280 400 300 300 55 310 55 310 3 4.0 19<br />

58 19.8 247 400 300 300 49 239 49 239 3 2.9 15<br />

17 15.4 526 600 600 600 110 599 110 599 3 7.6 31<br />

23 13.9 523 600 600 600 110 599 110 599 3 7.4 37<br />

40 8.1 329 400 350 350 69 358 69 358 3 4.5 22<br />

46 7 262 400 300 300 55 310 55 310 3 4.0 19<br />

58 5.6 232 400 250 250 49 239 49 239 3 2.9 15<br />

46 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

SYSTEM # 2<br />

COMPR 1 COMPR 2 COMPR 3 FAN<br />

Non-Fuse Disc Sw.<br />

RLA LRA RLA LRA RLA LRA QTY FLA LRA Rating Size Lug<br />

110 599 110 599 4 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 110 599 4 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 4 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 49 239 4 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 110 599 4 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 110 599 4 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 4 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 49 239 4 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 110 599 4 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 110 599 4 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 4 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 49 239 4 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 110 599 4 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 110 599 4 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 4 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 49 239 4 2.9 15 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 110 599 4 7.6 31 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

110 599 110 599 4 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 4 4.0 19 250 S4-250 S4: 6AWG - 350kcmil<br />

49 239 49 239 4 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 3 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 3 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 49 239 3 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 3 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 3 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 49 239 3 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 3 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 3 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 49 239 3 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 3 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 3 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 49 239 3 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 3 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 3 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 49 239 3 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

jOHNSON CONTROLS<br />

47


Electrical Data w/ Pumps – continued<br />

CHILLER<br />

MODEL<br />

Pump<br />

Model<br />

0115 L<br />

0135 F<br />

0135 C<br />

0135 D, M, O<br />

0135 E, R<br />

0135 K<br />

0150<br />

0155<br />

0150<br />

0155<br />

0150<br />

0155<br />

0150<br />

0155<br />

G<br />

H, L<br />

I, M<br />

J, R<br />

Volt<br />

Code<br />

Pump<br />

FLA<br />

MCA<br />

MIN<br />

N/F<br />

DS<br />

MIN<br />

DUAL<br />

ELEM<br />

FUSE<br />

MAX<br />

DUAL<br />

ELEM<br />

FUSE<br />

MAX CB<br />

SYSTEM # 1<br />

COMPR 1 COMPR 2 COMPR 3 FAN<br />

RLA LRA RLA LRA RLA LRA QTY FLA LRA<br />

17 27.1 538 600 600 600 110 599 110 599 3 7.6 31<br />

23 24.5 534 600 600 600 110 599 110 599 3 7.4 37<br />

40 14.8 336 400 400 400 69 358 69 358 3 4.5 22<br />

46 12.3 268 400 300 300 55 310 55 310 3 4.0 19<br />

58 9.8 237 400 250 250 49 239 49 239 3 2.9 15<br />

17 21.4 604 800 700 700 110 599 110 599 110 599 4 7.6 31<br />

23 20.4 601 800 700 700 110 599 110 599 110 599 4 7.4 37<br />

40 12 378 600 400 400 69 358 69 358 69 358 4 4.5 22<br />

46 10.2 301 400 350 350 55 310 55 310 55 310 4 4.0 19<br />

58 8.2 265 400 300 300 49 239 49 239 49 239 4 2.9 15<br />

17 32.2 615 800 700 700 110 599 110 599 110 599 4 7.6 31<br />

23 28.4 609 800 700 700 110 599 110 599 110 599 4 7.4 37<br />

40 15.4 382 600 400 450 69 358 69 358 69 358 4 4.5 22<br />

46 14.2 305 400 350 350 55 310 55 310 55 310 4 4.0 19<br />

58 11.4 268 400 300 300 49 239 49 239 49 239 4 2.9 15<br />

17 41.7 624 800 700 700 110 599 110 599 110 599 4 7.6 31<br />

23 36.3 617 800 700 700 110 599 110 599 110 599 4 7.4 37<br />

40 22 388 600 450 450 69 358 69 358 69 358 4 4.5 22<br />

46 18.2 309 400 350 350 55 310 55 310 55 310 4 4.0 19<br />

58 14.5 271 400 300 300 49 239 49 239 49 239 4 2.9 15<br />

17 54.7 637 800 700 700 110 599 110 599 110 599 4 7.6 31<br />

23 49.5 630 800 700 700 110 599 110 599 110 599 4 7.4 37<br />

40 29.1 395 600 450 450 69 358 69 358 69 358 4 4.5 22<br />

46 24.8 315 400 350 350 55 310 55 310 55 310 4 4.0 19<br />

58 19.8 277 400 300 300 49 239 49 239 49 239 4 2.9 15<br />

17 15.4 598 800 700 700 110 599 110 599 110 599 4 7.6 31<br />

23 13.9 595 800 700 700 110 599 110 599 110 599 4 7.4 37<br />

40 8.1 374 600 400 400 69 358 69 358 69 358 4 4.5 22<br />

46 7 297 400 350 350 55 310 55 310 55 310 4 4.0 19<br />

58 5.6 262 400 300 300 49 239 49 239 49 239 4 2.9 15<br />

17 32.2 668 800 700 700 110 599 110 599 110 599 4 7.6 31<br />

23 28.4 663 800 700 700 110 599 110 599 110 599 4 7.4 37<br />

40 15.4 414 600 450 450 69 358 69 358 69 358 4 4.5 22<br />

46 14.2 332 400 350 350 55 310 55 310 55 310 4 4.0 19<br />

58 11.4 294 400 350 350 49 239 49 239 49 239 4 2.9 15<br />

17 27.1 663 800 700 700 110 599 110 599 110 599 4 7.6 31<br />

23 24.5 659 800 700 700 110 599 110 599 110 599 4 7.4 37<br />

40 14.8 414 600 450 450 69 358 69 358 69 358 4 4.5 22<br />

46 12.3 330 400 350 350 55 310 55 310 55 310 4 4.0 19<br />

58 9.8 292 400 350 350 49 239 49 239 49 239 4 2.9 15<br />

17 41.7 678 800 800 800 110 599 110 599 110 599 4 7.6 31<br />

23 36.3 671 800 700 700 110 599 110 599 110 599 4 7.4 37<br />

40 22 421 600 450 450 69 358 69 358 69 358 4 4.5 22<br />

46 18.2 336 400 350 350 55 310 55 310 55 310 4 4.0 19<br />

58 14.5 297 400 350 350 49 239 49 239 49 239 4 2.9 15<br />

17 54.7 691 800 800 800 110 599 110 599 110 599 4 7.6 31<br />

23 49.5 684 800 800 800 110 599 110 599 110 599 4 7.4 37<br />

40 29.1 428 600 450 450 69 358 69 358 69 358 4 4.5 22<br />

46 24.8 343 400 400 400 55 310 55 310 55 310 4 4.0 19<br />

58 19.8 302 400 350 350 49 239 49 239 49 239 4 2.9 15<br />

48 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

SYSTEM # 2<br />

COMPR 1 COMPR 2 COMPR 3 FAN<br />

Non-Fuse Disc Sw.<br />

RLA LRA RLA LRA RLA LRA QTY FLA LRA Rating Size Lug<br />

110 599 110 599 3 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 3 7.4 37 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

69 358 69 358 3 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 3 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 49 239 3 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 56 425 4 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 56 425 4 7.4 37 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

69 358 36 239 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 27 187 4 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 24 148 4 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 56 425 4 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 56 425 4 7.4 37 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

69 358 36 239 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 27 187 4 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 24 148 4 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 56 425 4 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 56 425 4 7.4 37 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

69 358 36 239 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 27 187 4 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 24 148 4 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 56 425 4 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 56 425 4 7.4 37 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

69 358 36 239 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 27 187 4 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 24 148 4 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 56 425 4 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 56 425 4 7.4 37 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

69 358 36 239 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 27 187 4 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 24 148 4 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 4 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 4 7.4 37 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

69 358 69 358 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 4 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 49 239 4 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 4 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 4 7.4 37 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

69 358 69 358 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 4 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 49 239 4 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 4 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 4 7.4 37 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

69 358 69 358 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 4 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 49 239 4 2.9 15 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 4 7.6 31 800 S6-800 S6: (3) 2/0 - 400kcmil<br />

110 599 110 599 4 7.4 37 600 S6-600 S6: (2) 250kcmil - 500kcmil<br />

69 358 69 358 4 4.5 22 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

55 310 55 310 4 4.0 19 400 S5-400 S5: (2) 3/0 - 250kcmil<br />

49 239 49 239 4 2.9 15 1000 S7-1000 S7-1200: (4) 4/0 - 500kcmil<br />

jOHNSON CONTROLS<br />

49


Wiring Diagram<br />

50 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

jOHNSON CONTROLS<br />

51


1.6<br />

/1.3<br />

/1.2<br />

1L1<br />

NB1 NB1<br />

1L1 /3.1 /4.2 /5.1 /7.2 /11.1<br />

1L2 /3.1 /4.2 /5.1 /7.2 /11.1<br />

1L3 /3.1 /4.2 /5.1 /7.2 /11.1<br />

460V-3-60HZ<br />

380/415V-3-50/60HZ<br />

U V W<br />

=1-TC<br />

.9<br />

NB20<br />

PE<br />

NB17<br />

L3<br />

/1.6 /1.7<br />

/1.7 /1.7 /1.7<br />

/1.3 /1.3<br />

1 3 5<br />

1 3 5<br />

/1.4 /1.4 /1.4<br />

/1.2 /1.2<br />

/1.2 /1.2 /1.2<br />

1L2 1L3 =1-QCB =2-QCB<br />

2L1 2L2 2L3<br />

2<br />

4<br />

6<br />

460V-3-60HZ<br />

380/415V-3-50/60HZ NB1 460V-3-60HZ<br />

2<br />

1<br />

4<br />

3<br />

6<br />

5<br />

2<br />

PE<br />

4<br />

6<br />

NB20<br />

=2-TC<br />

.10<br />

2L1 /3.6 /4.6 /9.2 /13.1<br />

2L2 /3.6 /4.6 /9.2 /13.1<br />

2L3 /3.6 /4.6 /9.2 /13.1<br />

2<br />

1<br />

4<br />

3<br />

6<br />

5<br />

-QSD<br />

NB16<br />

380/415V-3-50/60HZ<br />

2<br />

1<br />

4<br />

3<br />

6<br />

5<br />

PE<br />

13<br />

=1-KM1 =1-KM2 =1-KM3<br />

/2.11<br />

/2.10<br />

/2.10<br />

14<br />

14<br />

13<br />

=2-KM1 =2-KM2 =2-KM3<br />

/2.7<br />

/2.6<br />

/2.5<br />

14<br />

14<br />

13<br />

13<br />

13<br />

14<br />

13<br />

14<br />

-XTBC2<br />

25<br />

-XTBC2<br />

26<br />

-XTBC2<br />

27<br />

-XTBC2<br />

28<br />

=1-KCR<br />

NB1 /2.2<br />

24<br />

NB1<br />

NB1<br />

=2-KCR<br />

/2.1<br />

23<br />

23<br />

24<br />

-XTBC2<br />

29<br />

-XTBC2<br />

30<br />

-XTBC2<br />

31<br />

-XTBC2<br />

32<br />

NB1<br />

1<br />

/2.1<br />

/5.1<br />

?A<br />

-XTBC2<br />

NB9<br />

20A<br />

110V<br />

L<br />

5<br />

2<br />

NB18<br />

115V-1-50/60HZ<br />

PE<br />

L1<br />

NB10<br />

GND<br />

N<br />

NB18<br />

POWER<br />

2 /6.1<br />

1 /6.1<br />

2 /2.1<br />

/8.1<br />

/8.1<br />

/3.2<br />

/10.1<br />

/10.1<br />

/4.2<br />

/12.1<br />

/12.1<br />

/5.1<br />

NB23 NB23<br />

=1-KM1 =1-KM2 =1-KM3 =2-KM1<br />

=2-KM2 =2-KM3<br />

/2.11 2 4 6<br />

/2.10 2 4 6<br />

/2.10 2 4 6<br />

/2.7 2 4 6<br />

/2.6 2 4 6<br />

/2.5<br />

M<br />

3~<br />

M<br />

3~<br />

NB2<br />

13 13 13 13 13 13 13<br />

NB1<br />

NB2<br />

NB20 NB20<br />

=1-UBR =2-UBR<br />

NB5<br />

-AMB<br />

NB6<br />

RS485 RS232<br />

485+<br />

485-<br />

REF<br />

SCR<br />

RTS<br />

CTS<br />

TXD<br />

RXD<br />

GND<br />

+5V<br />

GND<br />

SIG<br />

+5V<br />

SIG<br />

+5V<br />

SIG<br />

+5V<br />

SIG<br />

+5V<br />

GND<br />

SIG<br />

+5V<br />

GND<br />

SIG<br />

+5V<br />

GND<br />

SIG<br />

+5V<br />

GND<br />

SIG<br />

GND<br />

SIG<br />

GND<br />

SIG<br />

24V<br />

-T2<br />

-T1<br />

GND<br />

L 2 GND<br />

=1-CPF<br />

+EXT.ACC<br />

=1-QMMSC1 1 3 5<br />

=1-QMMSC2 1 3 5 =1-QMMSC3 1 3 5<br />

=2-QMMSC1 1 3 5<br />

=2-QMMSC2 1 3 5<br />

=2-QMMSC3<br />

2<br />

1<br />

4<br />

3<br />

L1 L2 L3 PE<br />

L1 L2 L3 PE<br />

L1 L2 L3 PE<br />

L1 L2 L3 PE<br />

L1 L2 L3 PE<br />

-ADIS<br />

6<br />

5<br />

=1-M1<br />

+EXT<br />

2<br />

1<br />

4<br />

3<br />

6<br />

5<br />

=1-M2<br />

+EXT<br />

2<br />

1<br />

-SKP<br />

M<br />

3~<br />

4<br />

3<br />

6<br />

5<br />

=1-M3<br />

+EXT<br />

2<br />

1<br />

M<br />

3~<br />

4<br />

3<br />

20<br />

6<br />

5<br />

=2-M1<br />

+EXT<br />

-SOA -PWM -RU -RP<br />

21<br />

2<br />

1<br />

/2.2<br />

M<br />

3~<br />

4<br />

3<br />

6<br />

5<br />

=2-M2<br />

+EXT<br />

33<br />

34<br />

-SF<br />

/2.1<br />

18 14 51 50 19<br />

33<br />

34<br />

1<br />

2<br />

1<br />

2<br />

L1<br />

M<br />

3~<br />

3<br />

4<br />

3<br />

4<br />

L2<br />

5<br />

6<br />

5<br />

6<br />

L3<br />

PE<br />

=2-M3<br />

+EXT<br />

-BECT<br />

+EXT.ACC<br />

-3<br />

-BLCT<br />

+EXT<br />

-BAMB<br />

+EXT<br />

=1-BSP<br />

+EXT<br />

-1 -2<br />

-4<br />

=1-TC<br />

.2<br />

=1-BDP<br />

+EXT<br />

B A C B A C<br />

-6<br />

=2-BSP<br />

+EXT<br />

=2-TC<br />

.4<br />

=2-BDP<br />

+EXT<br />

B A C B A C<br />

-5 -7<br />

A-<br />

A+<br />

LED PWR<br />

DB7<br />

DB6<br />

DB5<br />

DB4<br />

DB3<br />

DB2<br />

DB1<br />

DB0<br />

E<br />

R/W<br />

RS<br />

GND<br />

+5V<br />

GND<br />

LED GND<br />

GND<br />

COL1<br />

COL2<br />

COL3<br />

COL4<br />

NC<br />

NC<br />

NC<br />

NC<br />

ROW1<br />

ROW2<br />

ROW3<br />

NC<br />

NC<br />

NC<br />

NC<br />

NC<br />

NC<br />

SCR<br />

RED<br />

BLK<br />

1 2 3 4 5 6 7 8 9<br />

10<br />

11<br />

12<br />

13<br />

14<br />

15<br />

16<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18<br />

4 6 7 3 8 5 9 1 2 10<br />

1 4 7<br />

1 5 9 10 2 6 7 11<br />

J1<br />

J2<br />

1 2 3 4 5 6 7 8 9 10<br />

/2.11 /2.11 /2.10 /2.10 /2.9 /3.2 /3.3 /3.4 /2.3 /2.2 /2.2<br />

/5.3 /6.10 /2.1 /2.7 /2.6 /2.6 /2.5<br />

/2.5<br />

/8.10 /3.7 /3.8 /3.9<br />

NB7 NB8<br />

/4.3 /4.3 /4.4 /10.10<br />

/5.2<br />

/12.10<br />

/4.7 /4.8 /4.9<br />

1 2<br />

SCR<br />

RED<br />

BLK<br />

WHT<br />

SCR<br />

RED<br />

BLK<br />

WHT<br />

1 2 3<br />

1 5 9 10 2 6 7 11<br />

1 2 3<br />

2<br />

5<br />

8<br />

1 4<br />

3 6 9<br />

7 1 5 9 10 2 6 7 11<br />

1<br />

BLK<br />

RED<br />

SCR<br />

SCR<br />

RED<br />

BLK<br />

WHT<br />

SCR<br />

RED<br />

BLK<br />

WHT<br />

- +<br />

2 5 8<br />

3<br />

6<br />

11<br />

1 5 9 10 2 6 7 11<br />

6<br />

11<br />

P2<br />

S2<br />

P2<br />

S2<br />

P1<br />

S1<br />

P1<br />

S1<br />

1<br />

1<br />

2 1<br />

2<br />

3<br />

1<br />

2<br />

1 2<br />

1<br />

2<br />

SCR<br />

BLK<br />

RED<br />

BRN<br />

PNK<br />

BRN<br />

PNK<br />

-XTB4<br />

6<br />

9<br />

4 12<br />

4 12<br />

-J14<br />

-K1 -K2 -K3 -K4 -K5<br />

-J13<br />

-K6 -K7 -K8 -K9 -K10 -K11 -K12 -K13 -K14 -K15 -K16 -K17 -K18 -K19 -K20 -K21 -K22 -K23 -K24<br />

-J6<br />

-J7<br />

4 12<br />

-J9<br />

4 12<br />

-TB1 -TB3<br />

1 2 3 4 1 2 3 4 5 6<br />

-J11<br />

L1o L1i<br />

L1i<br />

L1o<br />

L2o L2i<br />

2<br />

1<br />

1 1 1 1 1 1<br />

S2<br />

S1<br />

1<br />

2<br />

S2<br />

S1<br />

1<br />

2<br />

Elementary Wiring<br />

-XTBC<br />

-QSD<br />

L1<br />

L2<br />

-QCB<br />

25<br />

26<br />

27<br />

1L1/1.1<br />

1L2/1.1<br />

1L3/1.1<br />

2L1/1.4<br />

2L2/1.5<br />

2L3/1.5<br />

1L1/1.1<br />

1L2/1.1<br />

1L3/1.1<br />

2L1/1.4<br />

2L2/1.5<br />

2L3/1.5<br />

1L1/1.1<br />

1L2/1.1<br />

1L3/1.1<br />

2L1/1.4<br />

2L2/1.5<br />

2L3/1.5<br />

28<br />

29<br />

30<br />

31<br />

32<br />

-F3<br />

-XTBC2<br />

-F1<br />

-XTBC2<br />

-XP1<br />

-XCTB2<br />

102<br />

101<br />

103<br />

104<br />

105<br />

106<br />

107<br />

108<br />

200<br />

201<br />

202<br />

203<br />

204<br />

205<br />

206<br />

207<br />

208<br />

100<br />

GND<br />

-XTBC2<br />

-FSI<br />

=1-KCR<br />

-XTBC1<br />

=2-KCR<br />

-XTBC1<br />

=1-R =2-R<br />

13<br />

12<br />

51<br />

50<br />

18<br />

14<br />

19<br />

41<br />

21<br />

20<br />

40<br />

BRN-POS<br />

BRN-NEG<br />

53<br />

52<br />

55<br />

54<br />

A-NEG<br />

A-POS<br />

5<br />

LK<br />

GND<br />

GND<br />

GND<br />

GND<br />

GND<br />

GND<br />

L<br />

91<br />

90<br />

1<br />

2<br />

52 jOHNSON CONTROLS


5<br />

6<br />

5<br />

6<br />

5<br />

6<br />

5<br />

6<br />

5<br />

6<br />

5<br />

6<br />

3<br />

4<br />

3<br />

4<br />

3<br />

4<br />

3<br />

4<br />

3<br />

4<br />

3<br />

4<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

2<br />

2<br />

2<br />

1<br />

1<br />

1<br />

2<br />

1<br />

2<br />

1<br />

GND<br />

GND<br />

GND<br />

2<br />

2<br />

2<br />

2<br />

2<br />

2<br />

E<br />

2<br />

2<br />

2<br />

E<br />

E<br />

PE<br />

PE<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

3<br />

3<br />

L1o<br />

L1i<br />

1<br />

1<br />

3<br />

3<br />

FORM 150.62-EG5 (108)<br />

2/1.1<br />

1/1.1<br />

NB2<br />

NB2<br />

21<br />

43<br />

44<br />

43<br />

44<br />

NB19 NB2<br />

NB2<br />

33<br />

34<br />

23<br />

24<br />

.7<br />

/1.10<br />

/1.6<br />

33<br />

34<br />

23<br />

24<br />

.11<br />

/1.10<br />

/1.6<br />

/1.7<br />

/1.7<br />

/1.7<br />

14<br />

/1.9<br />

22<br />

.4<br />

21<br />

/1.6<br />

/1.6<br />

/1.6<br />

14<br />

/1.8<br />

22<br />

.5<br />

21<br />

/1.5<br />

/1.5<br />

/1.5<br />

14<br />

/1.8<br />

22<br />

.5<br />

21<br />

/1.4<br />

/1.4<br />

/1.4<br />

14<br />

/1.9<br />

22<br />

.7<br />

21<br />

/1.3<br />

/1.3<br />

/1.3<br />

14<br />

/1.8<br />

22<br />

.9<br />

21<br />

13<br />

13<br />

13<br />

13<br />

13<br />

13<br />

/1.2<br />

/1.2<br />

/1.2<br />

14<br />

/1.8<br />

22<br />

.9<br />

13<br />

14<br />

13<br />

14<br />

-XTBC2<br />

=2-XTBF =2-XTBF<br />

=2-XTBF<br />

=1-XTBF<br />

=1-XTBF -XTBC2<br />

=1-XTBF<br />

2<br />

2<br />

2 2<br />

2<br />

2<br />

2<br />

2<br />

2<br />

T2<br />

=2-KCR A2<br />

=1-KCR<br />

A2<br />

.1<br />

S2<br />

S1<br />

NB4<br />

T1 T1<br />

T1<br />

T1 T1<br />

1 1<br />

1<br />

S1 S1<br />

=2-YLLSV<br />

S1<br />

S1 S1<br />

=1-YHGSV<br />

=1-YLLSV<br />

A1<br />

A1<br />

+EXT A1<br />

+EXT<br />

A1<br />

A1<br />

+EXT<br />

4<br />

4<br />

4<br />

.1 S2 .1 S2<br />

.2 S2 =1-ECH3<br />

.2 S2 .2 S2 =1-ECH2 =1-ECH1<br />

=2-ECH2 =2-ECH1 =2-KM3 A2 =2-KM2 A2<br />

=2-KM1 A2<br />

+EXT<br />

A2<br />

A2<br />

+EXT<br />

T2 T2 +EXT +EXT<br />

+EXT<br />

=1-KM3<br />

=1-KM2<br />

T2<br />

T2 T2<br />

=1-KM1<br />

A2<br />

GND<br />

-EPH<br />

+EXT<br />

GND<br />

-EEH<br />

+EXT<br />

A1<br />

A1<br />

A1<br />

-XTBC2<br />

140<br />

=2-BMP3<br />

+EXT<br />

T1<br />

M2 .3 M2 .7<br />

=2-XTBF =1-XTBF<br />

235 135<br />

NB11<br />

=2-XTBF<br />

226<br />

=2-XTBF =2-XTBF<br />

=2-XTBF<br />

NB11 NB11 225 224<br />

220<br />

NB11<br />

NB11 NB11<br />

126 125 124 123<br />

=1-XTBF<br />

120<br />

> ><br />

NB2<br />

M1<br />

M1<br />

=2-XTBF<br />

234<br />

=1-XTBF<br />

134<br />

.4 M2 .8<br />

=2-KM3<br />

.5<br />

22<br />

=2-KM2<br />

.6<br />

22<br />

=2-KM1<br />

.7<br />

22<br />

=1-KM3<br />

.10<br />

22<br />

=1-KM2 =1-KM1<br />

.10<br />

22<br />

.11<br />

22<br />

M2<br />

> ><br />

21<br />

21<br />

21<br />

21<br />

21<br />

21<br />

M1<br />

NB11<br />

M1<br />

=2-XTBF<br />

233<br />

=1-XTBF<br />

133<br />

1<br />

1<br />

=1-XTBF<br />

1<br />

1<br />

M2<br />

><br />

=2-BMP1<br />

+EXT<br />

.4<br />

><br />

M1<br />

M1<br />

=1-BMP1<br />

+EXT<br />

M2 .8<br />

=2-XTBF<br />

232<br />

235 234 233 232<br />

=2-BMP3<br />

+EXT<br />

=2-BMP2<br />

+EXT<br />

=1-BMP2<br />

+EXT<br />

=1-XTBF<br />

132<br />

135 134<br />

133 132<br />

=2-BMP2<br />

+EXT<br />

=2-BMP1<br />

+EXT<br />

=1-BMP3<br />

+EXT<br />

=1-BMP2<br />

+EXT<br />

=1-BMP1<br />

+EXT<br />

=1-XTBF =1-XTBF =1-XTBF -XTBC2<br />

=1-BMP3<br />

+EXT<br />

226<br />

225 225<br />

224<br />

126<br />

125<br />

124<br />

=2-XTBF<br />

=2-XTBF<br />

=1-XTBF<br />

NB3<br />

NB3<br />

1<br />

1<br />

P><br />

=2-FHP2<br />

+EXT<br />

P><br />

=1-FHP2<br />

+EXT<br />

=2-XTBF<br />

239<br />

3<br />

=1-XTBF<br />

139<br />

3<br />

15A<br />

239<br />

1<br />

139<br />

1<br />

-F2<br />

P><br />

=2-FHP1<br />

+EXT<br />

P><br />

=1-FHP1<br />

+EXT<br />

=2-KCR<br />

.1<br />

14<br />

=1-KCR<br />

.2<br />

14<br />

13<br />

13<br />

3<br />

NB1<br />

3<br />

=2-XTBF<br />

231<br />

=1-XTBF<br />

131<br />

140 136<br />

222<br />

221<br />

220<br />

219<br />

123<br />

122<br />

121<br />

120<br />

119<br />

-XTBC2<br />

24<br />

-XTBC2<br />

23<br />

218<br />

118<br />

1<br />

231<br />

24<br />

23<br />

131<br />

-XTB9 -XTB8 -XTB10<br />

2 1 7 6 3 2 1 7 6 5 4 3 2 1 7 6 5 4 3 2 1<br />

-XTB7<br />

V /5.3<br />

X /3.5<br />

Y /3.9 /4.9<br />

/6.9<br />

/4.5<br />

/10.9<br />

-K15 -K13 -K10<br />

-K9<br />

-K21<br />

-K20<br />

-K19<br />

-K18 -K17<br />

-K5<br />

-K4<br />

/1.7 /1.6 /1.5<br />

/1.4<br />

/1.9<br />

/1.8<br />

/1.8<br />

/1.8 /1.7<br />

/1.3<br />

/1.3<br />

-K3<br />

/1.2<br />

-K2<br />

/1.2<br />

-K1<br />

/1.1<br />

-AMB<br />

jOHNSON CONTROLS<br />

53


54 jOHNSON CONTROLS<br />

=1-MF1<br />

=1-MF2<br />

=1-MF1<br />

=1-MF2<br />

=1-MF1<br />

=1-MF1<br />

=1-MF2<br />

=1-MF3<br />

=1-MF4<br />

=1-MF1<br />

=1-MF2<br />

=1-MF3<br />

=1-MF4<br />

=2-MF1 =2-MF2<br />

=2-MF3 =2-MF4 =2-MF5<br />

=2-MF1<br />

=2-MF1<br />

=2-MF2<br />

=2-MF1 =2-MF2<br />

=2-MF3 =2-MF4<br />

=2-MF1 =2-MF2<br />

=2-MF3 =2-MF4<br />

=1-MF5<br />

=2-MF3 =2-MF2<br />

=1-MF3<br />

=1-MF2<br />

=1-MF1<br />

=1-MF2<br />

=1-MF3<br />

=1-MF4<br />

=1MF5<br />

=1-MF1<br />

=1-MF2<br />

=2-MF1<br />

=2-MF2<br />

=2-MF3<br />

=2-MF1<br />

=1-MF1<br />

=1-MF2<br />

=2-MF1 =2-MF2<br />

=2-MF3 =2-MF4<br />

=1-MF4<br />

=1-MF5<br />

=2-MF3 =2-MF2<br />

=1-MF3<br />

=1-MF6<br />

<strong>YLAA</strong>0100SE <strong>YLAA</strong>0101HE<br />

<strong>YLAA</strong>0091HE<br />

<strong>YLAA</strong>0115SE<br />

<strong>YLAA</strong>0120SE<br />

<strong>YLAA</strong>0125HE<br />

<strong>YLAA</strong>0135SE<br />

<strong>YLAA</strong>0150SE<br />

<strong>YLAA</strong>0155SE<br />

<strong>YLAA</strong>0141HE<br />

<strong>YLAA</strong>0175HE <strong>YLAA</strong>0156HE<br />

<strong>YLAA</strong>0070SE<br />

<strong>YLAA</strong>0071HE<br />

<strong>YLAA</strong>0080SE<br />

<strong>YLAA</strong>0090SE<br />

NB12<br />

NB21<br />

NB22<br />

NB22<br />

NB12<br />

NB13<br />

NB14<br />

NB15<br />

NB15<br />

NB12<br />

NB14<br />

NB15<br />

NB25<br />

NB26<br />

NB21<br />

NB14<br />

NB27<br />

NB27<br />

GND<br />

150<br />

151<br />

152<br />

T3<br />

T1<br />

T2<br />

GND<br />

153<br />

154<br />

155<br />

T3<br />

T1<br />

T2<br />

GND<br />

T3<br />

T1<br />

T2<br />

156<br />

157<br />

158<br />

GND<br />

250<br />

251<br />

252<br />

T3<br />

T1<br />

T2<br />

GND<br />

253<br />

254<br />

255<br />

T3<br />

T1<br />

T2<br />

GND<br />

T3<br />

T1<br />

T2<br />

256<br />

257<br />

258<br />

GND<br />

150<br />

151<br />

152<br />

T3<br />

T1<br />

T2<br />

GND<br />

T3<br />

T1<br />

T2<br />

153<br />

154<br />

155<br />

GND<br />

153A<br />

154A<br />

155A<br />

T3<br />

T1<br />

T2<br />

GND<br />

T3<br />

T1<br />

T2<br />

156<br />

157<br />

158<br />

GND<br />

T3<br />

T1<br />

T2<br />

156A<br />

156B<br />

157A<br />

157B<br />

158A<br />

158B<br />

GND<br />

250<br />

251<br />

252<br />

T3<br />

T1<br />

T2<br />

GND<br />

T3<br />

T1<br />

T2<br />

253<br />

254<br />

255<br />

GND<br />

253A<br />

254A<br />

255A<br />

T3<br />

T1<br />

T2<br />

GND<br />

T3<br />

T1<br />

T2<br />

256<br />

257<br />

258<br />

GND<br />

T3<br />

T1<br />

T2<br />

256A<br />

257A<br />

258A<br />

GND<br />

156B<br />

157B<br />

158B<br />

T3<br />

T1<br />

T2<br />

503A<br />

505A<br />

502<br />

501<br />

500<br />

GND<br />

504A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

505A<br />

504A 500<br />

501<br />

502<br />

503A<br />

509A<br />

511A<br />

508<br />

507<br />

506<br />

GND<br />

510A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

511A<br />

510A 506<br />

507<br />

508<br />

509A<br />

515A<br />

517A<br />

514<br />

513<br />

512<br />

GND<br />

516A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

517A<br />

516A 512<br />

513<br />

514<br />

515A<br />

521A<br />

523A<br />

520<br />

519<br />

518<br />

GND<br />

522A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

523A<br />

522A 518<br />

519<br />

520<br />

521A<br />

527A<br />

529A<br />

526<br />

525<br />

524<br />

GND<br />

528A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

529A<br />

528A 524<br />

525<br />

526<br />

527A<br />

563A<br />

565A<br />

562<br />

561<br />

560<br />

GND<br />

564A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

565A<br />

564A 560<br />

561<br />

562<br />

563A<br />

533A<br />

535A<br />

532<br />

531<br />

530<br />

GND<br />

534A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

535A<br />

534A 530<br />

531<br />

532<br />

533A<br />

539A<br />

541A<br />

538<br />

537<br />

536<br />

GND<br />

540A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

541A<br />

540A 536<br />

537<br />

538<br />

539A<br />

545A<br />

547A<br />

544<br />

543<br />

542<br />

GND<br />

546A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

547A<br />

546A 542<br />

543<br />

544<br />

545A<br />

551A<br />

553A<br />

550<br />

549<br />

548<br />

GND<br />

552A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

553A<br />

552A 548<br />

549<br />

550<br />

551A<br />

557A<br />

559A<br />

556<br />

555<br />

554<br />

GND<br />

558A<br />

1<br />

5<br />

2<br />

6<br />

4<br />

3<br />

GND<br />

559A<br />

558A 554<br />

555<br />

556<br />

557A<br />

GND<br />

156A<br />

157A<br />

158A<br />

T3<br />

T1<br />

T2<br />

GND<br />

256A<br />

257A<br />

258A<br />

T3<br />

T1<br />

T2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

PE<br />

U1<br />

V1<br />

W1<br />

W2<br />

U2<br />

V2<br />

=1-MF1<br />

+EXT<br />

=1-MF2<br />

+EXT<br />

=1-MF3<br />

+EXT<br />

=2-MF1<br />

+EXT<br />

=2-MF2<br />

+EXT<br />

=2-MF3<br />

+EXT<br />

=1-MF1<br />

+EXT<br />

=1-MF2<br />

+EXT<br />

=1-MF3<br />

+EXT<br />

=1-MF4<br />

+EXT<br />

=1-MF5<br />

+EXT<br />

=2-MF1<br />

+EXT<br />

=2-MF2<br />

+EXT<br />

=2-MF3<br />

+EXT<br />

=2-MF4<br />

+EXT<br />

=2-MF5<br />

+EXT<br />

=1-MF6<br />

+EXT<br />

=1-MF1<br />

+EXT<br />

=1-MF1<br />

+EXT<br />

=1-MF2<br />

+EXT<br />

=1-MF2<br />

+EXT<br />

=1-MF3<br />

+EXT<br />

=1-MF3<br />

+EXT<br />

=1-MF4<br />

+EXT<br />

=1-MF4<br />

+EXT<br />

=1-MF5<br />

+EXT<br />

=1-MF5<br />

+EXT<br />

=1-MF6<br />

+EXT<br />

=1-MF6<br />

+EXT<br />

=2-MF1<br />

+EXT<br />

=2-MF1<br />

+EXT<br />

=2-MF2<br />

+EXT<br />

=2-MF2<br />

+EXT<br />

=2-MF3<br />

+EXT<br />

=2-MF3<br />

+EXT<br />

=2-MF4<br />

+EXT<br />

=2-MF4<br />

+EXT<br />

=2-MF5<br />

+EXT<br />

=2-MF5<br />

+EXT<br />

=1-MF4<br />

+EXT<br />

=2-MF4<br />

+EXT<br />

Condenser Fan Mapping and Sequencing


FORM 150.62-EG5 (108)<br />

55<br />

jOHNSON CONTROLS<br />

-BECT<br />

-BLCT<br />

=1-YLLSV<br />

=1-BSP<br />

=2-BSP<br />

=1-ZCPR1<br />

=1-ZCPR2<br />

=1-ZCPR3<br />

=2-ZCPR1<br />

=2-ZCPR3<br />

=2-YLLSV<br />

=2-FHP1<br />

=2-FHP2<br />

=1-FHP1<br />

=1-FHP2<br />

=2-ZCPR2<br />

=2-BDP<br />

=2-BHP<br />

NB2 NB2<br />

NB11 NB11<br />

NB11<br />

NB11<br />

NB11<br />

NB11<br />

NB3<br />

NB3<br />

NB19<br />

139<br />

131A<br />

132<br />

139A<br />

239A<br />

231A<br />

232<br />

239A<br />

GND<br />

208<br />

207<br />

206<br />

220<br />

GND<br />

E<br />

2AH<br />

2AG<br />

120<br />

GND<br />

E<br />

GND<br />

205<br />

204<br />

203<br />

GND<br />

105<br />

104<br />

103<br />

GND<br />

202<br />

201<br />

200<br />

GND<br />

108<br />

107<br />

106<br />

124A<br />

2AJ<br />

2<br />

125A<br />

2<br />

2AK<br />

126A<br />

2<br />

2AN<br />

224A<br />

2AL<br />

2<br />

225A<br />

2<br />

2AM<br />

226A<br />

2AP<br />

2<br />

GND<br />

102<br />

101<br />

100<br />

133<br />

1AA<br />

2<br />

132A<br />

S2<br />

S1<br />

134<br />

1AB<br />

2<br />

133A<br />

S2<br />

S1<br />

135A<br />

1AE<br />

134A<br />

S2<br />

S1<br />

2<br />

233<br />

1AL<br />

2<br />

232A<br />

S2<br />

S1<br />

234<br />

1AM<br />

2<br />

233A<br />

S2<br />

S1<br />

235A<br />

1AF<br />

2<br />

234A<br />

S2<br />

S1<br />

GND 301<br />

302<br />

300 GND 304<br />

305<br />

303<br />

140A<br />

GND<br />

2AQ<br />

140B<br />

GND<br />

2AR<br />

2<br />

3<br />

1<br />

2<br />

3<br />

1<br />

2<br />

3<br />

1<br />

2<br />

3<br />

1<br />

PE<br />

L3<br />

L2<br />

L1<br />

4<br />

2<br />

3<br />

1<br />

4<br />

2<br />

3<br />

1<br />

PE<br />

L3<br />

L2<br />

L1<br />

PE<br />

L3<br />

L2<br />

L1<br />

PE<br />

L3<br />

L2<br />

L1<br />

PE<br />

L3<br />

L2<br />

L1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

1<br />

PE<br />

L3<br />

L2<br />

L1<br />

M1<br />

M2<br />

T1<br />

T2<br />

M1<br />

M2<br />

T1<br />

T2<br />

M1<br />

M2<br />

T1<br />

T2<br />

M1<br />

M2<br />

T1<br />

T2<br />

M1<br />

M2<br />

T1<br />

T2<br />

M1<br />

M2<br />

T1<br />

T2<br />

E<br />

W1<br />

V1<br />

U1<br />

V2<br />

U2<br />

W2<br />

E<br />

W1<br />

V1<br />

U1<br />

V2<br />

U2<br />

W2<br />

PE<br />

2<br />

1<br />

PE<br />

2<br />

1<br />

=1-FHP1<br />

+EXT<br />

=1-FHP2<br />

+EXT<br />

=2-FHP1<br />

+EXT<br />

=2-FHP2<br />

+EXT<br />

=2-M3<br />

+EXT<br />

=2-YLLSV<br />

+EXT<br />

=1-YLLSV<br />

+EXT<br />

=2-M2<br />

+EXT<br />

=1-M2<br />

+EXT<br />

=2-M1<br />

+EXT<br />

=1-M3<br />

+EXT<br />

=1-ECH1<br />

+EXT<br />

=1-ECH2<br />

+EXT<br />

=1-ECH3<br />

+EXT<br />

=2-ECH1<br />

+EXT<br />

=2-ECH2<br />

+EXT<br />

=2-ECH3<br />

+EXT<br />

=1-M1<br />

+EXT<br />

=1-BMP1<br />

+EXT<br />

=1-BMP2<br />

+EXT<br />

=1-BMP3<br />

+EXT<br />

=2-BMP1<br />

+EXT<br />

=2-BMP2<br />

+EXT<br />

=2-BMP3<br />

+EXT<br />

-MP1<br />

+PUMP<br />

-MP2<br />

+PUMP<br />

-EEH<br />

+EXT<br />

-EPH<br />

+EXT<br />

Compressor Wiring


NB2<br />

2L1 2L2 2L3<br />

2L3<br />

2L1 2L2 2L1 2L2 2L3<br />

1L1 1L2 1L3<br />

1L1 1L2 1L3<br />

1L1 1L2 1L3<br />

PE<br />

2L1 2L2 2L3<br />

2L1 2L2 2L3<br />

NB2 2L1 2L2 2L3<br />

L1 L2<br />

1L1 1L2 1L3<br />

1L1 1L2 1L3<br />

1L1<br />

1L2 1L3<br />

NB16 NB17<br />

L1 L2 L3<br />

L1 L2 L3<br />

L1 L2 L3<br />

=1-QCB =2-QCB<br />

-QSD /CB<br />

-QSD<br />

1L1 1L2 1L3<br />

1L3<br />

1L1 1L2 1L3<br />

NB2 NB2<br />

2L1 2L2 2L3<br />

2L1 2L2 2L3<br />

2L1 2L2 2L3<br />

PE PE<br />

NB19<br />

J11/QPA1:RED<br />

24<br />

1L1 1L2 1L3<br />

1L1 1L2 1L3<br />

1L1 1L2 1L3<br />

TEST<br />

TEST<br />

-QMMSP1<br />

-QMMSP2<br />

33<br />

300 301 302<br />

303 304 305<br />

=O+PUMP<br />

2<br />

2<br />

1L1<br />

1L2<br />

1L3<br />

2<br />

-QMMSP1<br />

-QMMSP2<br />

-XTBC<br />

43<br />

33<br />

34<br />

J11/QPA1:BLK<br />

44<br />

GND<br />

3 5<br />

J11/QPA2:RED 43<br />

33<br />

34<br />

J11/QPA2:BLK<br />

44<br />

A1<br />

A2<br />

A1<br />

A2<br />

21<br />

21<br />

-KP1 -KP2<br />

22<br />

22<br />

GND GND<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

1<br />

2<br />

3<br />

4<br />

L3<br />

5<br />

6<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

1<br />

=0-GND15 +INT<br />

1<br />

2<br />

1<br />

2<br />

3<br />

4<br />

4<br />

5<br />

6<br />

5<br />

6<br />

1<br />

2<br />

1<br />

2<br />

=0-GND1 =0-GND2<br />

1 1<br />

3<br />

4<br />

3<br />

4<br />

5<br />

6<br />

6<br />

Power Options Connection Diagram<br />

56 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

135<br />

118 29 13<br />

127A<br />

1L1 1L2 1L3<br />

1L1 1L2 1L3<br />

A1<br />

A2<br />

128A<br />

A1<br />

A2<br />

129<br />

NB12<br />

2<br />

A1<br />

A2<br />

NB18 227<br />

228<br />

229 NB12 2<br />

1L1 1L2<br />

A1<br />

A2 A1<br />

A2 A1<br />

A2<br />

235<br />

2L1 2L2 2L3<br />

2L1 2L2 2L3<br />

218 31 13<br />

A1<br />

13<br />

23<br />

33<br />

A2<br />

43<br />

350<br />

350<br />

351<br />

351<br />

352<br />

352<br />

350<br />

350<br />

351<br />

351<br />

352<br />

352<br />

350<br />

351<br />

352<br />

3 1 3 1 3 1<br />

3 1<br />

=1-F4 -F3<br />

=2-F4<br />

450<br />

450<br />

451<br />

451<br />

452<br />

452<br />

450<br />

450<br />

451<br />

451<br />

452<br />

452<br />

450<br />

451<br />

452<br />

A1<br />

13<br />

23<br />

33<br />

A2<br />

43<br />

=1-KCR<br />

13<br />

21<br />

13<br />

21<br />

13<br />

21<br />

=1-KF2 =2-KF2<br />

=1-KF1 =1-KF3 =2-KF1 =2-KF3<br />

13<br />

21<br />

13<br />

21<br />

13<br />

21<br />

=2-KCR<br />

14 22<br />

14 22<br />

14 22<br />

14 22<br />

14 22<br />

14 22<br />

14 24 34 44<br />

14 24 34 44<br />

30 18<br />

90 91<br />

350 351 352<br />

150 151 152 153 154 155 156 157 158<br />

250 251 252 253 254 255 256 257 258 450 451 452<br />

32 19<br />

153A 154A 155A 156A 157A 158A<br />

253A 254A 255A 256A 257A 258A<br />

GND GND GND GND GND GND<br />

GND GND GND GND GND<br />

NB14<br />

NB27 NB14<br />

NB27<br />

156B 157B 158B<br />

NB15<br />

NB2<br />

NB18<br />

NB2<br />

NB24<br />

-XTBF1<br />

135A<br />

135<br />

135<br />

134<br />

134<br />

134A<br />

133<br />

133<br />

133A<br />

139<br />

139<br />

139A<br />

132<br />

132<br />

132A<br />

131A<br />

131<br />

131<br />

126A<br />

126<br />

126<br />

125A<br />

125<br />

125<br />

124A<br />

124<br />

124<br />

120<br />

120<br />

120<br />

1AA<br />

1AB<br />

1AE 1<br />

2AK<br />

2AJ<br />

2AN<br />

2 2<br />

2 2<br />

2AG 2<br />

NB23<br />

1L1<br />

TEST<br />

119<br />

A1<br />

1L2<br />

1L3<br />

1L1<br />

TEST<br />

121<br />

1L2<br />

1L3<br />

1L1<br />

1L1<br />

TEST<br />

122<br />

1L2<br />

1L2<br />

1L3<br />

3 3 5<br />

1 3 5<br />

1 3 5<br />

1 3 5<br />

5<br />

=1-QMMSC1 =1-QMMSC2 =1-QMMSC3 =2-QMMSC1 =2-QMMSC2 =2-QMMSC3<br />

A2<br />

21<br />

A1<br />

A2<br />

21<br />

A1<br />

A2<br />

21<br />

NB23<br />

2L1<br />

TEST<br />

219<br />

A1<br />

2L2<br />

2L3<br />

A2<br />

21<br />

2L1<br />

TEST<br />

221<br />

A1<br />

2L2<br />

2L3<br />

A2<br />

21<br />

2L1<br />

TEST<br />

222<br />

A1<br />

2L2<br />

2L3<br />

A2<br />

21<br />

-XTBF2<br />

235<br />

235<br />

235A<br />

234<br />

234<br />

234A<br />

233<br />

233<br />

233A<br />

239<br />

239<br />

239A<br />

232<br />

232<br />

232A<br />

231<br />

231<br />

231A<br />

226<br />

226<br />

226A<br />

225<br />

225<br />

225A<br />

224<br />

224<br />

224A<br />

220<br />

220<br />

220<br />

1AL<br />

1AM<br />

1 1AF<br />

2AM<br />

2AL<br />

2AP<br />

2 2AH<br />

13 25<br />

13 25<br />

13 25<br />

13 27<br />

13 27<br />

13 27<br />

25<br />

25<br />

27<br />

27<br />

=1-KM1 =1-KM2 =1-KM3 =2-KM1 =2-KM2 =2-KM3<br />

14 26<br />

22 124<br />

14 26<br />

26<br />

22 125<br />

14 26<br />

26<br />

22 126<br />

14 28<br />

22 224<br />

14 28<br />

28<br />

22 225<br />

14 28<br />

28<br />

22 226<br />

GND GND GND GND GND GND<br />

100 101 102<br />

103 104 105<br />

106 107 108<br />

200 201 202<br />

203 204 205<br />

206 207 208<br />

GND GND GND<br />

GND<br />

1<br />

1<br />

1<br />

1<br />

2<br />

1<br />

1<br />

1<br />

2<br />

2<br />

2<br />

2<br />

2<br />

=1-GND1 +5_FANS =1-GND2 +5_FANS =1-GND3 +5_FANS =1-GND4 +5_FANS =1-GND5 +5_FANS<br />

1 1 1 1 1<br />

135E<br />

134E<br />

133E<br />

139E<br />

132E<br />

131E<br />

126E<br />

125E<br />

124E<br />

120E<br />

1E<br />

1E<br />

2E<br />

2E<br />

2E<br />

135I<br />

134I<br />

133I<br />

139I<br />

132I<br />

131I<br />

126I<br />

125I<br />

124I<br />

120I<br />

1I<br />

1I<br />

2I<br />

2I<br />

2I<br />

L1o<br />

L1i<br />

1<br />

=1-GND6 +5_FANS<br />

L2i<br />

L2o<br />

1<br />

2<br />

1L1<br />

1<br />

2<br />

3<br />

4<br />

L3i<br />

L3o<br />

1L2<br />

4<br />

5<br />

6<br />

1L3<br />

5<br />

6<br />

1<br />

2<br />

2<br />

2<br />

1<br />

1<br />

4<br />

1<br />

2<br />

1L1<br />

1<br />

2<br />

2<br />

2<br />

5<br />

6<br />

3<br />

4<br />

1<br />

2<br />

1L2<br />

4<br />

5<br />

6<br />

4<br />

1L3<br />

6<br />

2<br />

2<br />

5<br />

6<br />

2<br />

2<br />

1<br />

1<br />

2<br />

1<br />

2<br />

2<br />

4<br />

3<br />

4<br />

4<br />

2<br />

5<br />

6<br />

5<br />

6<br />

1L3<br />

6<br />

2<br />

2<br />

1<br />

1<br />

1L1<br />

L1i<br />

L1o<br />

1L2<br />

L2i<br />

L2o<br />

-GND8 -GND9 -GND10 -GND11 -GND12 -GND13<br />

1 1 1 1 1 1<br />

2<br />

1<br />

2<br />

2L1<br />

2<br />

4<br />

3<br />

4<br />

2L2<br />

4<br />

2<br />

2<br />

5<br />

6<br />

5<br />

6<br />

2L3<br />

6<br />

2<br />

2<br />

2<br />

1<br />

1<br />

3<br />

4<br />

2<br />

2<br />

5<br />

6<br />

1<br />

2<br />

2L1<br />

2<br />

3<br />

4<br />

2<br />

2L2<br />

4<br />

5<br />

6<br />

3<br />

4<br />

2L3<br />

6<br />

2<br />

5<br />

6<br />

2<br />

2<br />

1<br />

1<br />

L1o<br />

L1i<br />

1<br />

2<br />

2L1<br />

1<br />

2<br />

L2i<br />

L2o<br />

3<br />

4<br />

2L2<br />

3<br />

4<br />

5<br />

6<br />

L3i<br />

L3o<br />

2L3<br />

6<br />

2<br />

2<br />

1<br />

1<br />

1<br />

1<br />

=2-GND6 +5_FANS =2-GND7 +5_FANS =2-GND8 +5_FANS =2-GND9 +5_FANS =2-GND10 +5_FANS<br />

1 1 1 1 1<br />

-GND2 -GND7 -GND14<br />

-GND3<br />

1 1 1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

2<br />

2<br />

2<br />

2<br />

2<br />

2<br />

235I<br />

234I<br />

233I<br />

239I<br />

232I<br />

231I<br />

226I<br />

225I<br />

224I<br />

220I<br />

1I<br />

1I<br />

2I<br />

2I<br />

2I<br />

2<br />

2<br />

1<br />

2<br />

2<br />

235E<br />

234E<br />

233E<br />

239E<br />

232E<br />

231E<br />

226E<br />

225E<br />

224E<br />

220E<br />

1E<br />

1E<br />

2E<br />

2E<br />

2E<br />

Power Panel<br />

jOHNSON CONTROLS<br />

57


=0+PUMP<br />

=0+INT<br />

-QMMSP1<br />

1 1<br />

-QMMSP2<br />

=0+INT<br />

1<br />

1<br />

Dual Pump Wiring<br />

1L1/1.1<br />

1L2/1.1<br />

1L3/1.1<br />

1L1<br />

1L2<br />

1L3<br />

-AMB<br />

-J11<br />

4 9 14 5 10 15<br />

-QMMSP1<br />

1<br />

3<br />

5<br />

43 31<br />

-QMMSP2<br />

1<br />

3<br />

5<br />

43 31<br />

44 32<br />

44 32<br />

.4<br />

.5<br />

SCR<br />

SCR<br />

2<br />

4<br />

6<br />

2<br />

4<br />

6<br />

RED<br />

BLK<br />

RED<br />

BLK<br />

1<br />

3<br />

5<br />

1<br />

3<br />

5<br />

NB19<br />

-KP1<br />

-KP2<br />

.2 2 4 6<br />

.3<br />

2<br />

4<br />

6<br />

-MP1<br />

300<br />

301<br />

302<br />

GND<br />

U1 W1 V1<br />

M<br />

3~<br />

E<br />

-MP2<br />

303<br />

304<br />

305<br />

U1 W1 V1 E<br />

M<br />

3~<br />

GND<br />

43<br />

-QMMSP1<br />

-QMMSP2<br />

.2<br />

44<br />

.3<br />

43<br />

44<br />

1/1.1<br />

1<br />

-XTBC2<br />

23<br />

-XTB8<br />

6<br />

-AMB<br />

V/2.4<br />

-K13 -K11<br />

/1.6 /1.5<br />

-XTB8<br />

7 4<br />

-XTB8<br />

-XTBC2<br />

24<br />

24<br />

23<br />

33<br />

A1<br />

A1<br />

-KP1 A2<br />

-KP2<br />

A2<br />

2/1.1<br />

2<br />

1<br />

3<br />

5<br />

11<br />

2<br />

4<br />

6<br />

12<br />

.2<br />

.2<br />

.2<br />

1<br />

3<br />

5<br />

11<br />

2<br />

4<br />

6<br />

12<br />

.3<br />

.3<br />

.3<br />

58 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

59<br />

jOHNSON CONTROLS<br />

-AMB<br />

NB12 NB13<br />

NB22<br />

NB26<br />

.10<br />

.10<br />

.10 .10<br />

/1.6<br />

.7<br />

.10<br />

.5<br />

.6<br />

.10<br />

.3<br />

.4<br />

.10<br />

.2<br />

.2<br />

.10<br />

.7<br />

/7.9<br />

/7.7<br />

/7.4<br />

/7.2<br />

.7<br />

.5<br />

.3<br />

.7<br />

.2<br />

.6<br />

.4<br />

.2<br />

.7<br />

/7.10<br />

/7.10<br />

/7.10<br />

.6<br />

/7.8<br />

/7.8<br />

/7.8<br />

.5<br />

/7.8<br />

/7.8<br />

/7.8<br />

.4<br />

/7.6<br />

/7.6<br />

/7.6<br />

.3<br />

/7.5<br />

/7.5<br />

/7.5<br />

.2<br />

/7.3<br />

/7.3<br />

/7.3<br />

.2<br />

/7.3<br />

/7.3<br />

/7.3<br />

.7<br />

/7.11<br />

/7.11<br />

/7.11<br />

72<br />

81 82<br />

71<br />

54<br />

61 62<br />

53<br />

22<br />

21<br />

4<br />

3<br />

6<br />

1 2<br />

5<br />

22<br />

21<br />

2<br />

13<br />

6<br />

5<br />

1<br />

4<br />

3<br />

14<br />

22<br />

21<br />

2<br />

13<br />

6<br />

5<br />

1<br />

4<br />

3<br />

14<br />

22<br />

21<br />

2<br />

13<br />

6<br />

5<br />

1<br />

4<br />

3<br />

14<br />

22<br />

21<br />

2<br />

13<br />

6<br />

5<br />

1<br />

4<br />

3<br />

14<br />

22<br />

21<br />

2<br />

13<br />

6<br />

5<br />

1<br />

4<br />

3<br />

14<br />

22<br />

21<br />

2<br />

13<br />

6<br />

5<br />

1<br />

4<br />

3<br />

14<br />

22<br />

21<br />

2<br />

13<br />

6<br />

5<br />

1<br />

4<br />

3<br />

14<br />

22<br />

21<br />

2<br />

13<br />

6<br />

5<br />

1<br />

4<br />

3<br />

14<br />

5<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

54<br />

53<br />

22<br />

21<br />

82<br />

81<br />

22<br />

21<br />

22<br />

21<br />

72<br />

71<br />

22<br />

21<br />

22<br />

21<br />

62<br />

61<br />

22<br />

21<br />

22<br />

21<br />

22<br />

21<br />

22<br />

21<br />

96<br />

95<br />

96<br />

95<br />

96<br />

95<br />

96<br />

95<br />

A2<br />

A1<br />

A2<br />

A1<br />

A2<br />

A1<br />

A2<br />

A1<br />

A2<br />

A1<br />

A2<br />

A1<br />

A2<br />

A1<br />

A2<br />

A1<br />

A2<br />

A1<br />

-XTB8<br />

V/2.4<br />

1/1.1<br />

2/1.1<br />

=1-KFS1<br />

=1-KFS1<br />

=1-KFS1 =1-KFS1<br />

-K12<br />

=1-KFH4<br />

=1-KFS1<br />

=1-KFL3<br />

=1-KFH3<br />

=1-KFS1<br />

=1-KFL2<br />

=1-KFH2<br />

=1-KFS1<br />

=1-KFL1<br />

=1-KFH1<br />

=1-KFS1<br />

=1-KFL4<br />

=1-KFOL4<br />

=1-KFOL3<br />

=1-KFOL2<br />

=1-KFOL1<br />

=1-KFL4<br />

=1-KFH3<br />

=1-KFL3<br />

=1-KFH2<br />

=1-KFL2<br />

=1-KFH1<br />

=1-KFL1 =1-KFH4 =1-KFS1<br />

57<br />

60 58<br />

65 64<br />

68 67<br />

70 69<br />

74 72<br />

73<br />

81<br />

71<br />

59 56<br />

61<br />

62<br />

63<br />

66<br />

75<br />

2<br />

1<br />

Wiring


60 jOHNSON CONTROLS<br />

NB6<br />

NB6<br />

-XTBC2<br />

-XTBC1<br />

NB19<br />

NB22<br />

NB22<br />

NB19<br />

NB19<br />

40<br />

GND<br />

41<br />

-XTB9<br />

231<br />

1<br />

1<br />

-J7<br />

=1-BDP:SCR<br />

=1-BSP:SCR<br />

1-TC:PNK 52<br />

1-TC:BRN 53<br />

=1-BDP:WHT<br />

=1-BSP:WHT<br />

=1-BSP:BLK<br />

=1-BDP:BLK<br />

=1-BDP:RED<br />

=1-BSP:RED<br />

-J9<br />

=2-BDP:SCR<br />

=2-BSP:SCR<br />

2-TC:PNK 54<br />

2-TC:BRN 55<br />

=2-BDP:WHT<br />

=2-BSP:WHT<br />

=2-BSP:BLK<br />

=2-BDP:BLK<br />

=2-BDP:RED<br />

=2-BSP:RED<br />

-SOA<br />

13<br />

12<br />

?<br />

+BRN-POS<br />

- BRN-NEG<br />

-XP2<br />

BRN-NEG<br />

BRN-POS<br />

-J6<br />

BLCT:RED<br />

BAMB:SCR<br />

BLCT:SCR<br />

BAMB:RED<br />

BAMB:BLK<br />

BECT:SCR<br />

BECT:RED<br />

BECT:BLK<br />

BLCT:BLK<br />

5<br />

1<br />

40 41<br />

1<br />

1<br />

2 2<br />

229<br />

218<br />

228<br />

222<br />

227<br />

219<br />

220<br />

221<br />

218<br />

218<br />

25<br />

25<br />

26<br />

26<br />

27<br />

27<br />

28<br />

28<br />

29<br />

29<br />

30<br />

30<br />

31<br />

31<br />

32<br />

32<br />

5<br />

5<br />

LK<br />

L<br />

L<br />

LK<br />

2<br />

2<br />

2<br />

2<br />

2AS<br />

2<br />

2<br />

2<br />

2<br />

2<br />

2AR<br />

2AQ<br />

123<br />

123<br />

123<br />

140<br />

140<br />

140B<br />

140A<br />

13 13<br />

13<br />

13<br />

51<br />

14<br />

13<br />

13 13<br />

13<br />

13<br />

13<br />

13<br />

13<br />

13<br />

18<br />

18 18<br />

13<br />

13<br />

13<br />

13<br />

13<br />

13<br />

19<br />

19 19<br />

13<br />

13<br />

13<br />

20<br />

20<br />

21<br />

21<br />

50<br />

50<br />

14<br />

51<br />

A+<br />

A-POS<br />

A-<br />

A-NEG<br />

GND<br />

140<br />

136<br />

50 18<br />

12<br />

20 51<br />

19<br />

21<br />

14<br />

13<br />

13<br />

12<br />

-AMB<br />

031-02550-<br />

REF - +<br />

SHLD<br />

J2<br />

2<br />

J12<br />

9<br />

5<br />

11<br />

6<br />

J10<br />

5<br />

9<br />

9<br />

5<br />

7<br />

4<br />

7<br />

4<br />

7<br />

4<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1 1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

TB5<br />

RXD TXD<br />

+5V GND<br />

+5V<br />

SHLD GND + CTS RTS<br />

TB6<br />

1<br />

1<br />

1<br />

1<br />

1<br />

J4<br />

J14<br />

J13 J11<br />

J9<br />

J8<br />

J7<br />

J6<br />

J1<br />

TB4<br />

TB3<br />

TB2<br />

PL1<br />

TB1<br />

J15<br />

TB10<br />

TB9<br />

TB8<br />

TB7<br />

J11/QPA1:BLK<br />

J11/QPA2:SCR<br />

J11/QPA1:SCR<br />

J11/QPA2:RED<br />

J11/QPA2:BLK<br />

J11/QPA1:RED<br />

A-NEG<br />

A-POS<br />

129<br />

118<br />

128A<br />

122<br />

127A<br />

119<br />

123<br />

120<br />

121<br />

118<br />

118<br />

23<br />

130<br />

81<br />

136<br />

24<br />

131<br />

33<br />

1<br />

1<br />

1<br />

1<br />

23<br />

23<br />

1<br />

24<br />

24<br />

24<br />

GND<br />

3<br />

2<br />

1<br />

4<br />

3<br />

2<br />

1<br />

12<br />

11<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

12<br />

11<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

2<br />

1<br />

2<br />

1<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

L1o<br />

L1i<br />

S2<br />

S1<br />

P2<br />

P1<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

25E<br />

25I<br />

26E<br />

26I<br />

27E<br />

27I<br />

28E<br />

28I<br />

29E<br />

29I<br />

30E<br />

30I<br />

31E<br />

31I<br />

32E<br />

32I<br />

5E<br />

5I<br />

LE<br />

LI<br />

2E<br />

2I<br />

2E<br />

2I<br />

2E<br />

2I<br />

123E<br />

123I<br />

140E<br />

140I<br />

13E<br />

13I<br />

14E<br />

14I<br />

13E<br />

13I<br />

13E<br />

13I<br />

13E<br />

13I<br />

18E<br />

18I<br />

13E<br />

13I<br />

13E<br />

13I<br />

19E<br />

19I<br />

13E<br />

13I<br />

20E<br />

20I<br />

21E<br />

21I<br />

50E<br />

50I<br />

51E<br />

51I<br />

A+E<br />

A+I<br />

A-E<br />

A-I<br />

GNDE<br />

GNDI<br />

L1o<br />

L1i<br />

12<br />

11<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

15<br />

10<br />

5<br />

14<br />

13<br />

12<br />

11<br />

9<br />

8<br />

7<br />

6<br />

4<br />

3<br />

2<br />

1<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

23E<br />

23I<br />

24E<br />

24I<br />

1<br />

-J14<br />

-ADIS<br />

-F1<br />

-T1<br />

-XTB10<br />

-F2<br />

-J13<br />

-J11<br />

-XTB7<br />

-XTB8<br />

-GND1<br />

MicroPanel Connections


Notes<br />

FORM 150.62-EG5 (108)<br />

Designation DESCRIPTION<br />

Designation DESCRIPTION<br />

ACC ACCESSORY<br />

-QCB CIRCUIT BREAKER<br />

- ADIS DISPLAY BOARD -QMMSC MANUAL MOTOR STARTER COMPRESSOR<br />

- AMB MICRO BOARD<br />

-QMMSP MANUAL MOTOR STARTER PUMP<br />

-QSD SWITCH DISCONNECT<br />

- BAMB AMBIENT<br />

- BDP DISCHARGE PRESSURE R RESISTOR<br />

- BECT ENTERING CHILLED TEMPERATURE RED RED<br />

- BLCT LEAVING CHILLED TEMPERATURE RP RUN PERMISSIVE<br />

NOT FITTED ON REMOTE EVAP UNITS RU REMOTE UNLOAD Ist STEP<br />

-BMP MOTOR PROTECTOR COMPRESSOR SCR SCREEN<br />

- BSP SUCTION PRESSURE<br />

- SF FLOW SWITCH<br />

- SKP KEYPAD<br />

-CPF CAPACITOR POWER FACTOR - SOA SWITCH OFF AUTO<br />

- ECH<br />

-EEH<br />

-EPH<br />

CRANKCASE HEATER<br />

EVAPORATOR HEATER<br />

PUMP HEATER<br />

- T<br />

-TC<br />

TRANSFORMER<br />

TRANSFORMER CURRENT<br />

-EXT EXTERNAL TO CONTROL PANEL -UBR BRIGDE RECFIFIER<br />

- F<br />

FUSE<br />

- FHP HIGH PRESSURE CUTOUT<br />

WHT<br />

WHITE<br />

-FSI FAN SPEED INHIBIT TWO SPEED - XTBC TERMINAL BLOCK CUSTOMER<br />

FAN OPTION ONLY<br />

- XTBF<br />

TERMINAL BLOCK FACTORY<br />

GND GROUND -YHGSV HOT GAS SOLENOID VALVE<br />

G/Y GREEN / YELLOW (INCLUDING COIL SUPPRESSOR)<br />

- YLLSV LIQUID LINE SOLENOID VALVE<br />

(INCLUDING COIL SUPPRESSOR)<br />

J PLUG BOARD CONNECTOR FIELD MOUNTED AND WIRED ON REMOTE EVAP UNITS<br />

-K CIRCUIT BOARD RELAY - ZCPR COMPRESSOR<br />

-KF FAN CONTACTOR LINE<br />

-KFH FAN CONTACTOR HIGH SPEED<br />

(INCLUDING COIL SUPPRESSOR)<br />

-KFL FAN CONTACTOR LOW SPEED NOTE WELL {SEE NOTE}<br />

NB<br />

(INCLUDING COIL SUPPRESSOR)<br />

-KFOL FAN OVERLOAD<br />

-KFS RELAY FAN SPEED WIRING AND ITEMS SHOWN THUS<br />

-KM COMPRESSOR CONTACTOR<br />

ARE STANDARD YORK ACCESSORIES<br />

-KCR<br />

(INCLUDING COIL SUPPRESSOR)<br />

CONTROL RELAY<br />

WIRING AND ITEMS SHOWN THUS<br />

-KP PUMP CONTACTOR PART<br />

ARE NOT SUPPLIED BY YORK<br />

(INCLUDING COIL SUPPRESSOR)<br />

ITEMS THUS ENCLOSED FORM A<br />

- M COMPRESSOR MOTOR COMPONENTS OR SETS OFCOMPONENTS<br />

-MF MOTOR FAN<br />

-MP MOTOR PUMP<br />

NU NOT USED<br />

PE<br />

PWM<br />

PROTECTIVE EARTH<br />

PULSE WIDTH MODULATION TEMP<br />

RESET or REMOTE UNLOAD 2nd STEP<br />

jOHNSON CONTROLS<br />

61


Notes – continued<br />

GENERAL<br />

a. THIS DRAWING IS BASED ON IEC SYMBOLS.<br />

b. FIELD WIRING TO BE IN ACCORDANCE WITH THE RELEVANT ELECTRICAL CODE AS WELL AS ALL OTHER<br />

APPLICABLE CODES AND SPECIFICATIONS<br />

c. ALL SOURCES OF SUPPLY SHOWN ON THIS DIAGRAM TO BE TAKEN FROM ONE MAIN ISOLATOR, NOT<br />

SHOWN OR SUPPLIED BY YORK.<br />

d. GREEN AND YELLOW WIRE IS USED FOR EARTH, MULTI-COLOURED CABLE USED FOR LOW VOLTAGE.<br />

RED WIRE USED FOR A.C. CONTROL, BLUE WIRE FOR NEUTRAL, BLACK WIRE FOR A.C. AND D.C.<br />

POWER. ORANGE WIRE SHOULD BE USED FOR INTERLOCK CONTROL WIRING SUPPLIED BY EXTERNAL<br />

SOURCE.<br />

e. LEGEND DESIGNATION DEPICTS COMPONENT ABBREVIATIONS. NUMBER PREFIX LOCATED, IF<br />

APPLICABLE, ON SCHEMATIC CIRCUIT, REFERS TO SYSTEM THEREON, E.G.= 1-FHP2 REFERS TO HIGH<br />

PRESSURE CUTOUT NO 2 ON SYSTEM NO 1.<br />

f. ALL WIRING TO CONTROL SECTION VOLTAGE FREE CONTACTS REQUIRES A SUPPLY PROVIDED BY THE<br />

CUSTOMER MAXIMUM VOLTAGE 240 VOLTS. THE CUSTOMER MUST TAKE PARTICULAR CARE WHEN<br />

DERIVING THE SUPPLIES FOR THE VOLTAGE FREE TERMINALS WITH REGARD TO A COMMON POINT OF<br />

ISOLATION. THUS, THESE CIRCUITS WHEN USED MUST BE FED VIA THE COMMON POINT OF ISOLATION<br />

THE VOLTAGE TO THESE CIRCUITS IS REMOVED WHEN THE COMMON POINT OF ISOLATION TO THE UNIT<br />

IS OPENED. THIS COMMON POINT OF ISOLATION IS NOT SUPPLIED BY YORK. THE YORK VOLTAGE<br />

FREE CONTACTS ARE RATED AT 100VA. ALL INDUCTIVE DEVICES {RELAYS} SWITCH BY THE YORK<br />

VOLTAGE FREE CONTACTS MUST HAVE THEIR COIL SUPPRESSED USING STANDARD R/C SUPPRESSORS.<br />

g. CUSTOMER VOLTAGE FREE CONTACTS CONNECTED TO TERMINAL 13 MUST BE RATED AT 30V 5ma<br />

h. NO CONTROLS {RELAYS ETC.} SHOULD BE MOUNTED IN ANY SECTION OF THE CONTROL PANEL.<br />

ADDITIONALLY, CONTROL WIRING NOT CONNECTED TO THE YORK CONTROL PANEL SHOULD NOT BE RUN<br />

THROUGH THE PANEL.<br />

IF THESE PRECAUTIONS ARE NOT FOLLOWED, ELECTRICAL NOISE COULD CAUSE MALFUNCTIONS OR<br />

DAMAGE TO THE UNIT AND ITS CONTROLS.<br />

1<br />

2<br />

3<br />

NOTES<br />

REFER TO INSTALATION COMMISIONING OPERATION AND MAINTENANCE MANUAL FOR CUSTOMER<br />

CONNECTIONS AND CUSTOMER CONNECTION NOTES, NON COMPLIANCE TO THESE INSTRUCTIONS WILL<br />

INVALIDATE UNIT WARRANTY.<br />

WIRING AND COMPONENTS FOR COMPRESSOR 3 ONLY FITTED WHEN UNIT HAS 3 COMPRESSORS ON<br />

THE SYSTEM. 1-BMP3 IS REPLACED BY A LINK ACROSS TERMINALS 134 & 135. 2-BMP3 IS REPLACED BY A<br />

LINK ACROSS TERMINALS 234 & 235.<br />

FHP2 IS ONLY FITTED ON CE <strong>YLAA</strong> ??? AND ABOVE. WHEN NOT FITTED 1-FHP2 IS REPLACED BY A LINK<br />

ACROSS TERMINALS 132 & 139. 2-FHP2 IS REPLACED BY A LINK ACROSS TERMINALS 232 & 239<br />

4 FITTED ON UNITS WITH HOT GAS BYPASS OPTION.<br />

5 EMS OPTION IS WIRED AS SHOWN<br />

6 THIS WIRING MUST BE USED FOR OLD DISPLAY 031-0110-000<br />

7 NETWORK CONNECTION POINT<br />

8 PRINTER PORT<br />

9 REMOTE EMERGENCY STOP CAN BE WIRED BETWEEN TERMINAL L AND 5 AFTER REMOVING LINK<br />

POWER FACTOR CORRECTION ACCESSORY. POWER FACTOR CORRECTION FITTED TO EACH<br />

10<br />

COMPRESSOR CONTACTOR<br />

NOT FITTED ON COMPRESSORS WITH INTERNAL MOTOR PROTECTION. FOR SYTEM 1 TERMINALS 132 &<br />

11 133, 133 & 134 AND 134 & 135 ARE LINKED. FOR SYTEM 2 TERMINALS 232 & 233, 233 & 234 AND 234 & 235<br />

ARE LINKED.<br />

12 ONLY FITTED ON SYSTEMS WITH 3 OR 4 FANS<br />

13 ONLY FITTED ON SYSTEMS WITH 4 FANS<br />

14 ONLY FITTED ON SYSTEMS WITH 5 FANS<br />

15 ONLY FITTED ON SYSTEMS WITH 6 FANS<br />

INPUT SWITCH DISCONNECT( STANDARD ON CE UNITS) OR CIRCUIT BREAKER OPTION REPLACES<br />

16<br />

INPUT TERMINAL BLOCK<br />

17 INPUT SWITCH DISCONNECT & SYSTEM CIRCUIT BREAKER OPTION REPLACES INPUT TERMINAL BLOCK<br />

18<br />

115V CONTROL CIRCIUT REQUIRES A 115V SUPPLY UNLESS CONTROL CIRCUIT TRANSFORMER<br />

-T2 & -F3 ARE FITTED (STANDARD ON CE UNITS)<br />

FOR OPTIONAL HYDRO KIT. HEATER -EPH IS FITTED AND WIRED AS SHOWN.<br />

19 ON SINLGE PUMP -KP1, -QMMSP1 & -MP1 ARE FITTED & WIRED AS SHOWN.<br />

ON TWO PUMP HYDRO KITS -KP2, -QMMSP2 & -MP2 ARE ALSO FITTED AND WIRED AS SHOWN.<br />

20 CURRENT MEASUREMENT OPTION WIRED AS SHOW<br />

21 ONLY FITTED ON SYSTEMS WITH SINGLE SPEED FANS<br />

22 ONLY FITTED ON SYSTEMS WITH TWO SPEED FANS<br />

23 OPTIONAL COMPRESSOR MANUAL MOTORS STARTERS ( STANDARD ON CE UNITS)<br />

24 SEE SHEET 3 OF CONNECTION DIAGRAM FOR POWER INPUT OPTIONS<br />

25 ALTERNATE CONNECTIONS SHOWN FOR DIFFERENT TWO SPEED MOTOR TYPES<br />

26 ONLY FITTED ON SYSTEMS WITH A MAXIMUM OF 4 FANS<br />

62 jOHNSON CONTROLS


Application Data<br />

FORM 150.62-EG5 (108)<br />

Unit Location<br />

The <strong>YLAA</strong> chillers are designed for outdoor installation.<br />

When selecting a site for installation, be guided by the<br />

following conditions:<br />

1. For outdoor locations of the unit, select a place<br />

having an adequate supply of fresh air for the<br />

condenser.<br />

2. Avoid locations beneath windows or between<br />

structures where normal operating sounds may<br />

be objectionable.<br />

3. Installation sites may be either on a roof, or at<br />

ground level. (See FOUNDATION.)<br />

4. The condenser fans are the propeller-type, and<br />

are not recommended for use with duct work in<br />

the condenser air stream.<br />

5. When it is desirable to surround the unit(s), it is<br />

recommended that the screening be able to pass<br />

the required chiller CFM without exceeding 0.1"<br />

of water external static pressure.<br />

6. Protection against corrosive environments is available<br />

by supplying the units with either copper fin,<br />

cured phenolic, or epoxy coating on the condenser<br />

coils. The phenolic or epoxy coils should be offered<br />

with any units being installed at the seashore<br />

or where salt spray may hit the unit.<br />

In installations where winter operation is intended and<br />

snow accumulations are expected, additional height must<br />

be provided to ensure normal condenser air flow.<br />

Recommended clearances for units are given in Dimensions.<br />

When the available space is less, the unit(s) must<br />

be equipped with the discharge pressure transducer option<br />

to permit high pressure unloading in the event that<br />

air recirculation were to occur.<br />

Foundation<br />

The unit should be mounted on a flat and level foundation,<br />

ground or roof, capable of supporting the entire operating<br />

weight of the equipment. Operating weights are given in<br />

the PHYSICAL DATA tables.<br />

ROOF LOCATIONS – Choose a spot with adequate structural<br />

strength to safely support the entire weight of the unit<br />

and service personnel. Care must be taken not to damage<br />

jOHNSON CONTROLS<br />

the roof during installation. If the roof is “bonded”, consult<br />

the building contractor or architect for special installation<br />

requirements. Roof installations should incorporate the<br />

use of spring-type isolators to minimize the transmission<br />

of vibration into the building structure.<br />

GROUND LEVEL INSTALLATIONS – It is important that<br />

the units be installed on a substantial base that will not<br />

settle, causing strain on the liquid lines and resulting in<br />

possible leaks. A one-piece concrete slab with footers<br />

extending below the frost line is highly recommended. Additionally,<br />

the slab should not be tied to the main building<br />

foundation as noises will telegraph.<br />

Mounting holes (5/8" diameter) are provided in the steel<br />

channel for bolting the unit to its foundation. See DIMEN-<br />

SIONS.<br />

For ground level installations, precautions should be taken<br />

to protect the unit from tampering by or injury to unauthorized<br />

persons. Screws on access panels will prevent<br />

casual tampering; however, further safety precautions,<br />

such as unit enclosure options, a fenced-in enclosure, or<br />

locking devices on the panels may be advisable. Check<br />

local authorities for safety regulations.<br />

Chilled Liquid Piping<br />

The chilled liquid piping system should be laid out so<br />

that the circulating pump discharges into the cooler. The<br />

inlet and outlet cooler liquid connections are given in<br />

DIMENSIONS.<br />

Hand stop valves are recommended for use in all lines to<br />

facilitate servicing. Drain connections should be provided<br />

at all low points to permit complete drainage of the cooler<br />

and system piping. Additionally, a strainer (40 mesh) is<br />

recommended for use on the INLET line to the cooler.<br />

Pressure gauge connections are recommended for installation<br />

in the inlet and outlet water lines. Gauges are not<br />

furnished with the unit and are to be furnished by other<br />

suppliers.<br />

The chilled liquid lines that are exposed to outdoor ambients<br />

should be wrapped with a supplemental heater cable<br />

and covered with insulation. As an alternative, ethylene<br />

glycol should be added to protect against freeze-up during<br />

low ambient periods.<br />

A flow switch is available as an accessory on all units.<br />

The flow switch (or its equivalent) must be installed in the<br />

leaving water piping of the cooler and must not be used<br />

to start and stop the unit.<br />

63


Guide Specifications<br />

PART 1 – GENERAL .<br />

1.01 SCOPE<br />

A. The requirements of the General Conditions, Supplementary<br />

Conditions, Division 1, and Drawings apply<br />

to all Work herein.<br />

B. Provide Microprocessor controlled, multiple-scroll<br />

compressor, air-cooled, liquid chillers of the scheduled<br />

capacities as shown and indicated on the Drawings,<br />

including but not limited to:<br />

1. Chiller package with ZERO Ozone Depletion Potential<br />

Refrigerant R-410A<br />

2. Electrical power and control connections<br />

3. Chilled water connections<br />

4. Factory Start-Up<br />

5. Charge of refrigerant and oil (Except for Remote<br />

Evaporator applications).<br />

1.02 QUALITY ASSURANCE<br />

A. Products shall be Designed, Tested, Rated and Certified<br />

in accordance with, and installed in compliance<br />

with applicable sections of the following Standards<br />

and Codes:<br />

1. ANSI/ASHRAE Standard 15 – Safety Code for<br />

Mechanical Refrigeration<br />

2. ASHRAE 90.1– Energy Efficiency compliance.<br />

3. ANSI/NFPA Standard 70 – National Electrical<br />

Code (N.E.C.).<br />

4. ASME Boiler & Pressure Vessel Code, Section<br />

VIII, Division 1.<br />

5. ARI Standard 550/590 – Positive Displacement<br />

Compressors and Air Cooled Rotary Screw Water-<br />

Chilling Packages.<br />

6. Conform to Intertek Testing Services, formerly<br />

ETL, for construction of chillers and provide ETL/<br />

cETL Listing label.<br />

7. Manufactured in facility registered to ISO 9002.<br />

8. OSHA – Occupational Safety and Health Act<br />

B. Factory Test: Chiller shall be pressure-tested, evacuated<br />

and fully charged with refrigerant and oil, and shall<br />

be factory operational run tested with water flowing<br />

through the vessel.<br />

C. Chiller manufacturer shall have a factory trained and<br />

supported service organization that is within a 50 mile<br />

radius of the site.<br />

workmanship and material for a period of one year<br />

from date of initial start-up or eighteen (18) months<br />

from date of shipment, whichever occurs first.<br />

1.03 DELIVERY AND HANDLING<br />

A. Unit shall be delivered to job site fully assembled and<br />

charged with refrigerant and oil by the Manufacturer.<br />

B. Unit shall be stored and handled per Manufacturer’s<br />

instructions.<br />

C. Protect the chiller and its accessories from the weather<br />

and dirt exposure during shipment.<br />

D. During shipment, provide protective covering over<br />

vulnerable components. Fit nozzles and open ends<br />

with plastic enclosures.<br />

PART 2 - PRODUCTS<br />

2.01 CHILLER MATERIALS AND COMPONENTS<br />

A. General: Install and commission, as shown on the<br />

schedules and plans, factory assembled, charged,<br />

and tested air cooled scroll compressor chiller(s) as<br />

specified herein. Chiller shall be designed, selected,<br />

and constructed using a refrigerant with Flammability<br />

rating of “1”, as defined by ANSI/ASHRAE STANDARD<br />

- 34 Number Designation and Safety Classification of<br />

Refrigerants. Chiller shall include, but is not limited<br />

to: a complete system with a single refrigerant circuit<br />

35 tons (123kW) and below, and not less than two<br />

refrigerant circuits above 35 tons (123kW), scroll compressors,<br />

direct expansion type evaporator, air-cooled<br />

condenser, refrigerant, lubrication system, interconnecting<br />

wiring, safety and operating controls including<br />

capacity controller, control center, motor starting<br />

components, and special features as specified herein<br />

or required for safe, automatic operation.<br />

B. Cabinet: External structural members shall be constructed<br />

of heavy gauge, galvanized steel coated with<br />

baked on powder paint which, when subject to ASTM<br />

B117, 1000 hour, 5% salt spray test, yields minimum<br />

ASTM 1654 rating of “6”.<br />

C. Service Isolation valves: Service suction and discharge<br />

(ball type) isolation valves are added to unit per system.<br />

This option also includes a system high-pressure<br />

relief valve in compliance with ASHRAE15. (Factorymounted.)<br />

D. Pressure Transducers and Readout Capability<br />

D. Warranty: Manufacturer shall Warrant all equipment<br />

1. Discharge Pressure Transducers: Permits unit to<br />

and material of its manufacture against defects in<br />

sense and display discharge pressure.<br />

64 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

2. Suction Pressure Transducers: Permits unit to<br />

sense and display suction pressure.<br />

2.02 COMPRESSORS<br />

Compressors: Shall be hermetic, scroll-type, including:<br />

1. Compliant design for axial and radial sealing<br />

2. Refrigerant flow through the compressor with<br />

100% suction cooled motor.<br />

3. Large suction side free volume and oil sump to<br />

provide liquid handling capability.<br />

4. Compressor crankcase heaters to provide extra<br />

liquid migration protection.<br />

5. Annular discharge check valve and reverse vent<br />

assembly to provide low-pressure drop, silent<br />

shutdown and reverse rotation protection.<br />

6. Initial Oil charge.<br />

7. Oil Level sightglass.<br />

8. Vibration isolator mounts for compressors.<br />

9. Brazed-type connections for fully hermetic refrigerant<br />

circuits.<br />

10. Compressor Motor overloads capable of monitoring<br />

compressor motor current. Provides extra<br />

protection against compressor reverse rotation,<br />

phase-loss and phase imbalance<br />

2.03 REFRIGERANT CIRCUIT COMPONENTS<br />

Each refrigerant circuit shall include: liquid line shutoff<br />

valve with charging port, low side pressure relief device,<br />

filter-drier, solenoid valve, sight glass with moisture<br />

indicator, thermostatic expansion valves, and flexible,<br />

closed-cell foam insulated suction line and suction pressure<br />

transducer.<br />

2.04 HEAT EXCHANGERS<br />

A. Evaporator: <strong>YLAA</strong><br />

1. Direct expansion type with refrigerant inside high<br />

efficiency copper tubes, chilled liquid forced over<br />

the tubes by brass baffles.<br />

2. Constructed, tested, and stamped in accordance<br />

with applicable sections of ASME pressure vessel<br />

code for minimum 450 psig (3103 kPa)refrigerant<br />

side design working pressure and150 PSIG (1034<br />

kPa) water side design working pressure.<br />

3. Shell covered with 3.4” (19mm), flexible, closed<br />

cell insulation, thermal conductivity of 0.26k ([BTU/<br />

HR-Ft2 -°F]/in.) maximum. Water nozzles with<br />

grooves for mechanical couplings, and insulated<br />

by Contractor after pipe installation.<br />

4. Provide vent and drain fittings, and thermostatically<br />

controlled heaters to protect to -20°F (29°C)<br />

ambient in off-cycle.<br />

jOHNSON CONTROLS<br />

B. Air Cooled Condenser:<br />

1. Coils: Coils: Internally enhanced, seamless copper<br />

tubes, mechanically expanded into aluminum<br />

alloy fins with full height collars. Subcooling coil<br />

an integral part of condenser. Design working<br />

pressure shall be650 PSIG (45 bar).<br />

2. Low Sound Fans Shall be dynamically and statically<br />

balanced, direct drive, corrosion resistant<br />

glass fiber reinforced composite blades molded<br />

into a low noise, full-airfoil cross section, providing<br />

vertical air discharge and low sound. Each<br />

fan in its own compartment to prevent crossflow<br />

during fan cycling. Guards of heavy gauge, PVC<br />

(polyvinylchloride) coated or galvanized steel.<br />

3. Fan Motors: High efficiency, direct drive, 6 pole,<br />

3 phase, insulation class “F”, current protected,<br />

Totally Enclosed Air-Over (TEAO), rigid mounted,<br />

with double sealed, permanently lubricated, ball<br />

bearings.<br />

2.05 CONTROLS<br />

A. General: Automatic start, stop, operating, and protection<br />

sequences across the range of scheduled conditions<br />

and transients.<br />

B. Microprocessor Enclosure: Rain and dust tight NEMA<br />

3R/12 (IP55) powder painted steel cabinet with hinged,<br />

latched, and gasket sealed door.<br />

C. Microprocessor Control Center:<br />

1. Automatic control of compressor start/stop, anticoincidence<br />

and anti-recycle timers, automatic<br />

pumpdown shutdown, condenser fans, evaporator<br />

pump, evaporator heater, unit alarm contacts,<br />

and chiller operation from 0°F to 125°F (-18°C to<br />

52°C) ambient. Automatic reset to normal chiller<br />

operation after power failure.<br />

2. Remote water temperature reset via a Pulse Width<br />

Modulated (PWM) input signal or up to two steps<br />

of demand (load) limiting.<br />

3. Software stored in non-volatile memory, with<br />

programmed setpoints retained in lithium battery<br />

backed real time clock (RTC) memory for minimum<br />

5 years.<br />

4. Forty character liquid crystal display, descriptions<br />

in English (or Spanish, French, Italian, or German),<br />

numeric data in English (or Metric) units.<br />

Sealed keypad with sections for Setpoints, Display/Print,<br />

Entry, Unit Options & clock, and On/Off<br />

Switch.<br />

5. Programmable Setpoints (within Manufacturer<br />

limits): display language; chilled liquid temperature<br />

setpoint and range, remote reset temperature<br />

65


Guide Specifications – continued<br />

range, set daily schedule/holiday for start/stop,<br />

manual override for servicing, low and high ambient<br />

cutouts, number of compressors, low liquid<br />

temperature cutout, low suction pressure cutout,<br />

high discharge pressure cutout, anti-recycle timer<br />

(compressor start cycle time), and anti-coincident<br />

timer (delay compressor starts).<br />

6. Display Data: Return and leaving liquid temperatures,<br />

low leaving liquid temperature cutout<br />

setting, low ambient temperature cutout setting,<br />

outdoor air temperature, English or metric data,<br />

suction pressure cutout setting, each system<br />

suction pressure (optional on YCAL0014-0060<br />

models), discharge pressure (optional), liquid<br />

temperature reset via a YORK ISN DDC or Building<br />

Automation System (by others) via a 4-20milliamp<br />

or 0-10 VDC input or contact closure with<br />

optional BAS interface, anti-recycle timer status<br />

for each compressor, anti-coincident system start<br />

timer condition, compressor run status, no cooling<br />

load condition, day, date and time, daily start/stop<br />

times, holiday status, automatic or manual system<br />

lead/lag control, lead system definition, compressor<br />

starts/operating hours (each), status of hot gas<br />

valves, evaporator heater and fan operation, run<br />

permissive status, number of compressors running,<br />

liquid solenoid valve status, load & unload<br />

timer status, water pump status.<br />

7. System Safeties: Shall cause individual compressor<br />

systems to perform auto shut down; manual<br />

reset required after the third trip in 90 minutes.<br />

Includes: high discharge pressure, low suction<br />

pressure, high pressure switch, and motor protector.<br />

Compressor motor protector shall protect<br />

against damage due to high input current or thermal<br />

overload of windings.<br />

8. Unit Safeties: Shall be automatic reset and cause<br />

compressors to shut down if low ambient, low<br />

leaving chilled liquid temperature, under voltage,<br />

and flow switch operation. Contractor shall provide<br />

flow switch and wiring per chiller manufacturer<br />

requirements.<br />

9. Alarm Contacts: Low ambient, low leaving chilled<br />

liquid temperature, low voltage, low battery, and<br />

(per compressor circuit): high discharge pressure,<br />

and low suction pressure.<br />

D. Manufacturer shall provide any controls not listed<br />

above, necessary for automatic chiller operation. Mechanical<br />

Contractor shall provide field control wiring<br />

necessary to interface sensors to the chiller control<br />

system.<br />

2.06 POWER CONNECTION AND DISTRIBUTION<br />

A. Power Panels:<br />

1. NEMA 3R/12 (IP55) rain/dust tight, powder<br />

painted steel cabinets with hinged, latched, and<br />

gasket sealed outer doors. Provide main power<br />

connection(s), control power connections, compressor<br />

and fan motor start contactors, current<br />

overloads, and factory wiring.<br />

2. Power supply shall enter unit at a single location,<br />

be 3 phase of scheduled voltage, and connect<br />

to individual terminal blocks per compressor.<br />

Separate disconnecting means and/or external<br />

branch circuit protection (by Contractor) required<br />

per applicable local or national codes.<br />

B. Compressor, control and fan motor power wiring shall<br />

be located in an enclosed panel or routed through<br />

liquid tight conduit.<br />

2.07 ACCESSORIES AND OPTIONS<br />

Some accessories and options supercede standard product<br />

features. Your YORK representative will be pleased<br />

to provide assistance.<br />

A. Microprocessor controlled, Factory installed Across<br />

the-Line type compressor motor starters as standard.<br />

B. Outdoor Ambient Temperature Control<br />

1. Low Ambient Control: Permits unit operation to<br />

0°F ambient. Standard unit controls to 25°F ambient.<br />

2. High Ambient Control: Permits unit operation<br />

above 115°F ambient.<br />

C. Power Supply Connections:<br />

1. Single Point Power Supply: Single point Terminal<br />

Block for field connection and interconnecting wiring<br />

to the compressors. Separate external protection<br />

must be supplied, by others, in the incoming<br />

power wiring, which must comply with the National<br />

Electric Code and/or local codes.<br />

2. Single Point or Multiple Point Disconnect: Single<br />

or Dual point Non-Fused Disconnect(s) and lockable<br />

external handle (in compliance with Article<br />

440-14 of N.E.C.) can be supplied to isolate the<br />

unit power voltage for servicing. Separate external<br />

fusing must be supplied, by others, in the in<br />

coming power wiring, which must comply with the<br />

National Electric Code and/or local codes.<br />

3. Single Point Circuit Breaker: Single point Terminal<br />

Block with Circuit Breaker and lockable external<br />

handle (in compliance with Article 44014 of<br />

66 jOHNSON CONTROLS


FORM 150.62-EG5 (108)<br />

N.E.C.) can be supplied to isolate power voltage<br />

for servicing. Incoming power wiring must comply<br />

with the National Electric Code and/or local<br />

codes.<br />

E. Control Power Transformer: Converts unit power voltage<br />

to 120-1-60 (500 VA capacity). Factory-mounting<br />

includes primary and secondary wiring between the<br />

transformer and the control panel.<br />

F. Condenser Coil Environmental Protection:<br />

1. Post-Coated Dipped: Dipped-cured coating on<br />

condenser coils for seashore and other corrosive<br />

applications (with the exception of strong alkalis,<br />

oxidizers, and wet bromine, chlorine and fluorine<br />

in concentrations greater than 100ppm).<br />

H. Protective Chiller Panels (Factory or Field Mounted)<br />

1. Louvered Panels (condenser coils only):Painted<br />

steel as per remainder of unit cabinet, over external<br />

condenser coil faces.<br />

2. Wire Panels (full unit): Heavy gauge, welded wiremesh,<br />

coated to resist corrosion, to protect condenser<br />

coils from incidental damage and restrict<br />

unauthorized access to internal components.<br />

3. Louvered Panels (full unit): Painted steel as per<br />

remainder of unit cabinet, to protect condenser<br />

coils from incidental damage, visually screen<br />

internal components, and prevent unauthorized<br />

access to internal components.<br />

4. Louvered/Wire Panels: Louvered steel panels on<br />

external condenser coils painted as per remainder<br />

of unit cabinet. Heavy gauge, welded wire-mesh,<br />

coated to resist corrosion, around base of machine<br />

to restrict unauthorized access.<br />

5. End Louver (Hail Guard): Louvered steel panels<br />

on external condenser coil faces located at the<br />

ends of the chiller.<br />

I. Flow Switch (Field-mounted): Vapor proof SPDT,<br />

NEMA 4X switch ( ___150 PSIG or ___300 PSIG),<br />

-20°F to 250°F.<br />

J. Differential Pressure Switch: Alternative to an above<br />

mentioned flow switch. Pretempco model DPS300A-<br />

P40PF-82582-5 (300 psi max. working pressure)<br />

SPDT 5 amp 125/250VAC switch, Range 0 - 40 PSID,<br />

deadband 0.5 - 0.8 psi, with 1/4” NPTE Pressure Connections.<br />

K. Evaporator options:<br />

1. Provide 1-1/2”” cooler insulation in lieu of standard<br />

3/4”.<br />

2. Provide DX Cooler with 300 PSIG water-side design<br />

working pressure in lieu of standard 150 PSIG.<br />

3. Provide Raised Face Flanges for field installation<br />

on cooler nozzles and field piping:<br />

a. 150 PSIG, welded Flanges.<br />

b. 300 PSIG, welded Flanges.<br />

L. Remote Cooler: Manufacturer shall provide separately:<br />

chiller less evaporator, leaving and return water sensors,<br />

and liquid line components (solenoid valves, filter<br />

driers, sight glasses, and TXVs), as discrete elements<br />

of a complete factory system. Contractor shall be field<br />

erect system and provide interconnecting refrigerant<br />

piping and wiring in accordance with Manufacturer<br />

recommendations, and project plans and schedules.<br />

Where not otherwise specified, Contractor provided<br />

system piping shall be in accordance with applicable<br />

sections of ASHRAE Handbook.<br />

M. Hot Gas By-Pass: Permits continuous, stable operation<br />

at capacities below the minimum step of unloading to<br />

as low as 5% capacity (depending on both the unit &<br />

operating conditions) by introducing an artificial load<br />

on the cooler. Hot gas by-pass is installed on only one<br />

refrigerant circuit.<br />

N. Microprocessor Membrane Keypad Graphics on in lieu<br />

of Standard English:<br />

1. French language.<br />

2. German language.<br />

3. Spanish language.<br />

O. Thermal Storage: Leaving chilled liquid setpoint range<br />

for charge cycle from 25°F to 20°F minimum, with<br />

automatic reset of the leaving brine temperature up<br />

to 40°F above the setpoint.<br />

P. Low Temperature Process Brine: Leaving chilled liquid<br />

setpoint range 20°F to 50°F.<br />

Q. Chicago Code Relief Valves to meet Chicago Code<br />

requirements.<br />

R. Building Automation System (EMS) Reset Interface:<br />

Chiller to accept 4 to 20mA, 0 to 10 VDC, or discrete<br />

contact closure input to reset the leaving chilled liquid<br />

temperature.<br />

S. OptiView Remote Control Panel (Field-mounted):<br />

Graphical interface panel to remotely control and<br />

monitor up to 8 different units.<br />

jOHNSON CONTROLS<br />

67


T. Multi-Unit Sequencing Panel (Field-mounted): Separate<br />

Sequencing control center is provided to permit<br />

control of up to eight chillers in parallel based on mixed<br />

liquid temperature.<br />

U. Sound Reduction (Factory-mounted):<br />

1. Ultra Quiet - Low speed, reduced noise fans<br />

2. Compressor Acoustic Sound Blankets<br />

3. Compressor Acoustic Enclosure<br />

V. Vibration Isolation (Field-mounted):<br />

1. Neoprene Pad Isolators.<br />

2. 1 Inch Deflection Spring Isolators: Level adjustable,<br />

spring and cage type isolators for mounting<br />

under the unit base rails.<br />

3. 2 Inch Deflection Seismic Isolators: Level adjustable,<br />

restrained mounts in rugged welded steel<br />

housing with vertical and horizontal limit stops.<br />

Housings shall be designed to withstand a minimum<br />

1.0g accelerated force in all directions to 2<br />

inches.<br />

PART 3 – EXECUTION<br />

3.01 INSTALLATION<br />

A. General: Rig and Install in full accordance with Manufacturers<br />

requirements, Project drawings, and Contract<br />

documents.<br />

B. Location: Locate chiller as indicated on drawings, including<br />

cleaning and service maintenance clearance<br />

per Manufacturer instructions. Adjust and level chiller<br />

on support structure.<br />

C. Components: Installing Contractor shall provide and<br />

install all auxiliary devices and accessories for fully<br />

operational chiller.<br />

D. Electrical: Coordinate electrical requirements and connections<br />

for all power feeds with Electrical Contractor<br />

(Division 16).<br />

E. Controls: Coordinate all control requirements and<br />

connections with Controls Contractor.<br />

F. Finish: Installing Contractor shall paint damaged and<br />

abraded factory finish with touch-up paint matching<br />

factory finish.<br />

Form 150.62-EG5 (108)<br />

Supersedes: 150.62-EG5 (1107)<br />

File in ET2 Manual